188
TimeSource 3000
Troubleshooting
097-72000-02 Issue 6: October 2003
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
5
Troubleshooting with Error Messages
Use the information in Table M to troubleshoot the system based on the condition
description (conddescr) parameter in a message.
Note:
If only the character "C" is displayed on the terminal every few seconds, the
TimeSource 3000 system has restarted with corrupt software. Download and install the
system software again, using the procedure in the Software Release Document that came
with the software.
Table M. Message Troubleshooting
Message
Meaning
Action
CRITICAL ALARMS
HARDWARE
FAULT
A failure has been detected on
the shelf hardware.
Replace the plug-in card.
MAJOR ALARMS
HOLDOVER
All inputs (GPS signal, span
inputs, and remote oscillator
inputs) are lost or unacceptable,
and the system is now using the
internal oscillator.
Troubleshoot the GPS, SPAN x, and RO x
error messages (check the cable, source,
etc.)
MINOR ALARMS
BATTERY x FAIL
The specified –48 V battery
input has failed.
Troubleshoot, and repair, the specified
–48 V battery input.
BT3 WARMUP
The system is in a power-up
state when it should not be.
Perform the same action as shown in
GPS ERROR message.
DEVICE
DOWNLOAD
REQUIRED
The hardware device software is
corrupt or missing.
Download and install the appropriate
hardware device (DEV) software, using
the procedure in the Software Release
Document that came with the software.
Содержание TimeSource 3000
Страница 1: ...TimeSource 3000 GPS Primary Reference Source 097 72000 02 Issue 6 October 2003 ...
Страница 47: ...3 Chapter Installation This chapter provides the steps required for installation and power up ...
Страница 107: ...Chapter 4 TL1 Reference This chapter provides information for using the TL1 language ...
Страница 203: ...Chapter 6 Specifications This chapter provides equipment specifications ...