PARAMETER 

PARAMETER RANGE 

1 Channel 

1 Sensor 

1 Channel 

2 Sensor 

2 Channel 

2 Sensor 

44  Auxiliary relay set on flow fault 

YES/NO 

NO 

NO 

NO 

45  Auxiliary relay set on sensor 

communication fault  

YES/NO 

NO NO NO 

46  Auxiliary relay set on power restart 

alert  

YES/NO 

NO NO NO 

47  Auxiliary relay is latched 

YES/NO 

NO 

NO 

NO 

48  External input normal state 

OPEN, SHORT 

OPEN 

OPEN 

OPEN 

49  External input triggers fault  

YES/NO 

NO 

NO 

NO 

50  External input silences sounders 

YES/NO 

NO 

NO 

NO 

51  External input reset device 

YES/NO 

YES

YES

YES

52  External input disables ASD 

YES/NO 

NO 

NO 

NO 

53  External input ASD disabling time 

1..1440 min 

60 

60 

60 

54  Pre-alarm delay 

0 (OFF), 1..240 s 

55  Pre-alarm and Alarm are in 

cascade 

YES, 

NO 

NO NO NO 

58  Day start time 

HH:MI 

08:00 

08:00 

08:00 

59  Day end time 

HH:MI 

17:00 

17:00 

17:00 

60  Holiday day #1 date 

DD/MM 

empty 

empty 

empty 

 

… 

DD/MM 

empty empty empty 

79  Holiday day #20 date 

DD/MM 

empty 

empty 

empty 

80  Sounder activation mode 

On Pre-alarm, On Alarm 

Alarm

Alarm

Alarm

81 

Day/night 

mode 

enabled  YES/NO 

NO NO NO 

82  Monday is holiday 

YES/NO 

NO 

NO 

NO 

83  Tuesday is holiday 

YES/NO 

NO 

NO 

NO 

84  Wednesday is holiday 

YES/NO 

NO 

NO 

NO 

85 

Thursday 

is 

holiday 

YES/NO 

NO NO NO 

86  Friday is holiday 

YES/NO 

NO 

NO 

NO 

87 

Saturday 

is 

holiday 

YES/NO 

NO NO NO 

88  Sunday is holiday 

YES/NO 

NO 

NO 

NO 

89  Sensor 1 day alarm level 

1 . .9 

90  Sensor 2 day alarm level 

1..9 

91  Sensor 1 day pre-alarm level 

1..9 

92  Sensor 2 day pre-alarm level 

1..9 

93  Sensor 1 night alarm level 

1..9 

94  Sensor 2 night alarm level 

1..9 

95  Sensor 1 night pre-alarm level 

1..9 

96  Sensor 2 night pre-alarm level 

1..9 

97  Alarm mode 

Sensor alarm mode, module alarm 

mode 

X X X 

 

98  Sensor communication timeout 

0 (Disabled),1…240 s 

99  Remote output time for alarm 

50, 100,...10000ms 

X  

Содержание FAAST LT

Страница 1: ...control parameters from a PC running the proprietary software application PipeIQ Version 2 3 and above This manual describes how to monitor and configure the various operating parameters available in...

Страница 2: ...ice is in Normal the Service Mode state is entered automatically when the front cover is opened The FAAST LT unit switches off the power to the unit Once the service action is complete and the front c...

Страница 3: ...purposes only Manually setting the fan speed to change the air flow will not alter the associated hi lo flow limit settings in the FAAST LT unit Therefore this option should not be used to set or cha...

Страница 4: ...el 6 0 50 obs ft 1 64 obs m Level 7 1 00 obs ft 3 28 obs m Level 8 1 50 obs ft 4 92 obs m Level 9 2 00 obs ft 6 56 obs m To set these levels ensure the Configuration tab is selected in the left pane a...

Страница 5: ...ions see the PipeIQ Help Menu PipeIQ Help The online help is a guide through the PipeIQ application The Help opens in a separate window where it is possible to search and navigate to information on di...

Страница 6: ...r 2 enabled YES NO 8 Daylight saving enabled YES NO AUTO Allows the real time clock date to change for a daylight saving period 1 hour NO Daylight saving off YES period is specified by parameters 9 an...

Страница 7: ...t sets the fan speed to reach the reference flow programmed in the device In Manual mode the user can set the fan speed Use PipeIQ LT to change default configuration of the reference flow both modes a...

Страница 8: ...ated by external input Note that only one action can be selected at a time Note External input only active in NORMAL state 50 External input silences sounders YES NO 51 External input resets device YE...

Страница 9: ...ethod used to indicate an alarm SENSOR MODE When remote output on a sensor is set ON for configured time that sensor channel goes into alarm When the remote output turns OFF the channel stops signalli...

Страница 10: ...YES 19 Channel 2 alarm is latched YES NO YES YES YES 20 Alarm delay 0 240 s 0 0 0 21 Auxiliary relay is used for channel 2 faults YES NO YES YES YES 22 Channel 1 label 16 char ASCII code from 32 to 12...

Страница 11: ...MI 17 00 17 00 17 00 60 Holiday day 1 date DD MM empty empty empty DD MM empty empty empty 79 Holiday day 20 date DD MM empty empty empty 80 Sounder activation mode On Pre alarm On Alarm Alarm Alarm A...

Страница 12: ...32 to 127 X X 2 24 Channel 1 fan speed mode Manual Auto Auto Auto Auto 25 Channel 2 fan speed mode Manual Auto X X Auto 26 Channel 1 manual fan speed 0 10 X X X 27 Channel 2 manual fan speed 0 10 X X...

Страница 13: ...Sounder activation mode On Pre alarm On Alarm X X X 81 Day night mode enabled YES NO X X X 82 Monday is holiday YES NO X X X 83 Tuesday is holiday YES NO X X X 84 Wednesday is holiday YES NO X X X 85...

Страница 14: ...t X X User can configure a specific delay between fault condition and fault indication 0 240 s Fault F013 HIGH FLOW FAULT CH1 Channel 1 flow is over the configured limit X X User can configure a speci...

Страница 15: ...feet X Please clean the sensor Alert A009 COMPENSATION 0 6 DIRTY ALERT S1 The sensor 1 chamber is very dirty 0 6 feet X Please clean the sensor Alert A010 DRIFT LIMIT ALERT S1 The sensor 1 chamber is...

Страница 16: ...2 2 2 3 2 4 2 5 2 6 2 5 2 5 7 8 9 2 5 10 2 5 FAN SPEED 10 2 5 11 12 13 2 5 14 3 15 3 16 3 17 3 5 18 3 5 3 5 END 4 4 Example Pipe Configuration 1 Channel Single Pipe 100m x 18 Holes Class C Hole 2 Hol...

Страница 17: ...ing 5 10 10 10 10 10 10 5 4 8 75m 0 2 75m HOLE SIZE mm 1 2 5 2 2 5 3 2 5 4 3 5 3 6 3 7 3 8 3 9 3 10 3 11 12 13 14 15 16 17 18 END END HOLE Typical Example Pipe Configuration 1 Channel T Piece 2 Pipes...

Страница 18: ...Configuration 1 Channel Single Pipe With Filter Class C FILTER HOLE SIZE mm 1 3 5 2 4 3 3 4 3 5 3 5 END 3 5 Hole 4 Hole 3 Hole 2 Hole 1 5 3 5 6 7 3 5 6 Hole 6 6 6 6 6 Hole 7 6 6 End hole FAN SPEED 6 3...

Страница 19: ...D200 100 00 19 I56 3888 005 System Sensor Europe Pittway Tecnologica S r l Via Caboto 19 3 34147 TRIESTE Italy http www systemsensoreurope com...

Отзывы: