background image

D200-101-01

5

I56-6574-000

Table 2: Wiring Terminal Designations

(Note - Terminals marked CH2 will only be available on 2 channel 

models)

Table 3: Relays

No.

Function

Ext Power In + 

 

Primary PSU  

T1

Ext Power In - 

 

Primary PSU  

Aux Power In + 

 

Not used in default 

Aux Power In  - 

 

Not used in default 

NC Alarm Relay  

CH1  

T2

C Alarm Relay  

CH1  

NO Alarm Relay  

CH1  

NC Alarm Relay  

CH2  

T3

C Alarm Relay  

CH2  

10 

NO Alarm Relay  

CH2  

11 

NC Fault Relay  

CH1  

T4

12 

C Fault Relay  

CH1  

13 

NO Fault Relay  

CH1  

14 

NC Fault Relay (AUX) 

CH2  

T5

15 

C Fault Relay (AUX) 

CH2  

16 

NO Fault Relay (AUX) 

CH2  

17 

Sounder Output 1 - 

47 k-ohm EOL Resistor 

T6 

18 

Sounder Output 1 + 

19 

Sounder Output 2 - 

47 k-ohm EOL Resistor 

T7 

20 

Sounder Output 2 +  

21 

Configurable Input + 

(Reset) Default is active = short circuit 

(unsupervised)

T8

22 

Configurable Input - 

(Reset)

23 

NC Pre-Alarm Relay  

CH1  

T9

24 

C Pre-Alarm Relay  

CH1  

25 

NO Pre-Alarm Relay   

CH1  

26 

NC Pre-Alarm Relay  

CH2  

T10

27 

C Pre-Alarm Relay  

CH2  

28 

NO Pre-Alarm Relay  

CH2  

Table 3a: Relay Electrical Specification

SPECIFICATION 

MIN MAX 

UNITS 

COMMENTS 

Contact Rating 

 2 

0.5

A

A

30 VDC resistive load 

30 VAC resistive load 

Life Time 

10

5

   Operations 

 

1N6284CA

FAAST LT

FAAST LT

C

L

FAAST LT

R

C

L

WARNING: Switching Inductive Loads

Fitting the Terminal Blocks

To insert the terminal blocks into the unit use the following method:

1  Insert a corner of the block into the slot (see 

a

).

2  Push the length of the block into the slot until the block ‘clicks’ into 

place, the 2 upper hooks on the block should be visible (see 

c

).

a

b

c

RELAY 

ACTION: 

NOTES 

ALARM 1 or 2 

Set ON when ALARM CONDITION is met 

on a channel  

Default condition = Level 1. Alarm state is 

latched as default.  A manual RESET is 

necessary to deactivate  LED and relay. 

PRE-ALARM 1 or 2  

Set ON when PRE-ALARM CONDITION 

is met on channel. 

Default condition = Level 1. NOTE: When 

Pre-ALARM = ALARM = Level 1, Pre-ALARM 

will actually respond at 70% of Level 1. 

FAULT 1 or 2 

When FAULT CONDITION on Ch1 or Ch2 

or a common FAULT occurs. Fault is also 

indicated when in SERVICE mode and 

when the unit is unpowered.  

Fault state is not latched (default) 

SOUNDER 1 or 2 

Set ON when a channel is in ALARM / 

PRE-ALARM. Sounder 1 corresponds to 

Ch1 and Sounder 2 corresponds to Ch2 

Default condition = set on in ALARM. 

Содержание FAAST FL0111E-HS

Страница 1: ...it Warning The performance of this system is dependent upon the pipe network Any extension or modification to the designed installation may cause improper operation The operational effects of such changes need to be verified using the PipeIQ design software This equipment and all associated pipe work must be installed in accordance with all relevant codes and regulations PARTS LIST Description Qua...

Страница 2: ... place remove the protector from the bottom of the clear cover to stick the cover down as shown in Figure 3 Figure 5 Mounting Bracket FAAST LT 200 HANGING LUGS INDICATES CENTRE OF ASPIRATING PIPES FIXING HOLE FIXING HOLE USE FOR PLUMB LINE 90 mm 99 mm 59 329 212 mm 144 mm 41 mm mm mm POSITION OF BRACKET PLUMB LINE BASE OUTLINE OUTER DIMENSION OF UNIT 1 2 3 4 5 6 7 8 9 10 1 11213 Minimum clearance ...

Страница 3: ...es not used should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using highest level 1 sensitivity 1 2 3 4 5 6 CHANNEL 1 CHANNEL 2 ONLY FUNCTION ON 2 CHANNEL UNITS CHANNEL 1 NOT USED FOR COMMON CHAMBER UNIT CHANNEL 2 ONLY FUNCTIONS ON 2 CHANNEL AND COMMON CHAMBER UNITS FAAST LT MODEL INLET PIPE HOLE OUTLET P...

Страница 4: ...f the unit to lever open the door as shown above SAMPLING AREA SAMPLING AREA Whenever the FAAST LT 200 is installed outside the risk area return of the exhaust air back into the protected area can reduce flow faults due to pressure difference MODULE MOUNT MODULE MOUNT F LT PMB MODULE MOUNT KIT OPTIONAL If required an input output module can be installed into the FAAST LT 200 unit The optional modu...

Страница 5: ...CIFICATION MIN MAX UNITS COMMENTS Contact Rating 2 0 5 A A 30 VDC resistive load 30 VAC resistive load Life Time 105 Operations 1N6284CA FAAST LT FAAST LT C L FAAST LT R C L WARNING Switching Inductive Loads Fitting the Terminal Blocks To insert the terminal blocks into the unit use the following method 1 Insert a corner of the block into the slot see a 2 Push the length of the block into the slot...

Страница 6: ...A TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L O W H IG H F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 TEMPERA TURE INPUT 10b FL0122E HS 2 Channel Detector POWERING UP Using Default Settings 1 Connect a suitable 24VDC supply complying with European Standard EN 54 4 to pins 1 and 2 on terminal block T1 See Table 2 2 Check the voltage at the...

Страница 7: ... INITIALIZATION ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 INDICATOR ACTION WARNING OR TROUBLE COMMENT ACTION CHANNEL 1 2 ALARM ON Red Channel is in alarm relay is set No delay with default settings 1 BLINK Green when sensor is polled Not in alarm CHANNEL 1 2 PRE ALARM ON Yellow Channel is in pre alarm relay is set SMOKE LEVEL ON Yellow Led number indicates sensor alarm level reached...

Страница 8: ...troduce smoke particulates into the system It is recommended that smoke with a particulate life cycle of greater than 120s should be used standard aerosol sprays for point detector testing do not work well on aspirated systems Fault Testing Simulate a fault on the detector for example block the outlet pipe and check that a fault is signalled on both the front panel of the unit and at the CIE Fire ...

Страница 9: ...ernal port in the centre of the device to a spare USB port on the PC make sure that the USB connector is pushed fully into the FAAST LT 200 port until it clicks The device will now be in Remote Maintenance mode The USB connection must be made within 5 minutes of entering the Maintenance mode password The first time a PC running PipeIQ is connected to a FAAST LT 200 device the USB port drivers will...

Страница 10: ... 45l min 6 Repeat from step 3 adjust hole diameters and fan speed to achieve all the above figures 7 Next check that the sample hole sensitivity is practical for the chosen class i e it is not too sensitive Ideally to avoid false alarms hole sensitivity for a class C system should be 1 m or greater and certainly 0 5 m 8 If necessary change the Alarm level to reduce the sample hole sensitivity The ...

Страница 11: ...76 98 60 6 4 4 45 0 6 1 14 3 10 87 98 50 5 4 5 4 5 45 0 62 0 98 3 9 95 44 40 4 4 5 4 5 45 0 76 0 80 3 10 79 53 30 3 5 5 46 0 83 1 29 4 10 78 55 20 2 5 5 5 5 45 0 92 0 97 4 10 71 28 10 1 6 5 6 5 45 1 1 31 5 10 66 37 Non sensing end hole CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE END HOLE SIZE AND 10m SPACING 2 PIPE T FORM Per pipe length Number of holes Hole size End hole Air flow Flow balance Av...

Страница 12: ...pe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117 83 40 3 4 5 4 5 46 0 89 0 40 1 5 95 44 30 3 4 4 46 0 93 0 40 1 7 75 41 20 2 5 5 46 0 96 0 40 2 6 78 55 10 1 6 5 6 5 44 1 0 33 3 8 66 37 CLASS B PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 1 PIP...

Страница 13: ... 83 0 20 1 9 84 83 20 2 6 5 6 5 44 0 94 0 14 1 10 66 37 10 X X No adequate or recommended single sample hole size design CLASS A PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 2 PIPE T FORM Each pipe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117...

Отзывы: