System Sensor FAAST FL0111E-HS Скачать руководство пользователя страница 7

D200-101-01

7

I56-6574-000

Table 4: Front Panel Indicators and Fault Descriptions

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

Figure 11:

User Interface

Buttons

Front Panel Buttons

The  front  panel  has  3  user  buttons: 

TEST

RESET

 and 

DISABLE

These buttons are used to enter the pass-code which then allows the 

user to carry out simple test functions. 

Note: In 

Remote Maintenance and Service Mode

, these buttons are 

always disabled.

BUTTON 

NORMAL Mode 

MAINTENANCE Mode 

RESET      

When pressed for 2 s, starts PASSWORD 

PROCEDURE to enter Maintenance 

mode.

When pressed for 2 s latched alarms, faults and 

sounders (relays) are reset 
 In DISABLE Mode, if pressed for 2 s unit will exit from 

DISABLE Mode but remains in MAINTENANCE Mode 

DISABLE  

Used to increment  Password digits in 

PASSWORD PROCEDURE

When pressed for 2 s, device enters DISABLE Mode 

for 60 minutes (default). (Alarms, alerts and faults not 

reported). 
(To exit DISABLE Mode see RESET) 

TEST         

Used to confirm password in PASSWORD 

PROCEDURE. Default Password = 3111

When pressed for 2 s and released, both sensors will 

simulate alarm 
When pressed for 4 s and released, sensor #1 will 

simulate alarm 
When pressed for 6 s and released, sensor #2 will 

simulate alarm 

Warning: Outputs will be activated by test

COMBINATIONS 

RESET + DISABLE 

When pressed for 2 s, shows fan speed 

(on smoke level scales) for a preset time. 

When pressed for 2 s, shows fan speed (on smoke 

level scales) for preset time. 

RESET + TEST 

No action 

When pressed for 2 s, turns off sounders 

RESET + TEST + DISABLE 

No action 

When pressed for 2 s, unit exits from MAINTENANCE 

Mode 

Table 5: Front Panel Buttons

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

INDICATOR 

ACTION 

WARNING OR TROUBLE 

COMMENT / ACTION 

CHANNEL 1/2 

ALARM

ON Red 

Channel is in alarm (relay is set) 

No delay with default settings 

1 BLINK Green 

when sensor is polled   

Not in alarm 

CHANNEL 1/2 PRE-

ALARM

ON Yellow 

Channel is in pre-alarm (relay is set)   

 

SMOKE  LEVEL 

ON Yellow 

Led number indicates sensor alarm level 

reached

Only numbers 1 – 9 used 

INITIALIZATION 

ON Yellow 

FAAST LT is in initialization 

 

FAULT 

ON Yellow 

Common or multiple faults 

 

1 BLINK Yellow 

Fault delay 

Default = 60s. 

POWER 

ON Green 

FAAST LT is powered 

 

POWER FAULT 

ON Yellow 

Low / high voltage range warning 

Check PSU wiring and voltage. 

1 BLINK Yellow 

Power on alert 

Disabled as default 

CHANNEL FLOW 

INDICATORS 1/2   

ON Green 

The LED indicates the air flow  for a  

channel:

-

  Centre = normal flow 

-

  Left = flow low; (-20% at extreme) 

-

  Right = flow high; (+20% at extreme) 

On 2 channel unit: 

Upper row = Ch1 

Lower row = Ch2 

INDICATOR 

ACTION 

WARNING OR TROUBLE 

COMMENT / ACTION 

LOW FLOW 

1 BLINK Yellow 

Fault delay in progress 

Default is 60s; general fault set at end of delay 

ON Yellow 

Low flow fault 

Check filter; check pipe network for blockages. 

SENSOR 

1 BLINK Yellow 

Sensor initialization fault 

Try to restart device.  

Replace faulty sensor. 

2 BLINKS Yellow 

Sensor communication fault 

Che

ck sensor addresses and installation; replace 

sensor.

ASPIRATOR 

ON Yellow 

Air flow sensor fault 

Try to restart device. 

1 BLINK Yellow 

Flow initialization fault

Check filter; check pipe network for blockages. Try 

to restart the device. 

2 BLINKS Yellow 

Fan fault 

Try to restart device. 

DRIFT 

COMPENSATION 

1 BLINK Yellow 

Drift compensation, 1st alert 

Clean sensor 

2 BLINKS Yellow 

Drift compensation, 2nd alert 

Clean sensor 

3 BLINKS Yellow 

Drift compensation limit warning 

Sensor needs urgent maintenance 

TEMPERATURE 

1 BLINK Yellow 

Low temperature alert 

Check the air flow temperature 

2 BLINKS Yellow 

High temperature alert 

Check the air flow temperature 

INPUT  

1 BLINK Yellow 

External input fault 

Not used with default settings 

DISABLE  

1 BLINK Yellow 

Alarms, faults & alerts not reported 

Returns to Maintenance then Normal operation 

after 60min (default) 

SYSTEM 

1 BLINK Yellow 

Wrong configuration 

Flashes all FAULT LEDs. Try to restart device. 

2 BLINKS Yellow 

EEPROM fault 

Check power supply voltage. Try to restart device 

3 BLINKS Yellow 

Real time clock fault 

RTC is corrupted or time reading failed.  

SOUNDER 

1 BLINK Yellow 

Sounder fault 

Check the sounder circuit and the EOL 

FILTER 

1 BLINK Yellow 

Filter alert at set date 

No date set as default 

HIGH FLOW 

1 BLINK Yellow 

Fault delay in progress 

Default is 60s; general fault set at end of delay 

ON Yellow 

High flow fault 

Check pipe network for breaks or leaks. 

In case of simultaneous alerts/faults on the same LED, priority

 order is: ON (Highest), 1 blink, 2 blinks, 3 blinks (Lowest)

Содержание FAAST FL0111E-HS

Страница 1: ...it Warning The performance of this system is dependent upon the pipe network Any extension or modification to the designed installation may cause improper operation The operational effects of such changes need to be verified using the PipeIQ design software This equipment and all associated pipe work must be installed in accordance with all relevant codes and regulations PARTS LIST Description Qua...

Страница 2: ... place remove the protector from the bottom of the clear cover to stick the cover down as shown in Figure 3 Figure 5 Mounting Bracket FAAST LT 200 HANGING LUGS INDICATES CENTRE OF ASPIRATING PIPES FIXING HOLE FIXING HOLE USE FOR PLUMB LINE 90 mm 99 mm 59 329 212 mm 144 mm 41 mm mm mm POSITION OF BRACKET PLUMB LINE BASE OUTLINE OUTER DIMENSION OF UNIT 1 2 3 4 5 6 7 8 9 10 1 11213 Minimum clearance ...

Страница 3: ...es not used should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using highest level 1 sensitivity 1 2 3 4 5 6 CHANNEL 1 CHANNEL 2 ONLY FUNCTION ON 2 CHANNEL UNITS CHANNEL 1 NOT USED FOR COMMON CHAMBER UNIT CHANNEL 2 ONLY FUNCTIONS ON 2 CHANNEL AND COMMON CHAMBER UNITS FAAST LT MODEL INLET PIPE HOLE OUTLET P...

Страница 4: ...f the unit to lever open the door as shown above SAMPLING AREA SAMPLING AREA Whenever the FAAST LT 200 is installed outside the risk area return of the exhaust air back into the protected area can reduce flow faults due to pressure difference MODULE MOUNT MODULE MOUNT F LT PMB MODULE MOUNT KIT OPTIONAL If required an input output module can be installed into the FAAST LT 200 unit The optional modu...

Страница 5: ...CIFICATION MIN MAX UNITS COMMENTS Contact Rating 2 0 5 A A 30 VDC resistive load 30 VAC resistive load Life Time 105 Operations 1N6284CA FAAST LT FAAST LT C L FAAST LT R C L WARNING Switching Inductive Loads Fitting the Terminal Blocks To insert the terminal blocks into the unit use the following method 1 Insert a corner of the block into the slot see a 2 Push the length of the block into the slot...

Страница 6: ...A TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L O W H IG H F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 TEMPERA TURE INPUT 10b FL0122E HS 2 Channel Detector POWERING UP Using Default Settings 1 Connect a suitable 24VDC supply complying with European Standard EN 54 4 to pins 1 and 2 on terminal block T1 See Table 2 2 Check the voltage at the...

Страница 7: ... INITIALIZATION ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 INDICATOR ACTION WARNING OR TROUBLE COMMENT ACTION CHANNEL 1 2 ALARM ON Red Channel is in alarm relay is set No delay with default settings 1 BLINK Green when sensor is polled Not in alarm CHANNEL 1 2 PRE ALARM ON Yellow Channel is in pre alarm relay is set SMOKE LEVEL ON Yellow Led number indicates sensor alarm level reached...

Страница 8: ...troduce smoke particulates into the system It is recommended that smoke with a particulate life cycle of greater than 120s should be used standard aerosol sprays for point detector testing do not work well on aspirated systems Fault Testing Simulate a fault on the detector for example block the outlet pipe and check that a fault is signalled on both the front panel of the unit and at the CIE Fire ...

Страница 9: ...ernal port in the centre of the device to a spare USB port on the PC make sure that the USB connector is pushed fully into the FAAST LT 200 port until it clicks The device will now be in Remote Maintenance mode The USB connection must be made within 5 minutes of entering the Maintenance mode password The first time a PC running PipeIQ is connected to a FAAST LT 200 device the USB port drivers will...

Страница 10: ... 45l min 6 Repeat from step 3 adjust hole diameters and fan speed to achieve all the above figures 7 Next check that the sample hole sensitivity is practical for the chosen class i e it is not too sensitive Ideally to avoid false alarms hole sensitivity for a class C system should be 1 m or greater and certainly 0 5 m 8 If necessary change the Alarm level to reduce the sample hole sensitivity The ...

Страница 11: ...76 98 60 6 4 4 45 0 6 1 14 3 10 87 98 50 5 4 5 4 5 45 0 62 0 98 3 9 95 44 40 4 4 5 4 5 45 0 76 0 80 3 10 79 53 30 3 5 5 46 0 83 1 29 4 10 78 55 20 2 5 5 5 5 45 0 92 0 97 4 10 71 28 10 1 6 5 6 5 45 1 1 31 5 10 66 37 Non sensing end hole CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE END HOLE SIZE AND 10m SPACING 2 PIPE T FORM Per pipe length Number of holes Hole size End hole Air flow Flow balance Av...

Страница 12: ...pe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117 83 40 3 4 5 4 5 46 0 89 0 40 1 5 95 44 30 3 4 4 46 0 93 0 40 1 7 75 41 20 2 5 5 46 0 96 0 40 2 6 78 55 10 1 6 5 6 5 44 1 0 33 3 8 66 37 CLASS B PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 1 PIP...

Страница 13: ... 83 0 20 1 9 84 83 20 2 6 5 6 5 44 0 94 0 14 1 10 66 37 10 X X No adequate or recommended single sample hole size design CLASS A PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 2 PIPE T FORM Each pipe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117...

Отзывы: