Page
26
of
32
Burst Flow
Change
Burst detection configuration
parameter
0.2
Significant if > 15
events per week
Flow Mode
See Table 1: Flow Meter Modes.
0
Significant if > 15
events per week
SMS Transient
Alerts
Send an SMS when a pressure
transient is detected.
On
Minimal
SMS Burst
Alerts
Send an SMS alert when a burst is
detected.
On
Minimal
CSQ SMS
Messages
Send 20 SMS messages at 2 minute
intervals after deployment reporting
signal strength
Minimal
Mobile Number
Used for SMS transient alerts and
signal strength reporting at
deployment.
APN Address
APN for data communications on
cellular network.
Username
Username for APN.
Password
Password for APN.
Table 7: Configuration Parameters
7.4
Transient Sensitivity Adjustment
When initially manufactured, the devices are configured with an S3 Sensitivity of 130. This setting is
deliberately conservative to avoid the situation where the devices continually detect transient events on active
pipes.
Once PIPEMINDER-S has been installed for a few days the background S3 score may be evaluated using the
“S3 Value” plot in the graph on
RADAR. In most cases a clear background S3 value can be identified with
occasional event spikes; the S3 sensitivity should be set midway between these two.
The resulting number of transient events identified per day can vary significantly between pipelines but the
situation where transients are continuously detected should be avoided.
When relocating a device, it is important to re-set the S3 Sensitivity back to 130 until the background
knowledge at the new location is developed.