PARAMETER
PARAMETER RANGE
1 Channel
1 Sensor
1 Channel
2 Sensor
2 Channel
2 Sensor
44 Auxiliary relay set on flow fault
YES/NO
NO
NO
NO
45 Auxiliary relay set on sensor
communication fault
YES/NO
NO NO NO
46 Auxiliary relay set on power restart
alert
YES/NO
NO NO NO
47 Auxiliary relay is latched
YES/NO
NO
NO
NO
48 External input normal state
OPEN, SHORT
OPEN
OPEN
OPEN
49 External input triggers fault
YES/NO
NO
NO
NO
50 External input silences sounders
YES/NO
NO
NO
NO
51 External input reset device
YES/NO
YES
YES
YES
52 External input disables ASD
YES/NO
NO
NO
NO
53 External input ASD disabling time
1..1440 min
60
60
60
54 Pre-alarm delay
0 (OFF), 1..240 s
0
0
0
55 Pre-alarm and Alarm are in
cascade
YES,
NO
NO NO NO
58 Day start time
HH:MI
08:00
08:00
08:00
59 Day end time
HH:MI
17:00
17:00
17:00
60 Holiday day #1 date
DD/MM
empty
empty
empty
…
DD/MM
empty empty empty
79 Holiday day #20 date
DD/MM
empty
empty
empty
80 Sounder activation mode
On Pre-alarm, On Alarm
Alarm
Alarm
Alarm
81
Day/night
mode
enabled YES/NO
NO NO NO
82 Monday is holiday
YES/NO
NO
NO
NO
83 Tuesday is holiday
YES/NO
NO
NO
NO
84 Wednesday is holiday
YES/NO
NO
NO
NO
85
Thursday
is
holiday
YES/NO
NO NO NO
86 Friday is holiday
YES/NO
NO
NO
NO
87
Saturday
is
holiday
YES/NO
NO NO NO
88 Sunday is holiday
YES/NO
NO
NO
NO
89 Sensor 1 day alarm level
1 . .9
1
1
1
90 Sensor 2 day alarm level
1..9
1
1
1
91 Sensor 1 day pre-alarm level
1..9
1
1
1
92 Sensor 2 day pre-alarm level
1..9
1
1
1
93 Sensor 1 night alarm level
1..9
1
1
1
94 Sensor 2 night alarm level
1..9
1
1
1
95 Sensor 1 night pre-alarm level
1..9
1
1
1
96 Sensor 2 night pre-alarm level
1..9
1
1
1
97 Alarm mode
Sensor alarm mode, module alarm
mode
X X X
98 Sensor communication timeout
0 (Disabled),1…240 s
X
X
X
99 Remote output time for alarm
50, 100,...10000ms
X
X
X