WFDE Vane-type Waterflow Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Important

Please Read Carefully And Save

This instruction manual contains important information about the instal-
lation and operation of waterflow detectors. Purchasers who install wa-
terflow detectors for use by others must leave this manual or a copy of it 
with the user.
Read all instructions carefully before beginning. Follow only those instruc-
tions that apply to the model you are installing.

CAUTION

Use vane-type waterflow detectors in wet-pipe systems only. DO NOT USE 
IN DRY-PIPE, DELUGE, OR PRE-ACTION SYSTEMS. The sudden inrush of 
water in such systems may break the vane or damage the mechanism.

Do  not  use  in  potentially  explosive  atmospheres.  Do  not  leave  unused 
wires exposed.

Principles of Operation

Vane type waterflow detectors mount to water-filled pipes in sprinkler sys-
tems. Waterflow in the pipe deflects a vane. Deflection of the vane pro-
duces a switched output, usually after a specified delay. All WFDEs have 
a pneumatically controlled mechanical delay mechanism. Delays are non-
cumulative; they reset if the flow of water stops or drops below minimum 
triggering flow rate before the entire delay has elapsed. All detectors will 
activate on a sustained flow of water greater than the maximum specified 
in Table 1, but will not activate if the flow rate is less than the minimum 
specified in Table 1.

Steel Pipe Compatibility

CAUTION

DO  NOT  USE  THE  ABOVE  MODELS  ON  COPPER  PIPE.  The  clamping 
forces of the mounting bolts may collapse the pipe sufficiently to prevent 
the detector from functioning properly.

DO  NOT  INSTALL  STEEL  OR  IRON  PIPE  SECTIONS  IN  COPPER  PIPING 
FOR MOUNTING A WATERFLOW DETECTOR. Incompatibility between the 
dissimilar metals will cause bimetallic corrosion.

Specifications

Contact Ratings: 

10 A @ 125/250 VAC  

 

2.5 A @ 24 VDC  

 

 

EC–certificate Number: 0786-CPD-40151

Triggering Flow Rate: 

Refer to Table 1  

 

 

EN12259–5

Static Pressure Rating (maximum): 

17.25 bar (250 psi) (1725 KPa)   

 

16 bar (VdS)

Operating Temperature Ranges: 

0° – 68°C (32° – 155°F) 

 

 

Compatible Pipe: 

Steel Water Pipe (Refer to Table 1) 

 

Shipping Weight: 

1.8 – 3.2 Kilograms

Enclosure Rating: 

Nema4/IP54

Installation Guidelines

Before  installing  any  waterflow  alarm  device,  be  thoroughly  familiar 
with national codes of practice and the requirements of the authority 
having jurisdiction.
Failure to follow these directions may result in failure of the device to 
report a waterflow condition. System Sensor is not responsible for de-
vices that have been improperly installed, tested or maintained.
1.  Mount the detector where there is adequate clearance for installation 

and removal and a clear view of it for inspections. See Figure 1 for 
mounting dimensions.

2.  Locate the unit 1.8 – 2.1 meters above the floor to protect from damage.
3.  On horizontal runs, position the detector on top or on the side of the 

pipe. Do not mount it upside down because condensation may collect 
in the housing and impair the operation of the detector. For vertical 
flow  applications,  mount  detector  on  pipe  where  upflow  conditions 
exist. Failure to do so may prevent unit from operating properly.

4.  Mount detector at least 15 cm from a fitting which changes the direc-

tion of the water flow, or no closer than 61 cm from a valve or drain.

5. 

BE  SURE  DIRECTION-OF-FLOW  ARROW  MATCHES  ACTUAL  DI-
RECTION OF FLOW IN THE PIPE.

Mounting Instructions

1.  Drain the pipe.
2.  Cut a hole in the desired location. Center the hole in the pipe as shown 

in Figure 2, and be sure the hole is perpendicular to the center of the 
pipe. If the hole is off center, the vane will bind against the inside wall 
of the pipe. Use a drill or holesaw to cut a hole of the proper diameter. 
See Table 2 for hole size. Before drilling, use a punch or scribe to mark 
the drill site to keep the bit from slipping.

This  System  Sensor  installation  manual  covers  the  following  waterflow 
detectors for sprinkler/fire alarm applications.

Table 1.

MODEL 

NUMBER

DN

REF. PIPE

SIZE - mm (in)

NOMINAL

PIPE O.D.

(mm)

WALL

THICKNESS

(mm)

TRIGGERING

FLOW RATE

(liters/min)

WFD20E

50 (2)

60.3

2.3/2.9

30 – 57

WFD25E

65 (2-1/2)

76.1

2.6/2.9

WFD30-2E

80 (3)

88.9

2.9/3.2

WFD40E

100 (4)

114.3

3.2/3.6

WFD60E

150 (6)

168.3

4.0/4.5

WFD80E

200 (8)

219.1

4.5/5.9