background image

D200-101-01

8

I56-6574-000  

Password Sequence to Enter 

Maintenance

 Mode

Filters

Periodic cleaning or replacement of the filters will be required. 
The  filters  are  located  inside  the  cabinet  at  the  top  of  the  unit  (see 

Figure 9 displayed earlier in the guide) and are removed as shown in 

the sequence below:

Either replace the filter assembly or carefully brush off the accumulated 

dust. (Replacement filter part number: FL-IF-6.)

Note:

 If replacing the filter, remove the foam gasket from the old filter 

and place onto the new filter. When placing the new filter into the slot, 

ensure that the gasket is correctly aligned.

Refit the filter, close and secure the cabinet door. The unit will initialise 

and restart.

Smoke Sensors

The smoke sensors are located under the sensor cover (see Figure 

9 displayed earlier in the guide). To access the sensors, follow the 

sequence below:

 

F  i lters 

  

Either replace the filter assembly or carefully brush off the accumulated dust. 

Refit the filter, close and secure the cabinet door. The unit will initialise and restart. 

  

 

 

 

 

  

  

 

Smoke Sensors 

1

2

3

1

2

3

FOAM GASKET

4

The 

Default Password

 is 

3111

.

If no button is pressed for 10s during the password sequence, the unit 

returns to 

Normal

 mode. 

Exit from 

Maintenance

 Mode

press the three front panel user interface buttons 

TEST

RESET

 and 

DISABLE

 simultaneously for 2 seconds. 

Alternatively, reset the unit using the 

Remote Input

 (when set to 

default value) or power the device off and on again.

If there is no activity in 

Maintenance

 mode for 5 minutes (default), the 

FAULT

 indicator blinks green for 15s and then the unit automatically 

returns to the 

Normal

 state.

TESTING

Magnet Test

The alarm signalling can be tested for functionality by placing a test 

magnet in the position shown in Figure 9 (displayed earlier in the 

guide). This  method  does  not  reflect  EN54  standards  and  does  not 

test the air flow in the pipe-work.

Smoke Testing

The system alarm response can be tested for functionality using 

smoke. The choice of smoke source is dependant on the installation 

but in all cases the smoke must be present for the duration of the test. 

Smoke pellets or matches can be used close to the sampling point to 

introduce smoke particulates into the system. It is recommended that 

smoke with a particulate life cycle of greater than 120s should be used 

– standard aerosol sprays for point detector testing do not work well 

on aspirated systems

.

Fault Testing 

Simulate a fault on the detector (for example, block the outlet pipe) and 

check that a fault is signalled on both the front panel of the unit and at 

the CIE (Fire Panel).

SERVICE

WARNING

Isolate the aspirating detector from the fire alarm system to prevent any 

unwanted alarms when opening the front door of the unit. Make sure 

all power is removed from the system before removing any covers. 

Service Mode

Opening the cabinet door during normal operation will cause the unit 

to enter 

Service

 Mode. The 

FILTER

 LEDs will blink, the unit will switch 

off power to the fans and the fault relay will indicate a fault. When the 

cabinet door is closed, the unit restarts automatically.

1)  Press and hold 

RESET

;  Left  flow  indicator  will  turn 

yellow, then green.

2) Release 

RESET

 and 

FAULT

 indicator will switch on 

green. The left flow indicator will blink green indicating 

the device is ready for the first digit.

3) Press 

DISABLE

 to increment the LEDs 1…9.

4) Press 

TEST

 to select a digit.

5)  The flashing airflow segment will turn solid green and 

the next segment will begin to flash indicating set the 

next digit. 

6)  When  the  4th  digit  is  selected,  all  4  airflow  segments 

are  turned  off.  If  the  password  is  accepted  the 

FAULT

 indicator will remain green and the unit enters 

Maintenance

 mode. If the password is incorrect the 

FAULT

 indicator flashes yellow and the unit remains in 

Normal

 mode. 

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

Содержание FAAST FL0111E-HS

Страница 1: ...it Warning The performance of this system is dependent upon the pipe network Any extension or modification to the designed installation may cause improper operation The operational effects of such changes need to be verified using the PipeIQ design software This equipment and all associated pipe work must be installed in accordance with all relevant codes and regulations PARTS LIST Description Qua...

Страница 2: ... place remove the protector from the bottom of the clear cover to stick the cover down as shown in Figure 3 Figure 5 Mounting Bracket FAAST LT 200 HANGING LUGS INDICATES CENTRE OF ASPIRATING PIPES FIXING HOLE FIXING HOLE USE FOR PLUMB LINE 90 mm 99 mm 59 329 212 mm 144 mm 41 mm mm mm POSITION OF BRACKET PLUMB LINE BASE OUTLINE OUTER DIMENSION OF UNIT 1 2 3 4 5 6 7 8 9 10 1 11213 Minimum clearance ...

Страница 3: ...es not used should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using highest level 1 sensitivity 1 2 3 4 5 6 CHANNEL 1 CHANNEL 2 ONLY FUNCTION ON 2 CHANNEL UNITS CHANNEL 1 NOT USED FOR COMMON CHAMBER UNIT CHANNEL 2 ONLY FUNCTIONS ON 2 CHANNEL AND COMMON CHAMBER UNITS FAAST LT MODEL INLET PIPE HOLE OUTLET P...

Страница 4: ...f the unit to lever open the door as shown above SAMPLING AREA SAMPLING AREA Whenever the FAAST LT 200 is installed outside the risk area return of the exhaust air back into the protected area can reduce flow faults due to pressure difference MODULE MOUNT MODULE MOUNT F LT PMB MODULE MOUNT KIT OPTIONAL If required an input output module can be installed into the FAAST LT 200 unit The optional modu...

Страница 5: ...CIFICATION MIN MAX UNITS COMMENTS Contact Rating 2 0 5 A A 30 VDC resistive load 30 VAC resistive load Life Time 105 Operations 1N6284CA FAAST LT FAAST LT C L FAAST LT R C L WARNING Switching Inductive Loads Fitting the Terminal Blocks To insert the terminal blocks into the unit use the following method 1 Insert a corner of the block into the slot see a 2 Push the length of the block into the slot...

Страница 6: ...A TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L O W H IG H F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 TEMPERA TURE INPUT 10b FL0122E HS 2 Channel Detector POWERING UP Using Default Settings 1 Connect a suitable 24VDC supply complying with European Standard EN 54 4 to pins 1 and 2 on terminal block T1 See Table 2 2 Check the voltage at the...

Страница 7: ... INITIALIZATION ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 INDICATOR ACTION WARNING OR TROUBLE COMMENT ACTION CHANNEL 1 2 ALARM ON Red Channel is in alarm relay is set No delay with default settings 1 BLINK Green when sensor is polled Not in alarm CHANNEL 1 2 PRE ALARM ON Yellow Channel is in pre alarm relay is set SMOKE LEVEL ON Yellow Led number indicates sensor alarm level reached...

Страница 8: ...troduce smoke particulates into the system It is recommended that smoke with a particulate life cycle of greater than 120s should be used standard aerosol sprays for point detector testing do not work well on aspirated systems Fault Testing Simulate a fault on the detector for example block the outlet pipe and check that a fault is signalled on both the front panel of the unit and at the CIE Fire ...

Страница 9: ...ernal port in the centre of the device to a spare USB port on the PC make sure that the USB connector is pushed fully into the FAAST LT 200 port until it clicks The device will now be in Remote Maintenance mode The USB connection must be made within 5 minutes of entering the Maintenance mode password The first time a PC running PipeIQ is connected to a FAAST LT 200 device the USB port drivers will...

Страница 10: ... 45l min 6 Repeat from step 3 adjust hole diameters and fan speed to achieve all the above figures 7 Next check that the sample hole sensitivity is practical for the chosen class i e it is not too sensitive Ideally to avoid false alarms hole sensitivity for a class C system should be 1 m or greater and certainly 0 5 m 8 If necessary change the Alarm level to reduce the sample hole sensitivity The ...

Страница 11: ...76 98 60 6 4 4 45 0 6 1 14 3 10 87 98 50 5 4 5 4 5 45 0 62 0 98 3 9 95 44 40 4 4 5 4 5 45 0 76 0 80 3 10 79 53 30 3 5 5 46 0 83 1 29 4 10 78 55 20 2 5 5 5 5 45 0 92 0 97 4 10 71 28 10 1 6 5 6 5 45 1 1 31 5 10 66 37 Non sensing end hole CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE END HOLE SIZE AND 10m SPACING 2 PIPE T FORM Per pipe length Number of holes Hole size End hole Air flow Flow balance Av...

Страница 12: ...pe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117 83 40 3 4 5 4 5 46 0 89 0 40 1 5 95 44 30 3 4 4 46 0 93 0 40 1 7 75 41 20 2 5 5 46 0 96 0 40 2 6 78 55 10 1 6 5 6 5 44 1 0 33 3 8 66 37 CLASS B PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 1 PIP...

Страница 13: ... 83 0 20 1 9 84 83 20 2 6 5 6 5 44 0 94 0 14 1 10 66 37 10 X X No adequate or recommended single sample hole size design CLASS A PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 2 PIPE T FORM Each pipe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117...

Отзывы: