background image

  

I56-6500-000 

 

 10-05

PHYSICAL UNIT INSTALLATION

WARNING

Make sure that there are no pipes or electrical wires within the wall before 
drilling any mounting holes

SECURING THE MOUNTING BRACKET

The typical mounting location for the FAAST XT PRO unit is on the wall. The 
unit is mounted to the wall using the enclosed mounting bracket. Figure 1 
shows the wall mounting bracket. For easier access to the FAAST XT PRO 
unit, it is preferred to position the mounting bracket in an easily accessible 
location.

1.  Place the mounting bracket on the wall in the desired location and use it 

as a template to locate the necessary mounting holes.

2.  Mark the hole locations and remove the bracket. It is recommended to 

secure the bracket using the 3 outer mounting holes.

3.  Using a drill and the proper size bit for your mounting hardware, drill 

the necessary holes.

4.  Use appropriate fasteners to accommodate the mounting surface and 

FAAST XT PRO device weight.

5.  Secure the bracket to the wall.

MOUNTING THE DETECTOR TO THE BRACKET

Once the mounting bracket is attached, the unit is ready to be mounted on to 
the bracket. Perform the following procedure to mount the unit.

1.  Before installing the unit onto the bracket, remove the appropriate con-

duit caps from the top or bottom left side of the unit to match the orien-
tation of the wiring.

2.  Line up the unit with the three mounting clips and the mounting studs 

on the left side.

3.  Push the unit down onto the mounting clips and secure it with the sup-

plied washer and nut on the mounting studs protruding through the 
mounting slots shown in Figure 2.

CONNECTING THE AIR SAMPLING PIPE

ATTENTION

Detailed pipe network information and best practices can be found in the Pipe 
Installation Guide, available for download at systemsensor.com/faast

The input and output ports are designed to accept nominal one inch pipe 
(25mm). The input and output ports are tapered to provide fast, easy, pushfit 
connection of the sampling pipe to the unit. Perform the following procedure 
to connect the air sampling pipe to the unit.

1.  Square off and de-burr the end of the sampling pipe. Ensure that the pipe 

is free from any particles that might interfere with the pipe connection.

2.  Remove the input plug from the input port being used (either the top or 

bottom of the unit).

3.  Insert the air sampling pipe into the port, ensuring a snug fit. 

DO NOT 

glue these pipes.

EXHAUST PIPE

The device should always be exhausted in to the space that it is monitoring. 
There are some circumstances where it may be necessary to connect a pipe to 
the exhaust port to divert the exhaust away from the location of the unit. Add-
ing as little as 2ft of exhaust pipe also acts as a muffler for the fan – ensuring 
quieter operation. The output ports are tapered the same as the input ports, to 
provide fast, easy, push-fit connection of an exhaust pipe to the unit. Perform 
the following procedure to connect the exhaust pipe to the unit.

1.  Square off and de-burr the end of the exhaust pipe. Ensure that the pipe 

is free from any particles that might interfere with the pipe connection.

2.  Remove the plug from the exhaust port being used (either the top or 

bottom of the unit).

3.  Insert the air exhaust pipe into the port, ensuring a snug fit. 

DO NOT 

glue these pipes.

FIGURE 1: WALL MOUNTING BRACKET

11.15in (28.3cm)

11.17in (28.4cm)

3.23in (8.2cm)

3.23in (8.2cm)

.300 ± .010 (.76cm ± .3cm)

ASP115-01

FIGURE 2: MOUNTING SLOTS FOR MOUNTING STUDS

ASP116-00

firealarmresources.com

Содержание 9440X FAAST

Страница 1: ...ce and select Connect Device 5 Select Admin and enter the password the default password is pass word then click Connect 6 Upon connection a green dot will appear on the device icon in the navi gation tree CONNECTING TO FAAST XT PRO VIA ETHERNET Default Device IP Configuration IP Address 192 168 1 10 Subnet Mask 255 255 255 0 Default Gateway 192 168 1 1 Primary DNS 0 0 0 0 Secondary DNS 0 0 0 0 CON...

Страница 2: ...ATTENTION Detailed pipe network information and best practices can be found in the Pipe Installation Guide available for download at systemsensor com faast The input and output ports are designed to accept nominal one inch pipe 25mm The input and output ports are tapered to provide fast easy pushfit connection of the sampling pipe to the unit Perform the following procedure to connect the air samp...

Страница 3: ...D ALARM CONNECTION BLOCK FIGURE 4 FACP WIRING DIAGRAM TABLE 1 TERMINAL DESIGNATIONS TERMINAL BLOCK T1 External Power Powers Aspirating Smoke Detector T2 Not used T3 RS 485 Rx Rx and Tx can be wired in a half duplex configuration T4 RS 485 Tx Rx and Tx can be wired in a half duplex configuration T5 Alert Relay Maintains state on loss of power T6 Action1 Relay Maintains state on loss of power T7 Act...

Страница 4: ...INFORMATION The use of all FAAST products configuration design use and maintenance must be performed in accordance with the technical documentation General Terms and Conditions and local regulations and or directives for design installation and maintenance of fire alarm systems Product Manuals User Guides White Papers CAD Drawings Datasheets Engineering specifications are available from www system...

Отзывы: