pre operaTion TesTing 

1.   Fill the sprinkler system and check for leaks around the waterflow detec-

tor. If it leaks, first check for the proper torque on the U-bolt nuts. If the 
leak persists, drain the system and remove the detector (refer to Mainte-
nance). Check for dirt or foreign objects under the gasket, and make sure 
that the pipe surface is not dented. Reinstall the detector and check again 
for leaks. Do not proceed until all leaks have been stopped.

2.   Connect  an  ohmmeter  or  continuity  tester  across  the  COM  and  B-NO 

switch terminals. The ohmmeter should indicate an open circuit.

3.   Deflect  the  actuator  lever  and  hold  it  until  the  pneumatic  delay  shaft 

releases the switch buttons. The ohmmeter or continuity tester should 
show  a  short  circuit  after  the  delay  has  elapsed.  If  there  is  no  delay, 
check the setting of the delay adjustment dial.

figUre 3. assembLY Diagram:

COVER

WA

TERFLOW

PIPE

U-BOLT

TAMPER PROOF 

WRENCH

(P/N WFDW)

DELAY

MECHANISM 

(REPLACEMENT 

(P/N A3008-00)

MOUNTING PLATE

PIPE SADDLE

PLASTIC VANE

ROLL PADDLE 

OPPOSITE OF 

FLOW ARROW 

WHILE INSERTING

SADDLE GASKET

REFER TO 

TABLE 1

ELECTRICAL 

CONDUIT 

ENTRANCE

U-BOLT 

NUT

TERMINAL BLOCK 

(REPLACEMENT 

P/N A77-01-02)

COVER 

TAMPER 

SWITCH

W0373-00

Wiring

1.    All  models  have  two  SPDT  switches.  Switch  contacts  COM  and  B-NO 

are closed when water is flowing and open when it is not. Connect the 
switches, as shown in 

Figure 4

, depending on the application.

2.    When connected to a listed sprinkler/fire alarm control panel, the initiat-

ing circuit must be nonsilenceable.

3.    A ground screw is provided with all waterflow detectors. When ground-

ing is required, clamp wire with screw in hole located between conduit 
entrance holes. See 

Figure 5A

.

4.   If a second conduit entry is required, remove the knockout plug using a 

flat blade screwdriver as shown on 

Figure 5B

. Strike sharply with a ham-

mer  to  pierce  the  wall  of  the  knockout  plug.  Move  to  an  adjacent  wall 
section and repeat until the plug falls out. Make sure that the waterflow 
detector is supported adequately during this operation to avoid injury.

WARNING

High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a 
device to which AC power is applied. Doing so may result in injury or death.

6.   Remove the metal cover with the tamper-proof wrench provided. Move 

the actuator lever back and forth to check for binding. If the vane binds, 
remove the detector and correct the cause before proceeding.

CAUTION

Be sure the direction-of-flow arrow points in the right direction or else water 
flow will go unreported, see 

Figure 3

.

figUre 1. moUnTing Dimensions:

U-BOLT 

NUT

PIPE 

SADDLE

U-BOLT

WIDTH: SEE TABLE

PLASTIC 

VANE

PIPE

1.70˝

3.73˝

MODEL

WFD20A
WFD25A

WFD30-2A

WFD40A
WFD60A
WFD80A

WIDTH

4.60˝
4.60˝
5.20˝
6.77˝
9.06˝

10.75˝

W0151-00

figUre 2. moUnTing hoLe LocaTion:

WRONG

RIGHT

REMOVE BURRS FROM EDGE OF HOLE. CLEAN OUT SCALE

AND FOREIGN MATTER FROM INSIDE WALL OF PIPE.

W0106-00

TabLe 1:

WFD MODEL 

HOLE SIZE

TORQUE

20,25

1

1

/

4

˝

30-35ft-lb.

30-2, 40, 50, 60, 80 

55-60 ft.-lb.

D770-44-00 

I56-2338-004R