background image

D770-53-00 

I56-2617-001R

Operational Testing

Always notify the central station monitoring waterflow alarms before re-
pairing, maintaining or testing waterflow alarm devices.
1.  Replace  the  cover  and  tighten  the  security  screws  with  the  security 

wrench. Store the wrench in a secure place.

2.  Open  the  inspector’s  test  valve  and  time  how  long  it  takes  for  the 

detector to indicate a flow condition. The detector should remain ac-
tivated  until  the  inspector’s  test  valve  is  closed.  Air  pockets  in  the 
sprinkler system may increase the apparent time delay.

Maintenance

To prevent accidental water damage, control valves should be shut tight 
and  the  system  completely  drained  before  waterflow  detectors  are  re-
moved or replaced.
Inspect detectors monthly for leaks. If leaks are found, replace the detec-
tor. Test detectors at least quarterly as described under Operational Testing 
above  to  insure  proper  operation.  Test  more  often  as  required  by  appli-
cable codes or standards.
Under normal conditions System Sensor waterflow detectors should pro-
vide years of trouble-free service. If any part of the detector does not per-
form properly, replace the entire detector. 

Failure to follow this instruction 

may result in failure of the detector to report a waterflow condition. 
Proceed as follows to remove a detector:

1.  Drain the pipe.
2.  Turn off electrical power to the detector, and then disconnect wiring.
3.  Loosen nuts and remove U bolts.
4.  Gently  lift  the  saddle  far  enough  to  get  your  fingers  under  it.  With 

your fingers, roll the vane so it will fit through the hole while continu-
ing to lift the waterflow detector saddle.

5.  Lift detector clear of pipe.

CAUTION

If a vane breaks off in a pipe, find and remove it. Failure to do so may 
restrict the proper flow of water to part of the sprinkler system.

Figure 3. Assembly diagram:

Figure 4. Field wiring:

W0234-02

WFDE

B

B

COM

COM

WFDE

B

B

COM

COM

nonsilenceable

initiating zone of listed

Fire Alarm Control Panel

Typical Fire Alarm Control Panel Connection

Two Waterflow Detectors Shown

power source

compatible

with bell

local

bell

COM

B

Typical Local Bell Connection

Top View

NOTE: Common and B connections will

close when vane is deflected, i.e.,

when water is flowing. Dual switches

permit applications to be combined

on a single detector.

end-of-line-resistor

Break wire as shown for

supervision of connection.

DO NOT allow stripped wire

leads to extend beyond

switch housing. DO NOT

loop wires.

CONTACT RATINGS

125/250 VAC

24 VDC

10 AMPS

2.5 AMPS

B

COM

A

Schematic of

Individual Switch

in “No Waterflow”

Condition

T16-0010-XXX

B

COM

A

COM

COM

SWITCH 1     SWITCH 2

      B      B   

  A

•CAUTION•
ROUTE WIRING
AWAY FROM
SHARP EDGES 
& COMPONENTS

SWITCH SCHEMATIC
•READY• STATE

Cover

Tamper proof wrench

Delay mechanism

Pipe saddle

Plastic vane

Mounting plate

Roll paddle opposite

of flow arrow

while inserting

Saddle gasket

Waterflow

U bolt nut

Electrical conduit entrance

(22.2 mm dia.)

Terminal block

Pipe

U bolt

Refer to Table 2

MODEL

NUMBER

HOLE

DIAMETER

TORQUE

SETTING

WFD20E

31.8 mm +1.6 mm

1-1/4 in. +1/16 in

40.7 - 47.5 NT-M

30 - 35 FT-LBS

WFD25E

WFD30-2E

50.8 mm + 1.6 mm

2 in. +1/16 in.

74.6 - 81.3 NT-M

55 - 60 FT-LBS

WFD40E
WFD60E
WFD80E

W0101-02

Отзывы: