I56-6500-000 

 

 10-05

SPECIFICATIONS

Electrical Characteristics

External Supply Voltage  

18 – 30 VDC

Remote Reset Time  

External monitor must be pulled low for a minimum of 100 msec

Power Reset  

1 sec

Relay Contact Ratings  

3.0A @ 30VDC, 0.5A @125VAC

Environmental Ratings

Operating Temperature  

32°F (0°C) to 100°F (38°C) – Factory tested to 131F (55C)

Sampled Air Temperature  

-4°F (-20°C) to 140°F (60°C) 

Humidity  

10 to 95% non-condensing 

IP Rating  

IP30

9440X FAAST

Fire Alarm Aspiration Sensing Technology

®

INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-65

00-000

3825 Ohio Avenue, St. Charles, Illinois 60174

1.800.SENSOR2; Fax: 630.377.6495

www.systemsensor.com

The purpose of this document is to provide practical information for 
mounting and connecting to FAAST XT PRO. For full product informa-
tion, which includes installation guidelines, instructions for safe use, 
smoke sector identification procedures, and warranty and safety informa-
tion, refer to the FAAST XT PRO Comprehensive User Guide available at  
systemsensor.com/iFAASTXTPROuserguide or by scanning the QR code.

ITEMS INCLUDED WITH UNIT

•  FAAST XT PRO (9440X) unit
•  Mounting bracket and hardware
•  Installation and Maintenance Instructions
•  USB interface cable
•  PipeIQ® software, comprehensive manual, and other helpful documents 

may be downloaded at systemsensor.com/faast

CONNECTING TO FAAST XT PRO

FAAST XT PRO requires a configuration download from PipeIQ in order to ini-
tialize. This connection can be achieved using either the USB port located on 
the front of the device, or the Ethernet port located inside the wiring cabinet.

CONNECTING TO FAAST XT PRO VIA USB

NOTE: In order to connect your computer to the FAAST XT PRO using a USB 
connection, a USB driver must first be installed. The driver installation oc-
curs during the installation of PipeIQ version 2.0 or later. Once the driver is 
installed, connect to the device using the following steps.

1.  Launch PipeIQ. (Download from systemsensor.com/faast.)

2.  Create a new project and select FAAST XT PRO device, or open an existing 

project.

3.  Expand the tree view in the left side navigation pane to reveal the device.
4.  Right click on the device and select ‘Connect Device’.
5.  Select ‘Admin’ and enter the password – the default password is ‘pass-

word’ – then click ‘Connect’.

6.  Upon connection, a green dot will appear on the device icon in the navi-

gation tree.

CONNECTING TO FAAST XT PRO VIA ETHERNET

Default Device  

IP Configuration

IP Address:  

192.168.1.10

Subnet Mask:  

255.255.255.0

Default Gateway:   192.168.1.1
Primary DNS:  

0.0.0.0

Secondary DNS:   0.0.0.0

CONFIGURE YOUR PC

Your PC will need to be sitting on the same local area network as the FAAST XT 
PRO device in order to establish communication. Change your PC’s IP address 
to 192.168.1.15 by:

1.  Accessing your network setting in your PC’s control panel.
2.  Open ‘Local Area Connection’ settings and select ‘Properties’. 

3.  Select ‘Internet Protocol Version 4 (TCP/IPv4) and then select ‘Properties’.

4.  Select ‘Use the following IP address and enter 192.168.1.15. If the sub-

net mask does not automatically populate, enter 255.255.255.0 into the 
subnet mask field.

5.  Click OK, and close out of the network menus.

Important Note:

 Before changing your PC’s IP address, be sure to take note of 

whether your IP is currently dynamically set, or is a static IP address. If your PC is 
assigned a static IP address, make note of the IP address and subnet mask so that 
you can change back to the proper settings after the FAAST XT PRO is configured.

CONNECT USING PIPEIQ

1.  Launch PipeIQ. (Download from systemsensor.com/faast.)
2.  Create and save a new project, or open an existing project.
3.  Expand the tree view in the left side navigation pane to reveal the device
4.  Right click on the device and select ‘Connect Device’.
5.  Select Host/IP and type in the device’s IP address - default is 192.168.1.10.
6.  Select ‘Admin’ and enter the password – the default password is ‘pass-

word’ – then press ‘Connect’.

7.  Upon connection, a green dot will appear on the device icon in the navi-

gation tree.

INSTALLATION

This equipment must be installed in accordance with all local and national 
codes and regulations.

PIPE INSTALLATION

The pipe layout is designed using the PipeIQ software package. Refer to the 
Comprehensive Instruction Manual to design the pipe network. All pipe must 
be installed in accordance with local and national codes and regulations. The 
pipe network should be complete before proceeding with the physical and 
electrical system installation.

firealarmresources.com

Содержание 9440X FAAST

Страница 1: ...ce and select Connect Device 5 Select Admin and enter the password the default password is pass word then click Connect 6 Upon connection a green dot will appear on the device icon in the navi gation tree CONNECTING TO FAAST XT PRO VIA ETHERNET Default Device IP Configuration IP Address 192 168 1 10 Subnet Mask 255 255 255 0 Default Gateway 192 168 1 1 Primary DNS 0 0 0 0 Secondary DNS 0 0 0 0 CON...

Страница 2: ...ATTENTION Detailed pipe network information and best practices can be found in the Pipe Installation Guide available for download at systemsensor com faast The input and output ports are designed to accept nominal one inch pipe 25mm The input and output ports are tapered to provide fast easy pushfit connection of the sampling pipe to the unit Perform the following procedure to connect the air samp...

Страница 3: ...D ALARM CONNECTION BLOCK FIGURE 4 FACP WIRING DIAGRAM TABLE 1 TERMINAL DESIGNATIONS TERMINAL BLOCK T1 External Power Powers Aspirating Smoke Detector T2 Not used T3 RS 485 Rx Rx and Tx can be wired in a half duplex configuration T4 RS 485 Tx Rx and Tx can be wired in a half duplex configuration T5 Alert Relay Maintains state on loss of power T6 Action1 Relay Maintains state on loss of power T7 Act...

Страница 4: ...INFORMATION The use of all FAAST products configuration design use and maintenance must be performed in accordance with the technical documentation General Terms and Conditions and local regulations and or directives for design installation and maintenance of fire alarm systems Product Manuals User Guides White Papers CAD Drawings Datasheets Engineering specifications are available from www system...

Отзывы: