Transport
Do not move the device by pulling on the power cord, terminal box, impeller, safety guard or inflow duct.
Exercise caution when loading and unloading the fan for transport to prevent damage.
Use suitable hoisting devices: When using a crane, fasten the load with straps and ensure 4-point suspension.
Keep in mind during transport and loading/unloading that the fan weighs at least 80, 86 or 95 kg.
The following table shows values for orientation (weights without accessories):
Size
Weight
AJ(F)
Weight
AJR
Weight
AJ8
315-2/4
55 kg
52 kg
84 kg
355-2/4
70 kg
67 kg
90 kg
400-2/4
80 kg
85 kg
99 kg
Notice!
Attachment points:
mounting fastener, silencers on intake and pressure sides
When taking delivery on the fan, perform a visual inspection and check the equipment supplied for completeness.
Storage
Provided the original packaging is intact and there is no build-up of condensation, the jet fan can be stored in the original
packaging out of doors for up to one month. The unpacked fan must not be stored out of doors. In a dry, well ventilated
room without risk of condensation build-up, the jet fan can be stored indoors for up to 6 months.
Storage temperatures: –20 °C (–4 °F) to 60 °C (+140 °F).
Attention!
Risk of damage to the fan.
If the fan is stored longer than three months, turn the impeller by hand regularly.
Assembly
All fans are tested at the factory before shipping.
Proceed as follows after removing the packaging:
•
Check for damage sustained during transport,
•
Manually check whether the impeller turns without obstruction, and
•
Make sure no condensation has formed.
Danger!
Danger of personal injury if safety instructions are not observed.
Make sure general rules and regulations for occupational safety are observed when installing the fan.
Danger!
Danger of personal injury if the fan falls.
Make sure all parts and any areas required for preparation are inaccessible to unauthorized persons during instal-
lation.
Danger!
Danger of personal injury from electrical current.
Make sure the fan is disconnected from the power supply before making any electrical connections in the fan.
Make sure the electrical power supply cannot be inadvertently switched on while working on the fan.
All electrical connections in the fan must be made by a qualified electrician.
Size
50-4
50-4/6
50-4/8
85-4 85-4/6
85-4/8
Weight IV
in kg
105
102
105
140
141
142