1.   Waterflow  detectors  may  not  work  or  operate  properly  if  sprinkler  piping  be-

ing  monitored  is  plugged  with  pipe  scale,  mud,  stones  or  other  foreign  material. 
Sprinkler systems should be checked regularly for such blocking material, following 
the instructions in Chapter 5 of NFPA Standard 13A.

2.   Alarms generated by the activation of waterflow detectors may not be received by a 

central station if telephone or other communication lines to the detector are out of 
service, disabled, or open.

3.   Vane-type waterflow detectors have a normal service life of 10-15 years. Hard water 

systems, however, may substantially reduce waterflow detector service  life.

WARNING

The LimiTaTions of WaTerfLoW aLarm Devices

4.   Waterflow  detectors  are  not  a  substitute  for  insurance.  Building  owners  should 

always insure property and lives being protected by sprinkler systems.

5.   If  valves  controlling  the  water  supply  to  a  sprinkler  system  are  closed,  vane-type 

waterflow detectors will not work. All valves controlling a sprinkler water supply 
should be sealed or locked in the normally open position. The normally open posi-
tion should be monitored by a sprinkler supervisory switch.

Three-Year LimiTeD WarranTY

System Sensor warrants its enclosed waterflow detector to be free from defects in materi-
als and workmanship under normal use and service for a period of three years from date 
of manufacture. System Sensor makes no other express warranty for this waterflow detec-
tor. No agent, representative, dealer, or employee of the Company has the authority to 
increase or alter the obligations or limitations of this Warranty. The Company’s obligation 
of this Warranty shall be limited to the repair or replacement of any part of the waterflow 
detector which is found to be defective in materials or workmanship under normal use 
and  service  during  the  three  year  period  commencing  with  the  date  of  manufacture. 
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return 
Authorization  number,  send  defective  units  postage  prepaid  to:  System  Sensor,  Repair 

Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a 
note describing the malfunction and suspected cause of failure. The Company shall not 
be obligated to repair or replace units which are found to be defective because of damage, 
unreasonable use, modifications, or alterations occurring after the date of manufacture. 
In no case shall the Company be liable for any consequential or incidental damages for 
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss 
or damage is caused by the Company’s negligence or fault. Some states do not allow the 
exclusion or limitation of incidental or consequential damages, so the above limitation 
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you 
may also have other rights which vary from state to state.

operaTionaL TesTing

Always notify a central station monitoring waterflow alarms before repairing, 
maintaining, or testing waterflow alarm devices.

1.   Replace the cover and tighten the tamper proof screws with the tamper 

proof wrench. Store the wrench in a secure place.

2.   Open the inspector’s test valve and time how long it takes for the detec-

tor to indicate a flow condition. The detector should remain activated un-
til the inspector’s test valve is closed. Air pockets in the sprinkler system 
may increase the apparent delay.

mainTenance

To prevent accidental water damage, control valves should be shut tight and the 
system completely drained before waterflow detectors are removed or replaced.

Inspect  detectors  in  accordance  with  applicable  NFPA  codes  and  standards 
and/or the authority having jurisdiction for leaks and replace if a leak occurs. 
Test  detectors  at  least  quarterly,  as  described  under  Operational  Testing,  to 
ensure proper operation. Test more often if required by the authority having 
jurisdiction.

Under normal conditions, System Sensor waterflow detectors should provide 
years of trouble-free service. However, if the delay mechanism or switch en-
closure  needs  to  be  replaced,  follow  these  directions.  To  replace  the  delay 
mechanism  or  switch  enclosure,  use  a 

3

/

16

-inch  socket  head  screwdriver  to 

remove the three screws that hold it in place. Either mechanism can be easily 

replaced without removing the detector from the pipe or draining the pipe. To 
replace the delay mechanism, request Part No. A3008-00. For switch enclo-
sure, request Part No. A77-01-02. Do not repair or replace any other waterflow 
detector components. If any other part of the detector does not perform prop-
erly, replace the entire detector. Installation methods other than those listed 
in this installation manual may prevent the device from reporting the flow of 
water in the event the associated sprinkler system is activated by a fire. Sys-
tem Sensor is not responsible for devices that have been improperly installed, 
tested or maintained.

To remove a detector:

1.  Drain the pipe.
2.  Turn off electrical power to the detector and disconnect the wiring.
3.  Loosen the nuts and remove the U-bolts.
4.   Gently lift the saddle far enough to get your fingers under it. Then, roll 

the vane so it will fit through the hole while continuing to lift the water-
flow detector saddle.

5.  Lift the detector clear of the pipe.

CAUTION

If a vane breaks in a pipe, find and remove it. If it is not removed, the vane 
may restrict the flow of water to all or part of the sprinkler system. 

Please refer to insert for the Limitations of Fire Alarm Systems