background image

3. 

 Remove burrs and sharp edges from the hole. Clean and remove all 
scale and foreign matter from the inside of the pipe for a distance equal 
to the pipe diameter on either side of the hole to ensure free movement 
of the vane. Clean the outside of the pipe to remove dirt, metal chips, 
and cutting lubricant.

4. 

 Seat the gasket against the saddle and mount the detector directly to the 
pipe. Carefully roll the vane opposite the direction of flow and insert it 
through the hole (see 

Figure 3

). Seat the saddle firmly against the pipe 

so that the locating boss goes into the hole.

5. 

 Install the U-bolt, tightening the nuts alternately to ensure a uniform seal 
(see 

Table 1

 for torque values).

6.   Remove the cover with the tamper-proof wrench provided. Move the 

actuator lever back and forth to check for binding. If the vane binds, 
remove the detector and correct the cause before proceeding.

CAUTION

Be sure the direction-of-flow arrow and directional cover point in the correct 
direction or else water flow will go unreported. See 

Figure 3 

and

 Figure 6.

FIGURE 1. MOUNTING DIMENSIONS:

8.9 CM

(3.5")

6.6 CM

(2.6")

PIPE DIAMETER

PLUS 12.7 CM

(5")

PIPE

VANE

OVERALL WIDTH = PIPE DI 6.4 CM (2.5")

UBOLT

NUT

PIPE

SADDLE

UBOLLT

PIPE

FIGURE 2. MOUNTING HOLE LOCATION:

WRONG

RIGHT

REMOVE BURRS FROM EDGE OF HOLE. CLEAN OUT SCALE

AND FOREIGN MATTER FROM INSIDE WALL OF PIPE.

W0106-00

TABLE 1:

WFDNA MODEL

HOLE SIZE (IN)

TORQUE

20, 25

1

1

/

4

30–35 ft.-lb.

40

2

45- 50 ft.-lb

30, 50, 60, 80

2

60- 65 ft.-lb.

SS-200-035  2 I56-4175-002

PRE-OPERATION TESTING 

1. 

 Fill the fire sprinkler system and check for leaks around the waterflow 
detector. If it leaks, first check for the proper torque on the U-bolt nuts. 
If the leak persists, drain the system and remove the detector (refer to 
Maintenance). Check for dirt or foreign objects under the gasket, and 
make sure that the pipe surface is not dented. Reinstall the detector and 
check again for leaks. Do not proceed until all leaks have been stopped.

2. 

 Connect an ohmmeter or continuity tester across the COM and B-NO 
switch terminals. The ohmmeter should indicate an open circuit.

3.   Deflect the actuator lever and hold it until the pneumatic delay shaft 

releases the switch buttons. The ohmmeter or continuity tester should 
show a short circuit after the delay has elapsed. If there is no delay, 
check the setting of the delay adjustment dial.

FIGURE 3. ASSEMBLY DIAGRAM:

WATERF

LOW

U-BOLT

PIPE

SADDLE GASKET

REFER TO

 TABLE 1

U-BOLT

NUT

ELECTRICAL

CONDUIT

ENTRANCE

COVER

TAMPER PROOF

WRENCH

(P/N WFDW)

ROLL PADDLE

OPPOSITE OF

FLOW ARROW

WHILE INSERTING

PIPE SADDLE

MOUNTING PLATE

TIMER

(REPLACEMENT

P/N FS-RT)

COVER TAMPER

SWITCH

(OPTIONAL P/N CTS)

W0392-00

FIELD WIRING

1.    All models have two SPDT switches. Switch contacts COM and B-NO 

are closed when water is flowing and open when it is not. Connect the 
switches, as shown in 

Figure 7

, depending on the application.

2.    When connected to a listed fire sprinkler/fire alarm control panel, the 

initiating circuit must be unable to be silenced.

3.    A ground screw is provided with all waterflow detectors. When ground-

ing is required, clamp wire with screw in hole located between conduit 
entrance holes. See 

Figure 4

.

4. 

Use proper waterproof conduit fittings where required.

WARNING

High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on 
a device to which AC power is applied. Doing so may result in injury or death.

When utilizing switches at voltages greater than 74VDC 

 or 49VAC 

 means to provide all–pole disconnection must be incorporated in the 

fixed wiring, such as a circuit breaker.

W0384-00

Отзывы: