D200-100-00
8
I56-3888-005
#
PARAMETER
PARAMETER
RANGE
SA LB
DESCRIPTION
COMMENTS
41 Auxiliary relay set on
low/high temperature
alert
YES/NO
User chooses the event(s) that will
activate the auxiliary relay .
NO: not used
YES: activates the AUX relay
It is possible to have more than one
event set the Aux relay . If any one
of the chosen events occurs, the
Aux relay will be activated (they are
combined as an OR function) .
42 Auxiliary relay set on
external input in not
normal state
YES/NO
43 Auxiliary relay set on
low power alert / high
power fault
YES/NO
44 Auxiliary relay set on
flow fault
YES/NO
45 Auxiliary relay set on
sensor communication
fault
YES/NO
46 Auxiliary relay set on
power restart alert
YES/NO
47 Auxiliary relay is
latched
YES/NO
NO: The AUX relay is activated when a
chosen event is present and will reset
when the event trigger is removed .
YES: The general AUX relay is activated
when a chosen event is present . When
the event trigger is removed the relay
remains set until a device reset .
48 External input normal
state
OPEN, SHORT
No action is triggered by the input in this
state .
OPEN: requires closed contacts to cause
an input response .
SHORT: requires an open circuit to cause
an input response .
49 External input triggers
fault
YES/NO
User chooses the activity that is triggered
by the external input .
NO: not used
YES: activated by external input .
Note that only one action can be selected
at a time .
Note: External input only active in
NORMAL state .
50 External input silences
sounders
YES/NO
51 External input resets
device
YES/NO
52 External input disables
device
YES/NO
53 External input disabling
time
1..1440 min
When the external input is used to disable
the device, this option sets the disable
period .
54 Pre-alarm delay
0 (OFF), 1..240 s
A delay can be set to stop reporting a pre-
alarm condition for a defined period .
If the pre-alarm condition is removed
before activation of the pre-alarm is
reported, the delay will be reset .
55 Pre-alarm and Alarm
are in cascade
YES, NO
NO: Alarm (or alarm delay) will activate
immediately on alarm condition .
YES: Alarm condition does not activate
until pre-alarm condition (and related
delay) has completed .
58 Day start time
HH:MI
Start of daytime mode operation
Minimum daytime period = 1 hour .
59 Day end time
HH:MI
End of daytime mode operation
60 Holiday day #1 date
DD/MM
On these days, the device uses the night
time settings only (every year) .
00/00 = not used
Day/Night mode (Parameter 81)
must be set to YES .
Holidays #2…#19
DD/MM
79 Holiday day #20 date
DD/MM
80 Sounder activation
mode
On Pre-alarm, On
Alarm
This option defines which event will
activate the sounder relay .
If “On Pre-Alarm” is selected,
sounders remain active in alarm .
81 Day/night mode
enabled
YES/NO
Allows use of two different sets of alarm
and pre-alarm levels.
NO: Day settings are always used
YES: Device will change between day and
night settings at selected times .