4/64 |
F-B90
•
01, 02
– with grille on one side only.
•
11, 22
– with grille on both sides.
Types of Activation
•
H0
Fire damper with a manual crank activation mechanism and with a spring return release mechanism activated by a
fusible thermal link set to 74°C.
•
H2
Fire damper with an activation mechanism H0 + open and closed indication with AC 230 V or AC/DC 24 V contact
switches.
•
B230T
or
G230T
(G230T not available for sizes H=250)
Fire damper with an activation mechanism with a Belimo (B230T) or Gruner (G230T) spring return actuator (230V AC)
with an electro-thermal fuse 72°C and auxiliary switches.
•
B24T
or
G24T
(G24T not available for sizes H=250)
Fire damper with an activation mechanism with a Belimo (B24T) or Gruner (G24T) spring return actuator (24V AC/DC)
with electro-thermal fuse 72°C and auxiliary switches.
•
BST0
or
GST0
(GST0 not available for sizes H=250)
Fire damper with an activation mechanism with spring return actuator Belimo (BST0, AC/DC 24 V, supply through com.
unit: AC 230 V) or Gruner (GST0, AC/DC 24 V, supply through com. unit: AC 24 V) with an electro-thermal fuse 72°C
and auxiliary switches, with a Belimo supply and communication unit BKN230-24 or Gruner supply and communication
unit fs-UFC24-2 (other communication units on demand).
•
B24T-SR
or
G24T-SR
(G24T-SR not available for sizes H=250)
Fire damper with an activation mechanism with a Belimo (B24T-SR) or Gruner (G24T-SR) spring return actuator (24V
AC/DC) with electro-thermal fuse 72°C and auxiliary switches for Modulated dampers (possibility to open the blade at
the desired angle).
•
BSD230T
or
GSD230T
(Only for Grille types 11 and 22 & GSD230T not available for sizes H=250)
Overflow fire damper with Smoke Detector fitted activation mechanism (230V AC) with a Belimo or Gruner spring
return actuator with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication
unit or Gruner power supply unit (Actuator powered through transformer and than 24V AC/DC Smoke detector).
•
BSD24T
or
GSD24T
(Only for Grille types 11 and 22 & GSD24T not available for sizes H=250)
Overflow fire damper with Smoke Detector fitted activation mechanism (24V AC/DC) with a Belimo or Gruner spring
return actuator with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication
unit or Gruner power supply unit (Actuator powered through 24V AC/DC Smoke detector).
Design
The casing and the blades of the F-B90 are made of a galvanized sheet metal. A foam seal with an intumescent seal
that prevents leaks of heat or smoke. The casing has flanges on two sides with a thread to attach to sheet-metal duct
flanges. Two sides of the damper have inserts with a thread to attach the grille. The damper casing and two covers on
two sides give protection to the mechanism and the actuator of the F-B90. They also give access for easy connection.
Composition of materials
Body of the product contains these materials: Galvanized sheet metal; Galvanized steel fasteners; PE tapes and foil
Blades and mechanism access doors of the product contain these materials: Calcium silicate board; Polyurethane foam;
Intumescent strips; Acrylic sealant
The manufacturing processes of these materials agree with local regulations. The product does not contain dangerous
materials.
Содержание 178818
Страница 1: ...F B90 Multiblade Fire Damper Handbook...
Страница 21: ...21 64 F B90 5 1 1 2 B A1 A2 3 A1 B A2...
Страница 22: ...22 64 F B90 C1 C2 C3 C4 C5 i D 4 1 8 1 Fx D1 D2...
Страница 23: ...23 64 F B90 F3 5 2 E F F3 E1 E2 5 F1 F2 6...
Страница 48: ...48 64 F B90 Wire preparation C1 A1 A2 B C2 C2 H B G A1 A2 B 2 1 C2 C1...
Страница 61: ...61 64 F B90 D1 D2 D3 P13 P13 E E H B G 1 2 H...
Страница 64: ...Systemair DESIGN 2021 08 25 Handbook_F_B90_en GB...