D770-24-00 

I56-1452-005R

fiGUre 4. Wfd WirinG:

+

+

SSM24-X

SSV120-X

NOTE: COMMON AND B-NO 

CONNECTIONS WILL CLOSE 

WHEN VANE IS DEFLECTED, I.E., 

WHEN WATER IS FLOWING. DUAL 

SWITCHES PERMIT 

APPLICATIONS TO BE COMBINED 

ON A SINGLE DETECTOR.

BREAK WIRE AS 

SHOWN FOR 

SUPERVISION OF 

CONNECTION. DO 

NOT ALLOW 

STRIPPED WIRE 

LEADS TO EXTEND 

BEYOND SWITCH 

HOUSING. DO NOT 

LOOP WIRES.

POWER 

24VDC OR 

120VDC

INITIATING 

LOOP

UL LISTED 

COMPATIBLE 

CONTROL PANEL

CONTACT RATINGS

125/250 VAC

24 VDC

10 AMPS

2.5 AMPS

SCHEMATIC OF 

INDIVIDUAL 

SWITCH IN

“NO WATERFLOW” 

CONDITION

SUGGESTED EOL 

RESISTOR

B-NO

COM

A-NC

W0356-00

mechanicaL deLaY adjUsTmenT

The pneumatic delay is preset at the factory to 30 seconds. To adjust the set-
ting, turn the adjustment dial clockwise to increase the delay, counterclockwise 
to decrease it. The delay is adjustable from 0 to 90 seconds. See 

Figure 5

.

NOTE:

 Set the delay to the minimum required to prevent false alarms from 

flow surges.

After extended service, parts of the detector may become worn, reducing the 
delay  time  and  causing  false  alarms.  If  this  happens,  increase  the  delay.  If 
the delay is already at the maximum, replace the mechanical delay assembly. 
Refer to Maintenance for ordering replacement parts.

oPeraTionaL TesTinG

Always notify a central station monitoring waterflow alarms before repairing, 
maintaining, or testing waterflow alarm devices.

1.   Replace the cover and tighten the tamper proof screws with the tamper 

proof wrench. Store the wrench in a secure place.

2.   Open the inspector’s test valve and time how long it takes for the detec-

tor to indicate a flow condition. The detector should remain activated un-
til the inspector’s test valve is closed. Air pockets in the sprinkler system 
may increase the apparent delay.

mainTenance

To prevent accidental water damage, control valves should be shut tight and the 
system completely drained before waterflow detectors are removed or replaced.

Inspect detectors in accordance with applicable NFPA codes and standards and/
or the authority having jurisdiction for leaks and replace if a leak occurs. Test de-
tectors at least quarterly, as described under Operational Testing, to ensure proper 
operation. Test more often if required by the authority having jurisdiction.

Under normal conditions, System Sensor waterflow detectors should provide 
years of trouble-free service. However, if the delay mechanism or switch en-
closure  needs  to  be  replaced,  follow  these  directions.  To  replace  the  delay 
mechanism  or  switch  enclosure,  use  a 

3

16

-inch  socket  head  screwdriver  to 

remove the three screws that hold it in place. Either mechanism can be easily 
replaced without removing the detector from the pipe or draining the pipe. To 
replace the delay mechanism, request Part No. A3008-00. For switch enclo-
sure, request Part No. A77-01-02. Do not repair or replace any other waterflow 
detector components. If any other part of the detector does not perform prop-
erly, replace the entire detector. Installation methods other than those listed 
in this installation manual may prevent the device from reporting the flow of 
water in the event the associated sprinkler system is activated by a fire. Sys-
tem Sensor is not responsible for devices that have been improperly installed, 
tested, or maintained.

To remove a detector:

1.  Drain the pipe.
2.  Turn off electrical power to the detector and disconnect the wiring.
3.  Loosen the nuts and remove the U-bolts.
4.   Gently lift the saddle far enough to get your fingers under it. Then, roll 

the vane so it will fit through the hole while continuing to lift the water-
flow detector saddle.

5.  Lift the detector clear of the pipe.

CAUTION

If a vane breaks in a pipe, find and remove it. If it is not removed, the vane 
may restrict the flow of water to all or part of the sprinkler system. 

fiGUre 5. deLaY adjUsTmenT diaL:

DELAY

ADJUSTMENT

DIAL

55

70

0

15

45

30

TI

ME

  DE

LAY  IN  SECO

ND

S

NU

MB

ER

  ON

  DIAL  IS  APPRO

XIM

AT

E

NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST 

AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS. 

NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN 

SECONDS WITH AN ACCURACY OF +/− 50%.

W0112-02