51
14.4.9.2 Operation settings
Set up all operation parameters for the free cooling function in the
Data & Settings
>
Demand control
>
Free
cooling
menu.
Overview:
Data & Settings
>
Demand control
>
Free cooling
2021–03–01
Running when day outdoor temperature >
22 °C
Stop when night outdoor temperature >
18 °C
Stop when night outdoor temperature <
10 °C
Stop when room temperature <
18 °C
Free cooling start hour
0
Free cooling stop hour
7
Time to block heat output after free cooling
60 min
Fan-kick temperature check
180 s
Fan-kick interval time
60 min
Step by step:
1.
Select
Data & Settings
from the navigation icons
2. Select
Demand control
3. Select
Free cooling
4. Set day outdoor temperature min. limit to allow start of free cooling as
Running when day outdoor
temperature
>
5. Set outdoor temperature interval during night where free cooling is allowed as
Stop when night outdoor
temperature >/<
6. Set Room/Extract air temperature min. limit to stop free cooling
7. Set a time interval for when free cooling is allowed to run (0-24) as
Free cooling start/stop hour,
e.g. 0-7
means free cooling will run between 12 am (12:00) and 7 am (07:00) if allowed by the temperature limits)
8. Set the desired time to block heating output from the controller after free cooling
9. Set the desired fan run time for checking the outdoor temperature with an intake temperature sensor
10.Set the time delay between outdoor temperature checks with an intake temperature sensor.
254051 | A001