PROGRAMMING

To load network parameters into the RF sensor, it is necessary to 

link the RF gateway and the RF sensor in a configuration operation. 

At  commissioning  time,  with  the  RF  network  devices  powered 

on, the RF gateway will connect and program them with network 

information as necessary. The RF sensor then synchronises with 

its other associated devices as the RF mesh network is created by 

the gateway. (For further information, see the 

Radio Programming 

and Commissioning Manual

 - ref. D200-306-00.)

LED INDICATORS AND FAULT DESCRIPTION

The radio sensor has two LED indicators that show the status of 

the device.

4c

NOTE POLARITY

4a

Figure 4: Battery Installation 

and Rotary Address Switches

4d

4b

TESTING
Magnet Test

A correctly positioned test magnet will generate an alarm. Position 

the magnet (M02-04-00) as shown in Figure 5, after identifying the 

straight line ridge on the sensor base. To aid positioning, the sensor 

LEDs will turn on green for 1s when the alarm switch activates.

Direct Heat Testing (Hair dryer of 1000-1500 watts). 

Aim the heat toward the sensor from the side. Keep the heat source 

about 15 cm away to prevent damage to the cover during testing. 

The  sensor  should  signal  an  alarm  to  the  CIE  via  the  Gateway 

when the temperature at the sensor reaches 58°C.
Following testing, reset the alarm indication at the CIE (fire panel).

CLEANING

Use  a  vacuum  cleaner  and/or  clean,  compressed  air  to  remove 

dust and debris from the thermistor  and sensor cover as required 

(take care to avoid damaging the thermistor).

Note

When replacing batteries, all 4 will need to be replaced

LIMITATIONS OF HEAT SENSORS

These heat sensors will only work when connected to a compatible 

control panel. Heat detectors have operating limitations. They will 

not sense fires where heat does not reach the sensor, and may 

respond differently to varying heat conditions. Consideration must 

be given to the environment when selecting and siting fire sensors.
Heat sensors cannot last forever, and we recommend replacement 

after 10 years.

Figure 5: Test Magnet Position

+

+

+

+

1

2

3

4

LINE

ON BASE

TEST 

MAGNET

ROTARY ADDRESS SWITCHES

+

Sensor  Status LEDs 

Sensor Status 

LED State 

Meaning 

Power-on initialisation  
(no fault) 

Long Green pulse 

Device is un-commissioned 
(factory default)  

3 Green blinks 

Device is commissioned 

Fault 

Blink Amber every 1s. 

Device has an internal trouble 

Un-commissioned  

Red/Green double-blink every 14s  
(or just Green when communicating). 

Device is powered and is waiting to be 

programmed. 

Sync 

Green/Amber double-blink every 14s 
(or just Green when communicating). 

Device is powered, programmed and 

trying to find/join the RF network. 

Normal

Controlled by panel; can be set to Red 

ON, periodic blink Red or OFF. 

RF communications are established; 

device is working properly. 

Idle (low power mode)  Amber/Green double-blink every 14s 

Commissioned RF network is in standby; 

used when the gateway is powered off. 

Magnet test 

1s green pulse when test magnet 

activates the internal switch. 

Device signals Alarm, all delays are 

removed for 10 minutes. 

Patents Pending

NOTE

Do not run more than 

one interface at a 

time to commission 

devices in an area.

EN54-25: 2008 / AC: 2010 / AC: 2012 Components Using Radio 

Links.  EN54-5: 2000 / A1: 2002 Class A1S and A1R Heat Detectors

for use in fire detection and fire alarm systems for buildings.

0333 16

52051E-RF  DOP-IRF003

52051RE-RF  DOP-IRF004

System Sensor Europe, Life Safety Distribution GmbH

Javastrasse 2, 8604 Hegnau, Switzerland

EU Declaration of Conformity

Hereby, 

Life Safety Distribution GmbH declares 

that the 

radio equipment types

 52051E-RF and 52051RE-RF 

are 

in compliance

 with directive 2014/53/EU

The full text of the EU DoC can be requested from:

[email protected]

Содержание 52051E-RF

Страница 1: ...the sensor from the base without the use of a tool See Figures 3a and 3b for details on this Head Removal Warning An alert message is signalled to the CIE via the Gateway when a head is removed from...

Страница 2: ...ors have operating limitations They will not sense fires where heat does not reach the sensor and may respond differently to varying heat conditions Consideration must be given to the environment when...

Страница 3: ...tensile Vedere le figure 3a e 3b per altre informazioni Avviso di rimozione del sensore Un messaggio di avviso viene trasmesso al pannello di controllo tramite il gateway quando un sensore viene rimos...

Страница 4: ...collocazione dei sensori antincendio occorre tenere in considerazione le caratteristiche dell ambiente in cui verranno installati I rivelatori anti incendio non durano indefinitamente Se ne consiglia...

Страница 5: ...cabeza se quita de su base la central CIE recibe un mensaje de alerta mediante la pasarela La figura 4 muestra la instalaci n de la bater a y la ubicaci n de los selectores giratorios de direcci n Co...

Страница 6: ...mbiente al seleccionar y colocar sensores de fuego Los sensores t rmicos no duran para siempre Recomendamos sustituirlos cada 10 a os Figura 5 Posici n del im n de prueba 1 2 3 4 L NEAENLABASE IM NDEP...

Страница 7: ...elders Bei Entfernen des Melders aus dem Sockelgeht berdasGatewayeineSt rungsmeldungandieBrandmeldeanlage Abbildung 4 zeigt die Batterieinstallation und die Position der Adressdrehschalter Wichtig Die...

Страница 8: ...Sensor erreicht und k nnen au erdem unterschiedlich auf die verschiedenen W rmearten reagieren Bei der Auswahl und Anbringung von Rauchsensoren die Umgebungsbedingungen beachten W rmesensoren halten n...

Страница 9: ...a et 3b Alerte Retrait T te Un message d alerte est signal la centrale via l interface lorsque la t te d un d tecteur est retir e de son socle Se reporter la Figure 4 pour plus de d tails sur l instal...

Страница 10: ...t pas des feux couvant si la chaleur ne les atteint pas Les d tecteurs thermiques ont aussi des limitations Tenir compte de l environnement pour s lectionner les d tecteurs d incendie Les d tecteurs t...

Отзывы: