60
14.4.12 Changeover
14.4.12.1 Configuration
Select one heating sequence and one cooling sequence out of the configured sequences to use with the changeover
function in the
Configuration
>
Functions
>
Function activation
>
Heating/Cooling sequence setup
>
Changeover settings
menu.
Overview:
Configuration
> ... >
Heating/Cooling sequence setup
>
Changeover settings
2021–03–01
Changeover 1
Changeover sequence for heating
Heating
Changeover sequence for cooling
Cooling
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Function activation
4. Select
Heating/Cooling sequence setup
5. Select
Changeover settings
6. Select which sequence to control the changeover function when heating as
Changeover sequence for heating
7. Select which sequence to control the changeover function when cooling as
Changeover sequence for cooling.
14.4.12.2 Allocation
Select I/O (in-output) placement of where the changeover output and feedback input are connected to the controller in
the
Configuration
>
I/O allocation settings
submenus
Digital inputs
,
Analog outputs
and
Digital
outputs
.
Overview:
Configuration
>
I/O allocation settings
>
Digital
inputs
2021–03–01
Digital inputs
Device
Position
Cooling/(Heating) changeover 1
Controller
DI4
Configuration
>
I/O allocation settings
>
Analog
outputs
2021–03–01
Analog outputs
Device
Position
Changeover 1
Controller
AO4
254051 | A001