figUre 5a. groUnD screW LocaTion:

MOUNTING PLATE

GROUND 

SCREW 

(GREEN)

W0137-00

figUre 5b. KnocKoUT pLUg removaL:

W0148-01

mechanicaL DeLaY aDjUsTmenT

The pneumatic delay is preset at the factory to 30 seconds. To adjust the set-
ting, turn the adjustment dial clockwise to increase the delay, counterclockwise 
to decrease it. The delay is adjustable from 0 to 90 seconds. See 

Figure 6

.

NOTE:

 Set the delay to the minimum required to prevent false alarms from 

flow surges.

After extended service, parts of the detector may become worn, reducing the 
delay  time  and  causing  false  alarms.  If  this  happens,  increase  the  delay.  If 
the delay is already at the maximum, replace the mechanical delay assembly. 
Refer to Maintenance for ordering replacement parts.

figUre 6. DeLaY aDjUsTmenT DiaL:

DELAY

ADJUSTMENT

DIAL

55

70

0

15

45

30

TI

ME

  DE

LAY  IN  SECO

ND

S

NU

MB

ER

  ON

  DIAL  IS  APPRO

XIM

AT

E

NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST 

AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS. 

NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN 

SECONDS WITH AN ACCURACY OF +/− 50%.

W0112-02

figUre 4. WfDa Wiring:

TOP VIEW

B-NO

B-NO

COM

COM

B-NO

B-NO

COM

COM

TYPICAL FIRE ALARM CONTROL PANEL CONNECTION

B-NO

COM

A-NC

A-NC

A-NC

A-NC

NC

NO

COM

RED

NC

NO

COM

RED

BLACK

BLUE

BLACK

END-OF-LINE

RESISTOR

WIRE

NUT

WIRE

NUT

NC

NO

COM

BLUE

WIRE

NUT

A-NC

COVER

TAMPER

SWITCH

TO POWER

SOURCE

COMPATIBLE

WITH BELL

LOCAL

BELL

BLACK

RED

BLUE

WIRE CODE:

WATERFLOW OR SUPERVISORY SWITCH:

COM  TO B-NO = OPEN CIRCUIT

COM  TO A-NC = CLOSED CIRCUIT

(NON-ALARM 

CONDITION)

COVER TAMPER SWITCH:

BLACK/BLUE: OPEN

BLACK/RED: CLOSED

(COVER OFF)

TO NONSILENCEABLE 

INITIATING ZONE OF 

LISTED FACP

NOTE: COMMON AND B-NO 

CONNECTIONS WILL CLOSE WHEN VANE 

IS DEFLECTED, I.E., WHEN WATER IS 

FLOWING. DUAL SWITCHES PERMIT 

APPLICATIONS TO BE COMBINED ON A 

SINGLE DETECTOR.

NOTE: LOCAL BELL WILL ACTIVATE WHEN COVER IS REMOVED.

 TYPICAL LOCAL BELL CONNECTION

BREAK WIRE AS SHOWN FOR 

SUPERVISION OF CONNECTION. 

DO NOT ALLOW STRIPPED WIRE 

LEADS TO EXTEND BEYOND 

SWITCH HOUSING. DO NOT 

LOOP WIRES.