Note:
Once a year the edges of the heat exchanger plates are to be checked for cleanliness and damage.
The damper blades are fitted with synthetic bearings requiring no lubrication. Air-tightness of the damper, when the damper motor is in
the closed position, must be visually checked once a year. The damper motor is to be adjusted if the damper does not close tightly.
M.5.3
Energy recovery wheel
The energy wheel is to be checked at least once a year to ensure that it can turn freely and easily. This can be done by removing the
belt drive at the motor and then turning the rotor manually with a hand on the peripheral wheel casing. At the same time the leather
seals are to be checked for damage. The bearings are factory lubricated and do not require any service lubrication. During operation the
wheel can become dirty. The wheel can be cleaned by blowing through with compressed air.
M.5.4
Cross flow exchanger
If there is dust on the edges of the plates, remove it with a soft brush. If grease or other such substances are present, then the edges
must be washed using grease dissolving detergents.
M.5.5
By-pass damper
The damper blades are fitted with synthetic bearings requiring no lubrication. Each damper blade is connected by a pivoting system. The
steel rods and brass bushes do not require lubrication. Air-tightness of the dampers, when the damper motor is in the closed position,
must be visually checked once a year. The damper motor is to be adjusted if the damper does not close tightly.
M.5.6
Condensate water drain
At least once a year the drip tray beneath the heat exchanger, as well as the drain and the water trap must be cleaned. Take care
that there is sufficient water in the water trap. If a droplet eliminator has been fitted, this must be checked once a year and cleaned if
necessary.
Demount this type of water trap for careful cleaning.
M.5.7
Heating coil
After an extended running period (normally a few years) dust particles can accumulate on the surface of the coil. This can reduce the
efficiency of the coil. Cleaning must be carried out with the utmost care to ensure that the coil fins are not damaged. The piping system
must be vented once a year as air in the system can significantly reduce the capacity of the coil.
Check that the frost protection system is fully operational. A coil may burst due to frost if the frost protection system is not operational.
M.5.8
Cooling coil
Once a year clean the drip tray beneath the cooling coil, as well as the drain and the water trap. Take care that there is sufficient water
in the water trap. If a droplet eliminator has been fitted to the cooling coil, this must be checked once a year and cleaned if necessary.
M.5.9
Electric heater
Check that the built-in safety thermostat with an automatic reset function and the overheat thermostat with manual resetting are fully
operational.
42
| Adjustment and maintenance operations
Содержание Geniox 10
Страница 2: ...Geniox Air Handling Unit User Manual 3060386...
Страница 6: ...Geniox Air Handling Unit User Manual 3060386...
Страница 35: ...3060386 Geniox Air Handling Unit User Manual Star up adjustments use and commissioning 29...
Страница 51: ...Annex Geniox Air handling unit User Manual EN Document in original language Part number of this manual 3060386...
Страница 61: ...3060386 Geniox Air Handling Unit User Manual ERW maintenance 4 8...
Страница 62: ...Geniox Air Handling Unit User Manual 3060386 5 1 Roof curb master tables...
Страница 63: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 2...
Страница 64: ...Geniox Air Handling Unit User Manual 3060386 5 3 Roof curb master tables...
Страница 65: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 4...
Страница 66: ...Systemair NA 8 Rouse Street Tillsonburg ON N4G 5W8 Toll free 800 688 6363...