19

18

By monitoring the pressure drop over the inlet ring of both fans, the unit control can calculate the airflow moved by each fan using a technique based 
on the Bernoulli and continuity equations. The unit control will modulate the analog output sent to each EC fan motor in order to maintain a given 
airflow set point. Follow the steps below to enter the airflow set points of the supply and exhaust air fans.

Airflow control (CAV & airflow set points)

1 Air Control

Go to 

Air control 

by using the UP/DOWN arrow buttons. Select by 

pressing the RIGHT arrow button

Temperature

Air Control

Time settings

Access Rights

2 Flow Control SAF

From this submenu, the actual supply airflow measured is displayed 

along with the set point for the current unit operation mode. Press the 

RIGHT arrow button to access the next submenu.  

Flow control SAF

Actual:   CFM

  Setp: 

 

CFM

3 Flow Control SAF

From this submenu, the set points for normal speed (1/1) and reduced 

speed (1/2) for the supply air fan can be entered. Press the OK button to 

access the field, use the arrow buttons to set a value and press ok again 

to save the value. 

Flow control SAF

Step 1/1:   

CFM

Setp 1/2:   

CFM

4 Flow Control EAF

The same can be done for the exhaust air flow. Locate Flow control EAF 

from the air control menu and enter the EAF set points.

Flow control EAF

Actual:   CFM

  Setp: 

 

CFM

Flow control EAF

Step 1/1:   

CFM

Setp 1/2:   

CFM

 The airflow read on the unit external display is accurate to +/-5% of the measured value in a laboratory setting. According to the Field 
Performance Measurements of Fan Systems published by AMCA (AMCA 203-90), airflow field measurements typically have an uncertainty 
of up to 10%. If you are unsure of what is acceptable in your application, we recommend you contact a qualified air tester & balancer in your 
area.

The unit controller has a year-based 24h clock function. This means that a weekly schedule with holiday periods for a full year can be set. The clock 
also has an automatic daylight saving time change-over. To set the date and time follow the steps below. 

Time settings & schedule

1 Time settings

Go to 

Time settings 

by using the UP/DOWN arrow buttons. Select 

by pressing the RIGHT arrow button

Temperature

Air Control

→Time settings

Access Rights

2 Time/Date

Go to 

Time/Date

 by using the UP/DOWN arrow buttons. Select by 

pressing the RIGHT arrow button

→Time/Date

Timer normal speed

Timer reduced speed

Extended running

3 Time/Date

Press the OK button to access the field, use the arrow buttons to set 

a value and press ok again to save the value. Note the time parameter 

format is 00:00 to 24:00 

   Time: HH:MM

   Date: YYYY-MM-DD

Weekday: Sunday-Monday

Once the date and time has been set, schedules can be programmed to operate the unit in normal or reduced speed. While the normal speed schedule 
is active, the unit will run at the desired airflow set point (setp 1/1). The reduced speed schedule can be used for when a reduced airflow set point 
(setp 1/2) is desired during night, weekends or holidays for example. The normal speed schedule has precedence over the reduced speed schedule. 

Each schedule has two (2) run periods that can be set per day (i.e. run from period 1, 06:00-11:00 and from period 2, 13:00-21:00). If both periods 
for a weekday are set to 00:00-00:00 then the schedule for this day will be inactive. If either period for a weekday is set to 00:00-24:00 then the 
schedule will be active all day.

To set an operation schedule follow the steps below.

1 Timer normal speed

Access the timer normal speed submenu from the time settings menu. 

Use the UP/DOWN arrows to toggle between weekdays. Press the OK 

button to access the field, use the arrow buttons to set a value and 

press ok again to save the value. Note that the time parameter format is 

00:00 to 24:00

Normal speed

Monday

Per1: HH:MM-HH:MM

Per2: HH:MM-HH:MM

2 Timer reduced speed

Access the timer reduced speed submenu from the time settings menu. 

Use the UP/DOWN arrows to toggle between weekdays. Press the OK 

button to access the field, use the arrow buttons to set a value and 

press ok again to save the value. Note that the time parameter format is 

00:00 to 24:00

Reduced speed

Monday

Per1: HH:MM-HH:MM

Per2: HH:MM-HH:MM

Unit operation 

(Cont'd)

Unit operation 

(Cont'd)

Содержание fantech ECHO 2800Xi Series

Страница 1: ...on of the National Building Code and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components a...

Страница 2: ...d with BPM module only 21 o Extended running 23 o Fire alarm 26 o External switch 26 Alarm handling 27 Configuring BACnet MS TP port 1 29 Maintenance 31 Limited warranty 32 Parts list 33 The key to pr...

Страница 3: ...clothes dryer kitchen exhaust hoods combustion venting central vacuum system These appliances may cause lint dust or grease to collect in the HRV ERV damaging the unit Location The HRV ERV must be pr...

Страница 4: ...used to recirculate indoor air when ventilation is not required See the Recirculation section for more details If a BPM module accessory has been supplied with the unit it should be installed as per...

Страница 5: ...ned and sealed to the ducts with proper duct sealant to minimize air leakage Dampers fitted to the ductwork connecting the unit to the outside weather hoods should be adequately insulated in order to...

Страница 6: ...esponsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended The amount of air CFM that an HRV ERV will deliver is directly re...

Страница 7: ...he return air side and can be accessed by opening the larger hinged access panel Pressure transducer modules Each module has two 2 pressure transducer The first pressure transducer on the PTE module m...

Страница 8: ...nting holes 8 Connection block 9 Connection to yellow cable 10 Connection to orange cable 11 Connection to red cable 12 Connection to brown cable 13 Connection to black cable Supplied Cable 10 12 11 1...

Страница 9: ...hanges from stopped to starting up 2 The digital outputs for the fresh air damper and the exhaust air damper are activated 3 The exhaust air fan and the supply air fan will start after a preset time N...

Страница 10: ...e and time follow the steps below Time settings schedule 1 Time settings Go to Time settings by using the UP DOWN arrow buttons Select by pressing the RIGHT arrow button Temperature Air Control Time s...

Страница 11: ...be done when ventilation is not required during a certain period but air circulation is desired Recirculation units equipped with the BPM module only To have the recirculation mode controlled by a dig...

Страница 12: ...ow button Manual Auto Settings Configuration Access rights Once the input has been set the recirculation mode can be configured 3 Recirculation Using the UP DOWN arrow buttons locate the use extra tim...

Страница 13: ...cess the fields and set values Extended running 0 min Set the time value for extended running to remain active once the extended running input goes from on to off Time in ext running 0 min This field...

Страница 14: ...ing the UP DOWN arrow buttons Select by pressing the RIGHT arrow button AI DI UI AO Alarm handling The unit controller comes with preprogrammed alarms to ensure it functions properly and to help troub...

Страница 15: ...isplay Follow the steps below to handle active alarms 1 Access the alarm log Press the alarm button to access the alarm log when the red LED is flashing to indicate that an alarm has been triggered On...

Страница 16: ...n a large sink bathtub or shower 5 Pour clean tap water through the face of the core facing upward until it runs clear Ensure the entire surface is rinsed 6 Rotate the core so that its other air inlet...

Страница 17: ...ges incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to supply r...

Страница 18: ...35 34 Notes Notes...

Страница 19: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Отзывы: