6
a) Hold the mounting bracket against the surface it is to be mounted.
b) Mark the location of the two most useful key slots and remove the bracket. Using the provided ¾” long wood screws, attach screws
into the structure leaving 1/8” space between the screw head and mounting surface.
c) Using the provided self-tapping screws, attach the bracket to the fan as shown.
Figure. B
d) Holding the new assembled fan and bracket, align the key slots with the mounting screws and lock them into place.
Duct Installation (STEP 4)
Leave adjoining dryer duct a minimum of 10-1/8” away from fan inlet and outlet. Install the 10” long cleanout duct using the FC4 duct
clamps. See dimensional data below.
Pressure Switch Connection (STEP 5)
Do not connect the tubing in such a manner as to allow condensation from the duct to collect in the tubing
Drill a 3/8 inch diameter hole in the duct wall 6 to 8-inches from the inlet of the fan. Carefully insert the grommet into the hole.
Drilling into a metal duct may produce sharp burrs. Needle nose pliers can be used to remove or flatten sharp edges.
a) Attach one end of the clear pressure tubing to
the pressure sensor located on the electrical
box.
b) Mark the opposite end of the pressure tubing ½
inch from the edge and insert into the grommet
until the marking is reached.
Indicator Panel (STEP 6)
The DEDPV-705 is equipped with a remote mount, low voltage, operation indicator panel. This wall-mounted indicator panel contains a
blue LED that is intended to visually alert the occupant of any detected faults. The panel must be mounted in a 2 gang decora switch
plate with a warning label (decora plate and label provided). Refer to page 3, paragraph C for the required mounting location.
Connecting Indicator Panel (STEP 7)
Connect the end of the 50-foot cable that has a mating two-position connector to the receptacle located on the dryer booster fan control
box.