SystemAir fantech ECHO 2800Xi Series Скачать руководство пользователя страница 14

27

26

4 Configuring DI5

From this submenu, use the UP/DOWN arrow buttons to locate DI5 and 

select it by pressing the RIGHT arrow button. Press OK again to access 

the 

NO/NC

 field to set the digital input contact to either normally open 

(NO) OR  normally closed (NC) based on what  will be used to trigger the 

input. 

DI5 :  

 

 

 

 

 

NO/NC: NO Signal:

Fire alarm

Status: 

Off 

     

The external switch digital input can be used to stop the unit remotely. If the external switch input is triggered the unit will initiate the stop sequence 
and stop the ventilation. A controller alarm will also appear on the unit external display to indicate that the external switch is active.  

External switch

A means of triggering the input will be required (field supplied and specified) and wired to TB3 76 & 4, DI6 & +24VDC respectively (see 
wiring diagram). Remember to cut the power to the unit at the all pole circuit breaker before performing any electrical work.

The external switch input is configured on DI6 from the factory and is set as a normally open contact (NO) by default. If you require a normally closed 
contact (NC) follow the steps below.

1 Configuration

Go to 

Configuration

 by using the UP/DOWN arrow buttons. Select by 

pressing the RIGHT arrow button

Manual/Auto

Settings

→Configuration

Access rights

2 Inputs/Outputs

Locate 

Inputs/Outputs

 submenu by using the UP/DOWN arrow 

buttons and select it by pressing the RIGHT arrow button

→Inputs/Outputs

Sensor settings

Control function

Fan control

3 DI

Go to

 DI 

by using the UP/DOWN arrow buttons. Select by pressing the 

RIGHT arrow button

AI

→DI

UI

AO

4 Configuring DI6

From this submenu, use the UP/DOWN arrow buttons to locate DI6 and 

select it by pressing the RIGHT arrow button. Press OK again to access 

the 

NO/NC

 field to set the digital input contact to either normally open 

(NO) OR  normally closed (NC) based on what  will be used to trigger the 

input. 

DI6 

      

NO/NC: NO Signal:

External switch

Status: 

Off 

     

Fire alarm 

(cont'd)

Unit operation 

(Cont'd)

External switch 

(Cont'd)

Unit operation 

(Cont'd)

3 DI

Go to

 DI 

by using the UP/DOWN arrow buttons. Select by pressing the 

RIGHT arrow button

AI

→DI

UI

AO

Alarm handling

The unit controller comes with preprogrammed alarms to ensure it functions properly and to help troubleshoot problems when they occur. Active 
alarms are indicated by the flashing red LED on the unit external display.

These alarms have different characteristics. Alarms related to safe operation of the unit (alarms class A and B) will, when triggered, stop the 
ventilation until the alarm has been acknowledged and the alarm conditions are no longer met. Alarms of lower priority (Classe C) will not stop the 
ventilation and will auto reset once the alarm conditions are no longer met. Each alarm has a delay which is the time period the alarm conditions have 
to be met before the alarm is triggered. The table below lists all the preconfigured alarms of the unit with their descriptions and other characteristics. 
See table below.

Alarm

#

Description

Stop

Auto reset

Delay

Malfunction supply air fan

1

Alarm text: Run error supply air fan
Cause: No feedback from supply air fan

Yes

No

300s (5 min)

Malfunction extract air fan 2

Alarm text: Run error extract air fan 
Cause: No feedback from extract air fan

Yes

No

300s (5 min)

Filter guard 1

6

Alarm text: Check supply air filter
Cause: Supply air filter is dirty

No

No

300s (5 min)

Fire alarm

10

Alarm text: Fire alarm
Cause: Fire alarm DI is active

Yes

No

0s

External switch

11

Alarm text: External switch
Cause: External switch DI is active

Yes 

Yes

0s

High supply air temp

15

Alarm text: High supply air temp
Cause: Supply air temp ≥ 86°F [30°C]

No

No

300s (5 min)

Low supply air temp

16

Alarm text:  Low supply air temp
Cause: Supply air temp ≤ 50°F [10°C]

Yes

No

300s (5 min)

High Extract air temp

21

Alarm text: High extract air temp
Cause: Extract air temp ≥ 86°F [30°C]

No

No

300s (5 min)

Low extract air temp

22

Alarm text: Low extract air temp
Cause: Extract air temp ≤ 50°F [10°C]

No

No

30 min

Sensor error outdoor 
temp

27

Alarm text: Sensor error outdoor temp
Cause: No signal from outdoor air sensor

No

No

5s

2 Inputs/Outputs

Locate 

Inputs/Outputs

 submenu by using the UP/DOWN arrow 

buttons and select it by pressing the RIGHT arrow button

→Inputs/Outputs

Sensor settings

Control function

Fan control

Содержание fantech ECHO 2800Xi Series

Страница 1: ...on of the National Building Code and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components a...

Страница 2: ...d with BPM module only 21 o Extended running 23 o Fire alarm 26 o External switch 26 Alarm handling 27 Configuring BACnet MS TP port 1 29 Maintenance 31 Limited warranty 32 Parts list 33 The key to pr...

Страница 3: ...clothes dryer kitchen exhaust hoods combustion venting central vacuum system These appliances may cause lint dust or grease to collect in the HRV ERV damaging the unit Location The HRV ERV must be pr...

Страница 4: ...used to recirculate indoor air when ventilation is not required See the Recirculation section for more details If a BPM module accessory has been supplied with the unit it should be installed as per...

Страница 5: ...ned and sealed to the ducts with proper duct sealant to minimize air leakage Dampers fitted to the ductwork connecting the unit to the outside weather hoods should be adequately insulated in order to...

Страница 6: ...esponsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended The amount of air CFM that an HRV ERV will deliver is directly re...

Страница 7: ...he return air side and can be accessed by opening the larger hinged access panel Pressure transducer modules Each module has two 2 pressure transducer The first pressure transducer on the PTE module m...

Страница 8: ...nting holes 8 Connection block 9 Connection to yellow cable 10 Connection to orange cable 11 Connection to red cable 12 Connection to brown cable 13 Connection to black cable Supplied Cable 10 12 11 1...

Страница 9: ...hanges from stopped to starting up 2 The digital outputs for the fresh air damper and the exhaust air damper are activated 3 The exhaust air fan and the supply air fan will start after a preset time N...

Страница 10: ...e and time follow the steps below Time settings schedule 1 Time settings Go to Time settings by using the UP DOWN arrow buttons Select by pressing the RIGHT arrow button Temperature Air Control Time s...

Страница 11: ...be done when ventilation is not required during a certain period but air circulation is desired Recirculation units equipped with the BPM module only To have the recirculation mode controlled by a dig...

Страница 12: ...ow button Manual Auto Settings Configuration Access rights Once the input has been set the recirculation mode can be configured 3 Recirculation Using the UP DOWN arrow buttons locate the use extra tim...

Страница 13: ...cess the fields and set values Extended running 0 min Set the time value for extended running to remain active once the extended running input goes from on to off Time in ext running 0 min This field...

Страница 14: ...ing the UP DOWN arrow buttons Select by pressing the RIGHT arrow button AI DI UI AO Alarm handling The unit controller comes with preprogrammed alarms to ensure it functions properly and to help troub...

Страница 15: ...isplay Follow the steps below to handle active alarms 1 Access the alarm log Press the alarm button to access the alarm log when the red LED is flashing to indicate that an alarm has been triggered On...

Страница 16: ...n a large sink bathtub or shower 5 Pour clean tap water through the face of the core facing upward until it runs clear Ensure the entire surface is rinsed 6 Rotate the core so that its other air inlet...

Страница 17: ...ges incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to supply r...

Страница 18: ...35 34 Notes Notes...

Страница 19: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Отзывы: