SS-200-035  4 I56-4175-002 
 

 

©2015 System Sensor 

System Sensor warrants its enclosed waterflow detector to be free from defects in 
materials and workmanship under normal use and service for a period of three years 
from date of manufacture. System Sensor makes no other express warranty for this 
waterflow detector. No agent, representative, dealer, or employee of the Company 
has the authority to increase or alter the obligations or limitations of this Warranty. The 
Company’s obligation of this Warranty shall be limited to the repair or replacement of any 
part of the waterflow detector which is found to be defective in materials or workman-
ship under normal use and service during the three year period commencing with the 
date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 
(736-7672) for a Return Authorization number, send defective units postage prepaid 

1.  Waterflow detectors may not work or operate properly if sprinkler piping being moni-

tored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler sys-
tems should be checked regularly for such blocking material, following the instructions 
in Chapter 5 of NFPA Standard 13A.

2.  Alarms generated by the activation of waterflow detectors may not be received by 

a central station if telephone or other communication lines to the detector are out of 
service, disabled, or open.

WARNING

THE LIMITATIONS OF WATERFLOW ALARM DEVICES

3.  Vane-type waterflow detectors have a normal service life of 10-15 years. Hard water 

systems, however, may substantially reduce waterflow detector service life.

4.  Waterflow detectors are not a substitute for insurance. Building owners should always 

insure property and lives being protected by sprinkler systems.

5.  If valves controlling the water supply to a sprinkler system are closed, vane-type wa-

terflow detectors will not work. All valves controlling a sprinkler water supply should 
be sealed or locked in the normally open position. The normally open position should 
be monitored by a sprinkler supervisory switch.

THREE-YEAR LIMITED WARRANTY

to: System Sensor, Returns Department, RA #__________, 6581 Kitimat Road, Unit 6, 
Mississauga, Ontario L5N-3T5. Please include a note describing the malfunction and 
suspected cause of failure. The Company shall not be obligated to repair or replace units 
which are found to be defective because of damage, unreasonable use, modifications, 
or alterations occurring after the date of manufacture. In no case shall the Company 
be liable for any consequential or incidental damages for breach of this or any other 
Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the 
Company’s negligence or fault. Some states do not allow the exclusion or limitation of 
incidental or consequential damages, so the above limitation or exclusion may not apply 
to you. This Warranty gives you specific legal rights, and you may also have other rights 
which vary from state to state.

Please refer to insert for the Limitations of Fire Alarm Systems

FIGURE 6. DIRECTIONAL COVER

NOTCHED COVER INDICATES FLOW DIRECTION AT A

DISTANCE FROM MULTIPLE VIEWING ANGLES

W0382-00

FIGURE 7. WFDNA WIRING:

CONTACT RATINGS

125/250 VAC

10 AMPS

24 VDC

2.5 AMPS

ULC-LISTED

COMPATIBLE

CONTROL PANEL

POWER

24VDC

OR

120VAC

INITIATING

LOOP

SSM24-X

SSV120-X

NOTE: COMMON AND B-NO

CONNECTIONS WILL CLOSE

WHEN VANE IS DEFLECTED, I.E.,

WHEN WATER IS FLOWING. DUAL

SWITCHES PERMIT

APPLICATIONS TO BE COMBINED

ON A SINGLE DETECTOR.

SCHEMATIC OF

INDIVIDUAL

SWITCH IN

"NO WATERFLOW"

CONDITION

BREAK WIRE AS

SHOWN FOR

SUPERVISION OF

CONNECTION. DO

NOT ALLOW

STRIPPED WIRE

LEADS TO EXTEND

BEYOND SWITCH

HOUSING. DO NOT

LOOP WIRES.

A-NC

B-NO

COM

SUGGESTED EOL

RESISTOR

+

-

+

-

W0393-00