The isolation module is used to reduce potential noise coupling, and match impedances in
the cables between the DCD master shelf and TimeSource 3000. It also converts the 5 MHz
output from a square wave to a sine wave.
The isolation module is installed between the TimeSource 3000 Shelf and the DCD master
shelf. To connect between the module and the DCD Shelf, two 2 foot long RG-59/U, 75 ohm
coax cables are provided.
If an isolator kit is not required, the following cable options are available:
•
Remote oscillator cable kit (093-72001-01) includes:
-
Remote oscillator cables (2) (160-00201-06)
-
Right-angle BNC connector adapters (4)
•
Remote oscillator cable (160-00201-06)