I56-6500-000 

 

 

©2016 System Sensor. 10-05

System Sensor®, PipeIQ®, and FAAST Fire Alarm Aspiration Sensing Technology® are registered trademarks of Honeywell International, Inc. 

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must 
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide 
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used 
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa-
tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try 
to correct the interference by one or more of the following measures:
 

– Reorient or relocate the receiving antenna.

 

– Increase the separation between the equipment and receiver.

 

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

 

– Consult the dealer or an experienced radio/TV technician for help.

This Class B digital apparatus complies with Canadian ICES-003.

FCC STATEMENT

System Sensor warrants its enclosed smoke detector to be free from defects in materials 
and workmanship under normal use and service for a period of three years from date 
of manufacture. System Sensor makes no other express warranty for this smoke detec-
tor. No agent, representative, dealer, or employee of the Company has the authority to 
increase or alter the obligations or limitations of this Warranty. The Company’s obligation 
of this Warranty shall be limited to the repair or replacement of any part of the smoke 
detector which is found to be defective in materials or workmanship under normal use 
and service during the three year period commencing with the date of manufacture. 
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return 
Authorization number, send defective units postage prepaid to: Honeywell, 12220 Rojas 

WARRANTY

Drive, Suite 700, El Paso, TX 79936, USA. Please include a note describing the malfunc-
tion and suspected cause of failure. The Company shall not be obligated to repair or 
replace units which are found to be defective because of damage, unreasonable use, 
modifications, or alterations occurring after the date of manufacture. In no case shall the 
Company be liable for any consequential or incidental damages for breach of this or any 
other warranty, expressed or implied whatsoever, even if the loss or damage is caused by 
the Company’s negligence or fault Some states do not allow the exclusion or limitation of 
incidental or consequential damages, so the above limitation or exclusion may not apply 
to you. This Warranty gives you specific legal rights, and you may also have other rights 
which vary from state to state.

This aspiration detector does not produce any hazardous laser radiation and is certified 
as a Class 1 laser product under the U.S. Department of Health and Human Services 
(DHHS) Radiation Performance Standard according to the Radiation Control for Health 
and Safety Act of 1968. Any radiation emitted inside the smoke detector is completely 
within the protective housings and external covers. 

The laser beam cannot escape from the detector during any phase of operation. 
The Center of Devices and Radiological Health (CDRH) of the U. S. Food and Drug 
Administration implemented regulations for laser products on August 2, 1976. These 
regulations apply to laser products manufactured after August 1, 1976. Compliance is 
mandatory for products marketed in the United States.

LASER SAFETY INFORMATION

The use of all FAAST products (configuration, design, use and maintenance) must be performed in accordance with the technical documentation, General Terms and Conditions and 
local regulations and/or directives for design, installation and maintenance of fire alarm systems. Product Manuals, User Guides, White Papers, CAD Drawings, Datasheets, Engineering 
specifications are available from www.systemsensor.com/faast. The performance of this system is dependent upon the pipe network. Any extensions or modifications to the designed 
installation may cause improper operation. The operational effects of such changes shall be verified. A design tool is available from System Sensor webpage.
Class 1, Div 2 - RJ45 Connector is for maintenance use only and shall not be used while in a Hazardous Location unless power has been removed or the area is known to be non-
hazardous. These units are tested and regulatory approved to allow the pipe networks to be installed in corrosive or hostile environments. The aspiration unit itself should operate in 
a controlled environment as per the specifications listed in the manual. The detector unit is not suitable to be installed in hostile environments. 
Exposure of the detector to silicone vapor must be avoided as it may permanently inhibit the pipe identification sensor from detecting fire gases. Sources of silicone vapor include 
furniture polish, spray lubricants, and flexible uncured gaskets and sealants.
Avoid installing the detector in areas that have elevated levels of organic chemical vapors such as alcohol, as this will affect the baseline of the channel identification sensors. Other 
gases known to have an effect on MOS sensors that FAAST XT PRO uses for identifying the smoke in individual inlets, are oxidizing agents such as chlorine, ozone, nitrogen oxides. 
While these gases will not permanently damage the sensors and will not have an impact on the overall smoke detection, they may impair the ability to identify the inlet affected by 
smoke. 

GENERAL WARNINGS

SYSTEM POWERING

The following procedure describes how to initially power up the FAAST XT PRO 
system.

1.  Unplug the unit’s power connector to the unit before turning on the 

power.

2.  Turn on the power.
3.  Check the voltage at the connector. Make sure it is within the required 

voltage range.

4.  If wiring is not connected to the external monitor terminal, install a 

47k

 resistor (provided with the unit) into the terminal block and fit it 

into the T6 terminal.

5.  If the voltage is within the proper range, reconnect the power connector 

to the unit.

6.  Verify the system fan starts up and air begins to flow out of the exhaust 

port. The user interface will provide the device status.

7.  Connect a computer, with PipeIQ installed, to the unit using either the 

USB connection on the front of the device, or the Ethernet port located in 
the left side wiring door. (See ‘Connecting to FAAST XT PRO’ for detailed 
connection instructions.)

8.  Use the PipeIQ software to set up the unit configuration required for the 

particular application.

9.  The PC may now be disconnected unless a permanent networked con-

nection is desired. 

10.    The device will establish an airflow baseline during the first five minutes 

of operation after powering on, following the successful download of a 
configuration to the device from PipeIQ, or after initiating Baseline Reset 
from Functions menu on the unit’s display. During the initial baseline 
period the LCD will display Baseline message. 

 

 The calculated baseline is stored in the device’s non-volatile memory and 
is used to monitor changes in the system’s airflow that may be caused 
my dust build up, broken piping, clogged holes, etc. Therefore, it is im-
portant to verify that the system is setup and installed per the PipeIQ 
design file and meets the requirement of the local codes and authorities.

 

 The Baseline message is also displayed after power on reset, following 
the initial baseline period. During the five minutes after power up the 
device is monitoring the system to determine the current airflow baseline 
of the system. Once the current airflow baseline is established, it is com-
pared to the initial baseline stored in non-volatile memory to determine 
the overall health of the system.

firealarmresources.com

Содержание 9440X FAAST

Страница 1: ...ce and select Connect Device 5 Select Admin and enter the password the default password is pass word then click Connect 6 Upon connection a green dot will appear on the device icon in the navi gation tree CONNECTING TO FAAST XT PRO VIA ETHERNET Default Device IP Configuration IP Address 192 168 1 10 Subnet Mask 255 255 255 0 Default Gateway 192 168 1 1 Primary DNS 0 0 0 0 Secondary DNS 0 0 0 0 CON...

Страница 2: ...ATTENTION Detailed pipe network information and best practices can be found in the Pipe Installation Guide available for download at systemsensor com faast The input and output ports are designed to accept nominal one inch pipe 25mm The input and output ports are tapered to provide fast easy pushfit connection of the sampling pipe to the unit Perform the following procedure to connect the air samp...

Страница 3: ...D ALARM CONNECTION BLOCK FIGURE 4 FACP WIRING DIAGRAM TABLE 1 TERMINAL DESIGNATIONS TERMINAL BLOCK T1 External Power Powers Aspirating Smoke Detector T2 Not used T3 RS 485 Rx Rx and Tx can be wired in a half duplex configuration T4 RS 485 Tx Rx and Tx can be wired in a half duplex configuration T5 Alert Relay Maintains state on loss of power T6 Action1 Relay Maintains state on loss of power T7 Act...

Страница 4: ...INFORMATION The use of all FAAST products configuration design use and maintenance must be performed in accordance with the technical documentation General Terms and Conditions and local regulations and or directives for design installation and maintenance of fire alarm systems Product Manuals User Guides White Papers CAD Drawings Datasheets Engineering specifications are available from www system...