3060386 | Geniox Air Handling Unit - User Manual
Star-up, adjustments, use and commissioning | 31
H.4.9
Space pressure sensor
When room/space pressure control is requested, a differential pressure sensor will be shipped for installation in the field. The pressure
sensor will be required to be installed according to the manufacturer’s instruction.
H.4.10
Damper actuators
The units will be provided with a modulating damper motor with spring return function. They are powered by a 24 VAC signal and are
controlled by a 2-10 VDC signal.
H.4.11
Room/Space temperature sensors
Room/Space temperature sensor are also available for units that require space temperature maintenance/conditioning rather than
discharge/supply air temperature maintenance.
H.4.12
Frost protection
For the frost protection of the heating coil, the entering air temperature on the coil will be monitored. If the coil’s averaging bulb
temperature drops below threshold, the fans stop, dampers close and energy recovery wheel, if available, will be turned off.
H.4.13
Economizer mode
An outdoor temperature sensor has been installed inside the unit. The outdoor temperature is used to determine if economizer
functionality is available.
H.4.14
Energy recovery wheel (ERW)
The ERW capacity is controlled by modulating the speed of the rotor. This is controlled by a frequency converter that requires a 24 VAC
enable signal and a 0-10VDC analog speed control signal.
H.4.15
Set-up for Yaskawa VFD V1000-Z1000 for Geniox units with AC fans
C6-02: Carrier Frequency Selection (Hz): 4 (10kHz)
E1-01: Line Voltage: From Motor Name Plate
E1-04: Maximum Output Frequency: According to Fan Speed Production Report
E2-01: Motor Full Load Amps (A): According to motor name-plate
E2-02: Slip: According to motor name-plate
E2-03: Motor No Load Amps (A): According to motor name-plate
E2-11: Motor Power (KW): From Motor Name Plate
H3-03: Top Speed (%): 100
H3-04: Low Speed (%):
0% L4-06: Frequency Reference: 0
O4-17: Set Date and Time: 1
H.4.16
Set-up for Yaskawa V1000-Z1000 for Geniox units used for recovery wheel
C6-02: Carrier Frequency Selection (Hz): 3 (7.5 kHz)
E1-01: Line Voltage: From Motor Name Plate
E2-11: Motor Power (KW): From Motor Name Plate
L4-06: Frequency Reference: 0
E1-03: Starting Torque: B
E2-01: Motor Full Load Amps (A): According to motor name-plate
E2-02: Slip: According to motor name-plate
E2-03: Motor No Load Amps (A): According to motor name-plate
H3-03: Top Speed (%): Varies based on wheel size and enthalpy vs sensible wheel
H3-04: Low Speed (%): 0%
O4-17: Set Date and Time: 1
Содержание Geniox 10
Страница 2: ...Geniox Air Handling Unit User Manual 3060386...
Страница 6: ...Geniox Air Handling Unit User Manual 3060386...
Страница 35: ...3060386 Geniox Air Handling Unit User Manual Star up adjustments use and commissioning 29...
Страница 51: ...Annex Geniox Air handling unit User Manual EN Document in original language Part number of this manual 3060386...
Страница 61: ...3060386 Geniox Air Handling Unit User Manual ERW maintenance 4 8...
Страница 62: ...Geniox Air Handling Unit User Manual 3060386 5 1 Roof curb master tables...
Страница 63: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 2...
Страница 64: ...Geniox Air Handling Unit User Manual 3060386 5 3 Roof curb master tables...
Страница 65: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 4...
Страница 66: ...Systemair NA 8 Rouse Street Tillsonburg ON N4G 5W8 Toll free 800 688 6363...