3 Refrigerant control/reporting
DVCompact DXR comes pre-filled with R410A (50% R-32/50% R-125) refrigerant.
DVCompact DXR units belong to the groups “piece units containing more than 3 kg refrigerants per circuit“
and “equipment that contains fluorinated greenhouse gases in quantities of 5 tones of CO
2
equivalent
or more” and it must be checked for leaks. Leakage control with record keeping shall be done once
per year. Refrigerant control report must be always established by a cooling certified person before
commissioning of the unit. Any quantities added or recovered during maintenance, servicing and final
disposal will need to be recorded along with:
• leak checks
• actions taken
• the name of the service Company, the engineer / technician who performed the servicing and
maintenance
• dates
• results of inspections
These records have to be made available to the competent authority upon request. Different regulations
can be valid in different countries. Check with your local government.
3.1 Amount of refrigerant in the system
Model
Amount of
refrigerant, kg
3,3
4,7
5,3
8
9,7
11,8
20,0
23
26