System Sensor FAAST FL0111E-HS Скачать руководство пользователя страница 10

D200-101-01

10

I56-6574-000  

APPENDIX A - PipeIQ™ and PIPE SYSTEM DESIGN

Set number of 

holes and hole 

spacing

Start Project 

and create 

pipe layout

Set sample hole 

diameters and fan 

speed

Is air flow 

c.45l/min?

Are the 

parameters in 

range?

Is the flow 

balance 

≥ 0.5?

Is hole 

sensitivity OK 

for class?

Change alarm 

level

Save design

Y

N

Y

N

Y

Y

N

N

Review pipe 

layout

Is a design 

possible?

N

Y

??

PIPE DESIGN METHODOLOGY FLOW CHART

 

Pipe Design Methodology Flow Chart

USING PipeIQ™

 for

 SYSTEM DESIGN

PipeIQ is a design application to help a user create EN54 compliant 

pipe layouts. Generating a suitable working design will require some 

thought and understanding of the interacting variables in an aspirating 

system. 
The following methodology can assist when trying to design a pipe 

network using PipeIQ. By following this sequence of steps, it should 

be possible to arrive at an acceptable design (assuming one exists) 

that has adequate air flow and hole sensitivity to operate within the 

overall limits of the aspirating device. (See 

Pipe Design Methodology 

Flow Chart

.)

Suggested Design Methodology

1.  Start a project in PipeIQ, choose the detector type, select the 

aspirating class and follow the instructions to add a detector and 

create a representation of the physical pipe layout. 

 

To optimise the design:

2.   In the 

Manage Pipe – Edit Properties

 window, set the number 

of sample holes and hole spacing in the pipe network to comply 

with local fire regulations and the EN54 approved figures. The hole 

diameters can also be set in this window, or changed later. To end, 

click 

Update Holes

 and then 

OK

.

3.   In the 

Design

 tab, click on the 

Calculations

 button; the 

Calculation

 

window will appear. Set the sample hole diameters and fan speed 

to get the flow in the detector close to 45l/min. 

4.  Repeat step (3) above to eliminate any red boxes (out-of-range 

sensitivity, transport time etc.)

5.   Check the flow balance is ≥0.5. Using the auto-balance button will 

probably  create  multiple  sample  hole  diameters  along  the  pipe; 

avoid using this button if a single hole size is required. Be aware 

that the auto-balance function may also reduce the pipe air flow, 

ensure this is set back close to 45l/min.

6.  Repeat from step (3), adjust hole diameters and fan speed to 

achieve all the above figures.

7.  Next, check that the sample hole sensitivity is practical for the 

chosen class, i.e. it is not too sensitive. Ideally, to avoid false 

alarms, hole sensitivity for a class C system should be 1%/m or 

greater and certainly >0.5%/m.

8.   If necessary, change the 

Alarm

 level to reduce the sample hole 

sensitivity. The detector sensitivity is set from the 

Configuration

 

tab.

9.   Repeat from step (3) to finalise the pipe design and save.

Tips to achieve an adequate design

Maintain the air flow in a FAAST LT-200 unit at, or around, its 

optimum 

setting of 45 l/min

. Increase/decrease hole diameters and fan speed 

to achieve this.
Fewer holes in a pipe will tend to increase the sample hole sensitivity. 

Adding extra holes close together may mathematically appear to 

reduce the hole sensitivity, but in practical terms the system sensitivity 

will remain high. Change the alarm level to raise or lower the sensitivity 

of the sample holes.

Changing  the  hole  diameter  will  affect  the  hole  sensitivity  and  the 

hole balance. Smaller holes may improve the balance but will reduce 

the overall flow. Ensure this remains as close to 45l/min as possible. 

It is recommended that the flow balance is not less than 0.5 for an 

acceptable design.

Longer pipes will obviously have longer transport times; they also tend 

to reduce the air flow, which further extends the transport time. Rather 

than using one long single pipe, the use of a ‘T’ tap or two pipes per 

channel can reduce long pipe runs and reduce the transport time. It 

also helps with maintaining the air flow speed at the optimal level, since 

it is equivalent to increasing the pipe diameter to the aspirating device; 

but beware the flow does not get too high. In twin pipe systems it may 

be necessary to reduce hole sizes, compared with a single pipe, to 

achieve optimal flow. Alternatively, the fan speed can also be reduced, 

but both these actions will increase the transport time.
Use of the 

Auto-balance

 button in PipeIQ will probably give the holes in 

the pipe design a variety of different diameters. If one size of hole in the 

sample pipe is desirable (for simpler installation and commissioning) 

do not use this button. Pipes with equal size sample holes are also 

easier to test – the farthest end sample hole will be the least sensitive.

Содержание FAAST FL0111E-HS

Страница 1: ...it Warning The performance of this system is dependent upon the pipe network Any extension or modification to the designed installation may cause improper operation The operational effects of such changes need to be verified using the PipeIQ design software This equipment and all associated pipe work must be installed in accordance with all relevant codes and regulations PARTS LIST Description Qua...

Страница 2: ... place remove the protector from the bottom of the clear cover to stick the cover down as shown in Figure 3 Figure 5 Mounting Bracket FAAST LT 200 HANGING LUGS INDICATES CENTRE OF ASPIRATING PIPES FIXING HOLE FIXING HOLE USE FOR PLUMB LINE 90 mm 99 mm 59 329 212 mm 144 mm 41 mm mm mm POSITION OF BRACKET PLUMB LINE BASE OUTLINE OUTER DIMENSION OF UNIT 1 2 3 4 5 6 7 8 9 10 1 11213 Minimum clearance ...

Страница 3: ...es not used should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using highest level 1 sensitivity 1 2 3 4 5 6 CHANNEL 1 CHANNEL 2 ONLY FUNCTION ON 2 CHANNEL UNITS CHANNEL 1 NOT USED FOR COMMON CHAMBER UNIT CHANNEL 2 ONLY FUNCTIONS ON 2 CHANNEL AND COMMON CHAMBER UNITS FAAST LT MODEL INLET PIPE HOLE OUTLET P...

Страница 4: ...f the unit to lever open the door as shown above SAMPLING AREA SAMPLING AREA Whenever the FAAST LT 200 is installed outside the risk area return of the exhaust air back into the protected area can reduce flow faults due to pressure difference MODULE MOUNT MODULE MOUNT F LT PMB MODULE MOUNT KIT OPTIONAL If required an input output module can be installed into the FAAST LT 200 unit The optional modu...

Страница 5: ...CIFICATION MIN MAX UNITS COMMENTS Contact Rating 2 0 5 A A 30 VDC resistive load 30 VAC resistive load Life Time 105 Operations 1N6284CA FAAST LT FAAST LT C L FAAST LT R C L WARNING Switching Inductive Loads Fitting the Terminal Blocks To insert the terminal blocks into the unit use the following method 1 Insert a corner of the block into the slot see a 2 Push the length of the block into the slot...

Страница 6: ...A TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L O W H IG H F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 TEMPERA TURE INPUT 10b FL0122E HS 2 Channel Detector POWERING UP Using Default Settings 1 Connect a suitable 24VDC supply complying with European Standard EN 54 4 to pins 1 and 2 on terminal block T1 See Table 2 2 Check the voltage at the...

Страница 7: ... INITIALIZATION ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 INDICATOR ACTION WARNING OR TROUBLE COMMENT ACTION CHANNEL 1 2 ALARM ON Red Channel is in alarm relay is set No delay with default settings 1 BLINK Green when sensor is polled Not in alarm CHANNEL 1 2 PRE ALARM ON Yellow Channel is in pre alarm relay is set SMOKE LEVEL ON Yellow Led number indicates sensor alarm level reached...

Страница 8: ...troduce smoke particulates into the system It is recommended that smoke with a particulate life cycle of greater than 120s should be used standard aerosol sprays for point detector testing do not work well on aspirated systems Fault Testing Simulate a fault on the detector for example block the outlet pipe and check that a fault is signalled on both the front panel of the unit and at the CIE Fire ...

Страница 9: ...ernal port in the centre of the device to a spare USB port on the PC make sure that the USB connector is pushed fully into the FAAST LT 200 port until it clicks The device will now be in Remote Maintenance mode The USB connection must be made within 5 minutes of entering the Maintenance mode password The first time a PC running PipeIQ is connected to a FAAST LT 200 device the USB port drivers will...

Страница 10: ... 45l min 6 Repeat from step 3 adjust hole diameters and fan speed to achieve all the above figures 7 Next check that the sample hole sensitivity is practical for the chosen class i e it is not too sensitive Ideally to avoid false alarms hole sensitivity for a class C system should be 1 m or greater and certainly 0 5 m 8 If necessary change the Alarm level to reduce the sample hole sensitivity The ...

Страница 11: ...76 98 60 6 4 4 45 0 6 1 14 3 10 87 98 50 5 4 5 4 5 45 0 62 0 98 3 9 95 44 40 4 4 5 4 5 45 0 76 0 80 3 10 79 53 30 3 5 5 46 0 83 1 29 4 10 78 55 20 2 5 5 5 5 45 0 92 0 97 4 10 71 28 10 1 6 5 6 5 45 1 1 31 5 10 66 37 Non sensing end hole CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE END HOLE SIZE AND 10m SPACING 2 PIPE T FORM Per pipe length Number of holes Hole size End hole Air flow Flow balance Av...

Страница 12: ...pe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117 83 40 3 4 5 4 5 46 0 89 0 40 1 5 95 44 30 3 4 4 46 0 93 0 40 1 7 75 41 20 2 5 5 46 0 96 0 40 2 6 78 55 10 1 6 5 6 5 44 1 0 33 3 8 66 37 CLASS B PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 1 PIP...

Страница 13: ... 83 0 20 1 9 84 83 20 2 6 5 6 5 44 0 94 0 14 1 10 66 37 10 X X No adequate or recommended single sample hole size design CLASS A PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 2 PIPE T FORM Each pipe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117...

Отзывы: