7 Installation

7.1 Unpacking

Verify that all ordered equipment are delivered before starting the installation. Any discrepancies from the
ordered equipment must be reported to the supplier of Systemair products.

7.2 Where to Install the Unit

The unit without roof is meant for indoor installation. The electronic components should not be exposed to
lower temperature than 0°C or higher than +50°C.

When mounting; make sure to leave enough space to access the service doors (figure 3).

Note:

If there is not sufficient space to open the inspection doors it is possible to unscrew the hinges to remove
the doors completely for inspection and maintenance.

General maintenance includes replacing the filters and removing fan motor inside the unit for cleaning.

Avoid placing the unit against a wall, as low frequency noise can cause vibrations in the wall.

The outdoor air intake of the building should if possible be put in the northern or eastern side of the building
and away from other exhaust outlets like kitchen fan outcasts or laundry room outlets. The extract air
should ideally be led out via a roof cowl away from any outdoor air intakes, windows, balconies etc.

Warning

• The door handles are lockable. Make sure that the handles are locked during operation of the unit.

• The unit must be duct connected or in some other way provided with protection so that it is not

possible to come in contact with the fans through the duct connections

7.3 Installation procedure

Warning

Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used. Use protective clothing.

1

Prepare the surface where the unit is to be mounted. Make sure that the surface is flat, levelled and
that it supports the weight of the unit.

Perform the installation in accordance with local rules and regulations.

2

Make sure that the factory mounted rubber gaskets between the sections are undamaged

DVCompact

Installation and Service

211117

9

Systemair Sverige AB

Содержание DVCompact DXR-10

Страница 1: ...atalogues brochures and other printed material UAB Systemair reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can b...

Страница 2: ...Unloading on the site 7 6 1 1 Unloading by fork lift truck 7 6 1 2 Unloading with crane 8 6 1 3 Lifting the unit mounted on a base frame 8 7 Installation 9 7 1 Unpacking 9 7 2 Where to Install the Un...

Страница 3: ...principles for design Risk assessment and risk reduction EN 13857 Safety of machinery Safety distances to prevent hazard zones being reached by upper or lower limbs EN 60 335 1 Household and similar...

Страница 4: ...splace the air and cause asphyxiation in unfavorable conditions Caution For safety reasons only personnel with relevant technical competence may perform installation work The installation instructions...

Страница 5: ...d or recovered during maintenance servicing and final disposal will need to be recorded along with leak checks actions taken the name of the service Company the engineer technician who performed the s...

Страница 6: ...and product number from the type label figure 1 Fig 1 Type label Position Description 1 Product order number 2 Product code product specification 3 Product item number production number consecutive n...

Страница 7: ...3510 1720 1720 1497 DVCompact DXR 50 970 2320 4310 2020 2020 2516 DVCompact DXR 60 1120 2320 4610 2170 2170 3309 DVCompact DXR 80 1270 24601 5050 2470 2470 3664 1 This section is split into 3 parts di...

Страница 8: ...PM Motor A DVCompact DXR 10 2 2 2 4 2 2 1 DVCompact DXR 15 3 0 3 4 2 6 2 9 DVCompact DXR 20 4 4 4 7 3 6 3 8 DVCompact DXR 25 4 4 6 0 4 7 6 4 4 6 6 3 DVCompact DXR 30 6 0 8 0 6 4 8 2 6 2 8 4 DVCompact...

Страница 9: ...emoved and unit covered with tarpaulin or similar materials In order to minimize condensation sufficient air circulation must be ensured between the covering and the unit During transportation the uni...

Страница 10: ...on 6 1 3 Lifting the unit mounted on a base frame When lifting the unit mounted on the base frame with holes use metal tubes inserted through the holes in the frame and suspend the unit by soft cables...

Страница 11: ...ng should if possible be put in the northern or eastern side of the building and away from other exhaust outlets like kitchen fan outcasts or laundry room outlets The extract air should ideally be led...

Страница 12: ...m size 50 don t have the disc lock system Their sections are fitted together by the use of internal triangular brackets that are fitted from factory figure figure 5 Danger Make sure that the Mains sup...

Страница 13: ...t figure 4 See wiring diagram for more information Other temperature sensors are built in to the unit from factory Fig 4 Installed supply air sensor 7 4 2 Installation of VAV models If the unit is del...

Страница 14: ...ped with traps with same diameter as the drain pipe Fig 6 Drain trap Positive pressure Positive pressure Pa H1 Min mm H2 mm 500 90 65 750 120 90 1000 150 120 Fig 7 Drain trap Negative pressure Negativ...

Страница 15: ...wn cable 7 Connection to black cable 7 5 Electrical connections Danger All electrical connections must be carried out in accordance with local rules and regulations Make sure that the power supply to...

Страница 16: ...s A and heat pump section pos B The unit must not be put into operation before all the electrical safety precautions have been read and understood See the enclosed wiring diagram for internal and exte...

Страница 17: ...51 52 53 LON 57 58 59 RS 485 contact and Exo line via TCP IP WEB are included as standard figure 9 Note RS 485 port and TCP IP port can not be used simultaneously I e possible communications are Modb...

Страница 18: ...verige AB reserves the right to make changes and improvements to the contents of this manual without prior notice Systemair UAB Lin st 101 LT 20174 Ukmerg LITHUANIA Phone 370 340 60165 Fax 370 340 601...