background image

FIGURE 4. KNOCKOUT PLUG REMOVAL:

GROUND 

SCREW

W0383-01

FIGURE 5. DELAY ADJUSTMENT DIAL:

NOTE: RETARD  TIME MAY EXCEED 90 SECONDS. ADJUST

AND  VERIFY  

THAT  TIME DOES NOT EXCEED 90 SECONDS.

NUMBER ON DIAL IS APPROXIMATE  TIME DELAY IN SECONDS

DELAY

ADJUSTMENT

DIAL

W0385-00

SS-200-035  3 I56-4175-002

MECHANICAL DELAY ADJUSTMENT

The pneumatic delay is preset at the factory to 30 seconds. To adjust the set-
ting, turn the adjustment dial clockwise to increase the delay, counterclock-
wise to decrease it. The delay is adjustable from 0 to 90 seconds max. 

See 

Figure 5.

 As a point of reference when setting time delay in dark environ-

ments the notch in the dial indicates an approximate 30 second time delay 
and the larger of the three tabs indicates an approximate 60 second time 
delay.

NOTE:

 Set the delay to the minimum required to prevent false alarms from 

flow surges.

Periodically test time delay as required by Authority Having Jurisdiction or 
code authority.

OPERATIONAL TESTING

Always notify a central station monitoring waterflow alarms before repairing, 
maintaining, or testing waterflow alarm devices.

1. 

 Replace the cover and tighten the tamper proof screws with the tamper 
proof wrench. Store the wrench in a secure place.

2. 

 Open the inspector’s test valve and time how long it takes for the detec-
tor to indicate a flow condition. The detector should remain activated un-
til the inspector’s test valve is closed. Air pockets in the sprinkler system 
may increase the apparent delay.

MAINTENANCE

To prevent accidental water damage, control valves should be shut tight and 
the system completely drained before waterflow detectors are removed or 
replaced.

Inspect detectors in accordance with applicable ULC and NFPA codes and 
standards and/or the Authority Having Jurisdiction for leaks and replace if a 
leak occurs. Test detectors at least quarterly, as described under Operational 
Testing, to ensure proper operation. Test more often if required by the author-
ity having jurisdiction.

Under normal conditions, System Sensor waterflow detectors should provide 
years of trouble-free service. However, if the delay mechanism becomes 
faulty, a replacement kit is available. To replace the delay mechanism, re-
quest Part No. FS-RT. Complete instructions are enclosed with replacement 
parts. The mechanism can be easily replaced without removing the detector 
from the pipe or draining the pipe. Do not repair or replace any other water-
flow detector components. If any other part of the detector does not perform 
properly, replace the entire detector. Installation methods other than those 
listed in this installation manual may prevent the device from reporting the 
flow of water in the event the associated sprinkler system is activated by a 
fire. System Sensor is not responsible for devices that have been improperly 
installed, tested, or maintained.

To remove a detector:

1. 

Drain the pipe.

2. 

Turn off electrical power to the detector and disconnect the wiring.

3. 

Loosen the nuts and remove the U-bolts.

4. 

 Gently lift the saddle far enough to get your fingers under it. Then, roll 
the vane so it will fit through the hole while continuing to lift the waterflow 
detector saddle.

5. 

Lift the detector clear of the pipe.

CAUTION

If a vane breaks in a pipe, find and remove it. If it is not removed, the vane 
may restrict the flow of water to all or part of the fire sprinkler system. 

Отзывы: