SystemAir fantech ECHO 2800Xi Series Скачать руководство пользователя страница 4

7

6

Installing the BYPASS module (BPM1434 module) accessory

Through normal operation and including defrost mode, the HRV/ERV may produce some condensation. This water should flow into a nearby drain, or 
be taken away by a condensate pump. The HRV/ERV and all condensate lines must be installed in a space where the temperature is maintained 
above the freezing point. A “P” trap should be made in the drain line. This will prevent odors from being drawn back up into the unit.

Install the drain hose, making a “P” trap

Installing Drain Line

The unit has hinged access doors on the front and removable panels on the back. The front left and right access doors are hinged for easy access to 
the filters, exchanger and fan motors while the back left and right panels are fastened to the unit. 
When facing the front access doors the outdoor and exhaust air duct connections are on the left side of the unit and the supply and return air duct 
connections are on the right side of the unit. If this factory configuration is not suitable for the HRV/ERV designated space, the front access doors 
and back panels are interchangeable in order to get an alternate configuration for duct connections as shown below.

Factory configuration (left). Configuration can be reversed on site for alternate duct layout (right)

Port configuration

Outdoor and 
Exhaust Air

Outdoor and 
Exhaust Air

Supply and 
Return Air

Supply and 
Return Air

The BPM module accessory is an insulated recirculation damper box that is mounted on the side of the unit, over the outdoor air duct connection of the 
unit. It extends the outdoor air duct connection and has another duct connection for recirculating indoor tempered air.

The purpose of the BPM1434 module accessory is to offer an alternative exchanger defrost method. Instead of the default timed based exhaust defrost 
that can cause depressurization of the ventilated space in some especially tight building envelops, the BPM module can recirculate tempered indoor air 
through the supply air stream during defrost. See the “Exchanger defrost” section for more details.

The BPM module accessory can also be used to recirculate indoor air when ventilation is not required. See the “Recirculation” section for more details.

If a BPM module accessory has been supplied with the unit it should be installed as per the provided installation manual that comes with 
the accessory.

The unit control has a dedicated 24VAC digital output to energize the BPM module. See the “Wiring the dampers & the BPM module actuators” section 
for more information on wiring the BPM module.

Weather hoods, louvers, ducts and dampers

The outdoor air intake weather hood or louver must be positioned well away from any source of contamination. The outdoor air intake and the exhaust 
air weather hoods or louvers must be adequately spaced, 10 feet (3 m) apart minimum, to prevent cross-contamination. They must be located such 
that they are high enough off the ground or other horizontal surfaces, 18 inches (460 mm) minimum, to be clear of any snow accumulation or other 
possible obstructions or as required per local building code.

In order to minimize the friction losses, the open area of the weather hoods or louvers must be adequate for the required airflow of the ventilation 
system. It is recommended that the velocity through the open area of a weather hood or louver be kept below 500 FPM (2.5 m/s) to minimize the rain 
water entrainment.

The weather hoods or louvers must have a screen with 1/4 inch (6 mm) mesh to prevent birds and rodents from entering the ductwork. Do not use 
smaller mesh as it may be more susceptible to getting clogged. 

The outside perimeter of weather hoods or louvers must be adequately sealed to prevent leakage into the building envelop.  

The ducts should be fabricated of galvanized sheet metal. In order to minimize the friction losses, ductwork should be sized adequately and be kept 
short with as few bends or elbows as possible. Favor 45° elbows over 90° elbows and use “Y” tees over standard 90° tees if possible. Account for 
dampers and/or other duct mounted accessories as part of the duct design. 

All duct joints must be fastened and sealed with proper duct sealant to minimize air leakage. 

Ducts connecting the unit to the outside weather hoods should be adequately insulated in order to prevent any condensate to form on the surface of the 
ducts.

Installation 

 (Cont'd)

Installation 

 (Cont'd)

K (Drain 2x)

in

mm

3/4 NPT  19 NPT

Содержание fantech ECHO 2800Xi Series

Страница 1: ...on of the National Building Code and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components a...

Страница 2: ...d with BPM module only 21 o Extended running 23 o Fire alarm 26 o External switch 26 Alarm handling 27 Configuring BACnet MS TP port 1 29 Maintenance 31 Limited warranty 32 Parts list 33 The key to pr...

Страница 3: ...clothes dryer kitchen exhaust hoods combustion venting central vacuum system These appliances may cause lint dust or grease to collect in the HRV ERV damaging the unit Location The HRV ERV must be pr...

Страница 4: ...used to recirculate indoor air when ventilation is not required See the Recirculation section for more details If a BPM module accessory has been supplied with the unit it should be installed as per...

Страница 5: ...ned and sealed to the ducts with proper duct sealant to minimize air leakage Dampers fitted to the ductwork connecting the unit to the outside weather hoods should be adequately insulated in order to...

Страница 6: ...esponsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended The amount of air CFM that an HRV ERV will deliver is directly re...

Страница 7: ...he return air side and can be accessed by opening the larger hinged access panel Pressure transducer modules Each module has two 2 pressure transducer The first pressure transducer on the PTE module m...

Страница 8: ...nting holes 8 Connection block 9 Connection to yellow cable 10 Connection to orange cable 11 Connection to red cable 12 Connection to brown cable 13 Connection to black cable Supplied Cable 10 12 11 1...

Страница 9: ...hanges from stopped to starting up 2 The digital outputs for the fresh air damper and the exhaust air damper are activated 3 The exhaust air fan and the supply air fan will start after a preset time N...

Страница 10: ...e and time follow the steps below Time settings schedule 1 Time settings Go to Time settings by using the UP DOWN arrow buttons Select by pressing the RIGHT arrow button Temperature Air Control Time s...

Страница 11: ...be done when ventilation is not required during a certain period but air circulation is desired Recirculation units equipped with the BPM module only To have the recirculation mode controlled by a dig...

Страница 12: ...ow button Manual Auto Settings Configuration Access rights Once the input has been set the recirculation mode can be configured 3 Recirculation Using the UP DOWN arrow buttons locate the use extra tim...

Страница 13: ...cess the fields and set values Extended running 0 min Set the time value for extended running to remain active once the extended running input goes from on to off Time in ext running 0 min This field...

Страница 14: ...ing the UP DOWN arrow buttons Select by pressing the RIGHT arrow button AI DI UI AO Alarm handling The unit controller comes with preprogrammed alarms to ensure it functions properly and to help troub...

Страница 15: ...isplay Follow the steps below to handle active alarms 1 Access the alarm log Press the alarm button to access the alarm log when the red LED is flashing to indicate that an alarm has been triggered On...

Страница 16: ...n a large sink bathtub or shower 5 Pour clean tap water through the face of the core facing upward until it runs clear Ensure the entire surface is rinsed 6 Rotate the core so that its other air inlet...

Страница 17: ...ges incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to supply r...

Страница 18: ...35 34 Notes Notes...

Страница 19: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Отзывы: