14.4.10.2 Configuration
Configure what type of cooler is connected in the
Configuration
>
Functions
>
Function activation
>
Heat-
ing/Cooling sequence setup
>
Cooling
menu.
Overview:
Configuration
>. .. >
Heating/Cooling sequence setup
>
Cooling
2021–03–01
Type of sequence
Cooling
Type of cooler
DX
Type of feedback
Alarm
Digital start output
Yes
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Heating/Cooling sequence setup
4. Select
Cooling (SEQ-C)
5. Set
Type of sequence
to
Cooling
6. Select the type of cooler (e.g.
DX
)
7. Select the type of feedback from the cooler as
Type of feedback
(e.g.
Alarm
or
Run indication
)
8. Select
Yes
as
Digital start output
if the external cooler requires a digital start signal.
14.4.10.3 Allocation
Select I/O (in-output) placement of where the cooler control signal output, digital start output and feedback input are
connected to the controller in the
Configuration
>
I/O allocation settings
submenus
Digital inputs
,
Analog outputs
and
Digital outputs
.
Overview:
Configuration
>
I/O allocation settings
>
Digital
inputs
2021–03–01
Digital inputs
Device
Position
Feedback cooling (SEQ-C)
Controller
UI4
Configuration
>
I/O allocation settings
>
Analog
outputs
2021–03–01
Analog outputs
Device
Position
Cooling (SEQ-C)
Controller
AO4