39
14.4.3.3 Operation settings
Adjust the fan pressure set points in the
Data & Settings
>
Fan Control
>
Fan setpoints
menu.
Overview:
Data & Settings
>
Fan control
>
Fan setpoints
2021–03–01
Setpoint low speed supply air fan
100 Pa
Setpoint low speed extract air fan
100 Pa
Setpoint normal speed supply air fan
200 Pa
Setpoint normal speed extract air fan
200 Pa
Setpoint high speed supply air fan
200 Pa
Setpoint high speed extract air fan
200 Pa
Step by step:
1.
Select
Data & Settings
from the navigation icons
2. Select
Fan control
3. Select
Fan setpoints
4. Select and adjust setpoints for the available fan speed levels.
14.4.4
Temperature control type (Room)
14.4.4.1 Activation
Activate room temperature control.
Select
Cascade room temp control
as temperature control type in the
Configuration
>
Functions
>
Func-
tion activation
menu.
Overview:
Configuration
>
Functions
>
Function activation
2021–03–01
Temperature control type
Room cascade
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Function activation
4. Select
Room cascade
as
Temperature control type
.
254051 | A001