background image

Appendix 5. – Bridges in controller as delivered from factory 

 

  

Bridges are factory inserted to allow test of fan without connecting control cables. 

In case of using the fan for smoke and heat extraction,

 remove the red bridge 16-17 (fire mode) and connect 

controller to fire central up to wiring scheme (10-11 at 3~ controller). 

Warning

: removing this bridge without 

connecting to fire central and running the fan in fire mode causes no protection is active. Running in fire 

mode is allowed only in case of fire or during periodical tests.

  

For fan speed setting with potentiometer replace bridge 9-10 (6-7 at 3~ controller) and connect potentiometer 

(R >= 1kΩ) according to wiring scheme. 

For fan speed setting using AN1 input (0-10V): remove bridge 9-10 (6-7 at 3~ controller) and connect 0-10V 

input according to wiring scheme. 

Replace bridge 18-19 (11-12 at 3~ controller) with start – stop switch. 

Controller default setup controls the fan speed with potentiometer or AN1 input.  

Using internal regulator for fan speed control requires change of controller setting via MODBUS (see controller 

instructions). Using MODBUS for fan speed control requires change of controller setting via MODBUS (see 

controller instructions).  

Minimum fan speed can be increased in setup via MODBUS.  

Maximum fan speed can be decreased in setup via MODBUS. 

More about settings please see controller instructions. 

1~ controller 

3~ controller 

Содержание DVG-H-EC F200

Страница 1: ...maintenance of roof fans DVG EC Appendixes 1 Mounting of service switch Mounting of vertical outlets for DVG V 3 4 Accessories mounting 5 Bridges in controller and wiring schemes Controller Compacto i...

Страница 2: ...allation 4 4 2 Safety instructions for installation commissioning maintenance and controlling 4 4 3 Installation of the fan 4 4 4 Instructions for installation 5 5 0 COMMISSIONING 6 6 0 APPROVAL 6 7 0...

Страница 3: ...he risk for this carries the operator alone 2 0 TECHNICAL DESCRIPTION Casing Electric motor with impeller is fastened to a sturdy supporting construction The casing cover is made of see water resistan...

Страница 4: ...protective guard EN 13857 After installation impeller must not be accessible anymore During installation commissioning maintenance and controlling unauthorized personal should not have access to the f...

Страница 5: ...qualified electrician In case of unprofessional connection guarantee will not be valid The risk for this carries the operator alone Observe attached detailed instructions of motor and controller suppl...

Страница 6: ...oints for leakage Check if foreign objects were left in the fan or in the connected ducts Check if protective elements are fitted Check the accuracy of the electric wiring and connections to the mains...

Страница 7: ...not deviate from the starting values at installation In case that parameters deviate the electric motor or the impeller have to be replaced or repaired This must only be done by an authorised customer...

Страница 8: ...acturer 9 0 GUARANTEE Guarantee will be valid only if transport storage installation connection and periodical maintenance have been executed in compliance with the above instructions and local regula...

Страница 9: ...age des Revisionsschalters Montage der Umlenkungsbleche bei DVG V Appendix 1 Mounting of service switch Mounting of vertical outlets for DVG V Bilaga 1 Beslag av tj nste kopplar beslag av lodlinjeutta...

Страница 10: ...Zubeh r Montage Appendix 3 Accessories mounting Bilaga 3 Tillbeh r installation 3 DVG H SSG F ASG F VKG F ASSG F DVG H VKG F ASSG F FDG F DVG H VKG F SSG F ASG F ASSG F DVG H VKG F SSGE F FDGE F ASG...

Страница 11: ...Zubeh r Montage Appendix 4 Accessories mounting Bilaga 4 Tillbeh r installation 4 DVG V SSG F ASG F VKG F ASSG F DVG V VKG F ASSG F FDG F DVG V VKG F SSG F ASG F ASSG F DVG V VKG F SSGE F FDGE F ASG...

Страница 12: ...6 7 at 3 controller and connect potentiometer R 1k according to wiring scheme For fan speed setting using AN1 input 0 10V remove bridge 9 10 6 7 at 3 controller and connect 0 10V input according to w...

Страница 13: ...DVG 355 355 EC DVG 450 EC Wiring 1 230V 50 60Hz 27 11 2013...

Страница 14: ...DVG 560 EC DVG 630 EC DVG 630 EC DVG 800 EC Wiring 3 400V 50 60Hz 27 11 2013 27 11 2013...

Страница 15: ...03 2012 DVG EC overensstammer med bestammelserna i testrapporter fran LGAI Technological Center S A Bellaterra Barcelona nr 09 100216 502 av den 12 juni 2009 och nr 11 2673 1035 av den 14 juni 2011 D...

Отзывы: