3060386 | Geniox Air Handling Unit - User Manual
Instruction for unloading on the site as well as installation and connection | 21
G.3 Installation - electrical
G.3.1
Description
Electrical installations must comply with the current electrical standards of the region the unit is to be installed.
Locate unit wiring diagrams inside. Refer to the unit wiring diagrams for position of components, wiring, connection point, and fuse
size information. Refer to the unit nameplate for specific electrical information, such as voltage, maximum circuit ampacity (MCA) and
maximum overcurrent protection (MOP).
G.3.2
Wiring diagrams
The wiring diagrams are printed in separate manuals delivered with the units.
The wiring diagram includes:
• General description, Circuit diagrams, Cabinet layout, Terminal matrix and Cable plan.
G.3.3
Installation of main power supply
The power supplied to the unit shall be one of: 208V/3Ph/60Hz, 460V/3Ph/60Hz or 575V/3Ph/60Hz. Refer to the unit nameplate to
determine correct voltage required. All units are shipped with a disconnect, even if we do not supply an electrical panel.
The unit must be electrically protected in accordance to CSA-22.2 No.236-11.
Correct phase sequence is critical to the operation of the unit. A label is installed on the control panel showing correct phase sequence.
G3.3.1 120V Lighting Circuit with 15Amp GFI Option
The 120V/1Ph/60Hz Lighting circuit will be powered by the client with a 15 Amp Circuit (Breaker or Fuse). It will be connected to a
120V/1Ph/60Hz Off/On 15Amp Light Switch mounted in a PVC blank box with a weather tight VSC15/10 Weather Proof Light Switch
cover. The light switch wired in parallel with the 120V/1Ph/60Hz marine style lights with cage having an energy efficient 15W LED A19
E26 base 66190 Lamp with a temperature range of -20 to 45 C.
The 15Amp GFI Duplex self-test with LED receptacle is separate 120V/1Ph/60Hz Power supplied by the client. The receptacle are in a
weatherproof PVC blank box and a WGF15/10 GFI cover install to protect the weatherproof the receptacle. The GFI receptacle assembly
are on the outside of the AHU casing approximately 18 inches from the bottom of the AHU base.
G3.3.2 Units with Electric Heaters
Units with Electric Heaters (If applicable to the configuration) come with:
I. Standard magnetic contactors
II. Standard automatic thermal cutouts (standard) or manual thermal cutouts (when required by Electrical Code (Canada or US));
III. Option Fixed or adjustable airflow switch
IV. Standard Control transformer with secondary fuse
V. Standard fuse holder for power to the Geniox Control Panel
VI. Standard Internal wiring for the number of stages indicated
VII. Standard Non Fused Disconnect switch with sub fusing
The integrated disconnect takes the place of a standard disconnect otherwise supplied with the unit.
G.3.3.3
Necessary mains power supply for Geniox units with cabinet/control system
Necessary mains power supply is printed on the unique nameplate installed on each Geniox unit.
Содержание Geniox 10
Страница 2: ...Geniox Air Handling Unit User Manual 3060386...
Страница 6: ...Geniox Air Handling Unit User Manual 3060386...
Страница 35: ...3060386 Geniox Air Handling Unit User Manual Star up adjustments use and commissioning 29...
Страница 51: ...Annex Geniox Air handling unit User Manual EN Document in original language Part number of this manual 3060386...
Страница 61: ...3060386 Geniox Air Handling Unit User Manual ERW maintenance 4 8...
Страница 62: ...Geniox Air Handling Unit User Manual 3060386 5 1 Roof curb master tables...
Страница 63: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 2...
Страница 64: ...Geniox Air Handling Unit User Manual 3060386 5 3 Roof curb master tables...
Страница 65: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 4...
Страница 66: ...Systemair NA 8 Rouse Street Tillsonburg ON N4G 5W8 Toll free 800 688 6363...