D770-53-00 

I56-2617-001R

CAUTION

When drilling out hole, make certain that center of hole saw cut does not 
remain in pipe.

3.  Remove burrs and sharp edges from hole. Clean out scale and foreign mat-

ter from inside wall of pipe to ensure free movement of the vane. Clean the 
outside of the pipe to remove dirt, metal chips, and cutting lubricant.

4.  Seat the saddle gasket against the saddle and mount detector directly 

to pipe. Carefully roll the vane opposite the direction of flow and in-
sert it through the hole (see Figure 3). Seat the saddle firmly against 
the pipe so that the locating boss goes into the hole.

5.  Install the U-bolt around the pipe. Thread both nuts onto the U-bolt 

and tighten them alternately to ensure a uniform seal. See Table 2 for 
torque values.

6.  Remove the metal cover with the tamper proof wrench provided. Move 

the  actuator  lever  back  and  forth  to  check  for  binding.  If  the  vane 
binds, remove the detector and correct the problem before proceeding.

CAUTION

Be sure the direction-of-flow arrow points in the correct direction, other-
wise a waterflow condition will go unreported. See Figure 3.

Preoperation Testing

1.  Fill the sprinkler system and check for leaks around the WFDE. If it 

leaks,  first  check  for  proper  torque  on  U-bolt  nuts.  If  leak  persists, 
drain  the  system  and  remove  the  detector  (see  removal  instructions 
under Maintenance). Check for dirt or foreign objects under the gasket. 
Check that pipe surface is not dented. Reinstall the detector and check 
again for leaks. Do not proceed until all leaks have been stopped.

2.  Connect  an  ohmmeter  or  continuity  tester  across  (COM  and  B)  ter-

minal switch contacts (see Figure 4). The ohmmeter should show an 
open circuit, no continuity.

3.  Deflect the actuator lever and hold it until the pneumatic delay shaft 

releases the switch buttons. The ohmmeter or continuity tester should 
show a short circuit after the delay has elapsed. If there is no delay, 
check the setting of the delay adjustment dial.

Field Wiring

WARNING

High Voltage. Electrocution Hazard. Do not handle live AC wiring or work 
on a device to which AC power is applied. Doing so may result in severe 
injury or death.

When  utilizing  switches  at  voltages  greater  than  74VDC        or 
49VAC         means to provide all–pole disconnection must be incorporated 
in the field wiring, such as a circuit breaker.

1.  All models have two SPDT switches. Switch contacts (COM and B) are 

closed when water is flowing and open when water is not flowing. Con-
nect the switches as shown in Figure 4 depending on the application.

2.  When connected to a listed sprinkler/fire alarm control panel, the ini-

tiating circuit must be non-silenceable.

3.  A  ground  screw  is  provided  with  all  WFDE  units.  When  grounding 

is required, clamp wire with screw in hole located between conduit 
entrance holes. See Figure 5.

4.  Use proper waterproof conduit fittings where required.
5.  A 22.2 mm conduit hole is provided for electrical connection. An additional 

22.2 mm diameter knockout is provided for multiple line connections.

Mechanical Delay Adjustment

The pneumatic delay is preset at dial setting 25 at the factory. To adjust the 
delay, turn the adjustment dial on the delay mechanism. Turn clockwise to 
increase the delay, counterclockwise to decrease the delay. Delay can be ad-
justed over a range from 0 to 30 seconds maximum. See Figure 6 (page 4).

NOTE:

 Set the delay to the minimum required to prevent false alarms due 

to flow surges.
After extended service, parts of the detector may become worn reducing the 
delay time and causing false alarms. If this happens, increase the delay. 

Figure 2. Location of mounting hole:

Figure 1. Mounting dimensions:

W0105-00

W0106-00

Table 2:

7.6 cm

(3

˝)

9.5 cm

(3-3/4˝)

Pipe saddle

U-bolt nut

Plastic vane

Pipe

U-bolt

Overall width = pipe di 7.6 cm (3˝)

Pipe diameter

plus 13.3 cm

(5-1/4˝)

Wrong

Right

Remove burrs from edge of hole. Clean out scale
and foreign matter from inside wall of pipe.

MODEL

NUMBER

HOLE

DIAMETER

TORQUE

SETTING

WFD20E

31.8 mm +1.6 mm

1-1/4 in. +1/16 in

40.7 - 47.5 NT-M

30 - 35 FT-LBS

WFD25E

WFD30-2E

50.8 mm + 1.6 mm

2 in. +1/16 in.

74.6 - 81.3 NT-M

55 - 60 FT-LBS

WFD40E
WFD60E
WFD80E