background image

Note: A setting of “999” in this position will disable single phasing and  

          voltage unbalance protection.

Percent Unbalance =

Maximum Deviation from the Average

Average

x 100

Example: The measured line-to-line voltages are 203, 210, and 212.

Average =

569

+

 572

+

 578

3

=

 57

3

The maximum deviation from the average is the largest difference

between the average voltage (

573

) and any one voltage reading.

573

-

 569

=

 4     573

-

 572

= 1

     578

-

 573

=

 5

The maximum deviation from the average is 5.

5

57

3

x 100 =

 0

.

87

% Unbalance

MULT-

“MULT” is the multiplication factor for determining true current settings   

           based on current transformer ratio of external CTs.  The appropriate 

           number can be determined from Table No. 1 on page 2. “MULT” must be  

           correctly programmed in order to accurately program the current settings.

OC-

   Represents the manufacturer’s maximum Service Factor Amperage (SFA).  

          The “OC” (overcurrent) setting depends on many factors such as motor  

          usage, motor size, environmental factors and tolerance of the motor.  The  

          motor manufacturer should be consulted for “OC” settings.  However, “OC” 

          is typically between 110% and 125% of Full Load Amperage (FLA).

UC-

   The “UC” (undercurrent) setting is typically set to 80% of full load 

          amperage (FLA).  The overload relay with a “UC” setting of 80% of FLA  

          will typically detect a loss of load for many pumps and motors such as 

          a dry well condition for submersible pumps.  The “UC” setting may be set  

          to 0.00 to disable undercurrent (loss of load) protection.

CUB-

“CUB” is the current unbalance trip point.  Most motor manufacturers 

          recommend operating under no more than 5% current unbalance,  

          therefore, a setting of “5” is a good place to start.  However, your motor  

          manufacturer should be contacted for exact settings.

Note: Current unbalance is calculated the same way as voltage unbalance.

Note: A setting of “999” in this position will eliminate single phasing and  

          current unbalance protection.

TC-

    “TC” designates the trip class for overload protection.  The trip class  

          defines the trip delay when an overload is detected.  Trip class is 

          determined by the type of motor and application.  Your motor manufacturer  

          should be consulted for the proper setting.  Table No. 2 on page 9 shows  

          the trip class and a general description of the applications.

07/25/03 

 

 

 

                 -6-

Содержание 777-575-FT

Страница 1: ...t motor conductor i e the A phase conductor should go through the A round hole See Figure 1 for a typical wiring diagram 2 2 For amperages less than 26 amps loop the motor conductors according to Tabl...

Страница 2: ...IAGRAM FOR 26 90 FLA FULL LOAD AMPS NUMBER OF LOOPS NUMBER OF CONDUCTORS THROUGH A B and C MULT PROGRAM SETTING 2 0 2 5 9 10 10 2 6 3 0 8 9 9 3 1 3 5 7 8 8 3 6 4 0 6 7 7 4 1 5 0 5 6 6 5 1 6 0 4 5 5 6...

Страница 3: ...RMS 600 VAC MAX SYMCOM INC 800 243 8848 RAPID CITY SD IND CONT EQ LISTED 784X LR46510 L1 L2 L3 NO C NC MODEL 777 FT OVERLOAD RELAY 20 90A RESET PROGRAM RD3 RF VUB OC RU ADDR MULT RD2 KWS HV LKW RD1 C...

Страница 4: ...GRAM adjustment is between approximately 7 O Clock and 11 O Clock Likewise the ADDR setting will only be programmed when the DISPLAY PROGRAM adjustment is between approximately 11 O Clock and 5 O Cloc...

Страница 5: ...ection for the application All parameters are actual values except the VUB and CUB settings which are percentages The range these parameters can be programmed to is found in the specifications at the...

Страница 6: ...consulted for OC settings However OC is typically between 110 and 125 of Full Load Amperage FLA UC The UC undercurrent setting is typically set to 80 of full load amperage FLA The overload relay with...

Страница 7: ...rip mode TC J00 the RD1 position becomes the motor acceleration time To view and adjust MA TC must be J00 The motor acceleration time is related to the load on a motor For high inertia loads such as f...

Страница 8: ...The following settings are available 0 1 oc1 2 oc2 3 oc3 4 oc4 A and ocA A setting which includes oc will allow the overload relay to automatically reset after an overload fault eg a setting of oc2 w...

Страница 9: ...bled 1 minute after the motor starts and provides a 2 second trip time for motors exceeding 400 SFA regardless of trip class J00 Fast Linear Trip Mode This setting provides an adjustable linear trip t...

Страница 10: ...s that 1 start attempt usually clears the sand out of the impeller RF oc1 UCTD UCTD 10 GF Because it may take several days to get a new pump motor and schedule for maintenance personnel to remove and...

Страница 11: ...label The multi function display also announces system faults such as low voltage high voltage single phasing unbalance and reverse phasing errors Any time the MODE SELECT switch is in the RUN positio...

Страница 12: ...img down RD2 before restarting Display alternates uc with RUN The overload relay has tripped on undercurrent and is timing down RD3 before restarting If undercurrent is not a normal condition for this...

Страница 13: ...computer Control and monitoring is also possible from SymCom s RM 1000 and RM 2000 PLC and SCADA systems using the RS 485 standard and MODBUS protocol can also be used NOTE An RS 485MS 2W module is r...

Страница 14: ...ust the Display Program adjustment until cLr appears on the display Release the Reset Program Button To verify the last fault was cleared place the Mode Select switch in the Run position Then press an...

Страница 15: ...urrent 15 Timing 5 1 second Repeatability Voltage 0 5 of nominal voltage Current 1 of nominal current TRIP TIMES Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpo...

Страница 16: ...Compliance to a Level of 6 KV Line to Line Hi Potential Test Meets UL508 2 x Rated Voltage 1000 Volts for 1 Minute Vibration IEC 68 2 6 10 55 Hz 1 mm Peak to Peak 2 Hours 3 Axis Shock IEC 68 2 27 30...

Страница 17: ...h 0 315 Seconds RD2 Motor Cool Down Timer 2 500 Minutes x 0 5 if TC J00 OCTD Overcurrent Trip Delay Linear 2 250 x 0 158 0 315 Seconds RD3 Dry Well Recovery Timer 2 500 Minutes x 0 5 if TC J00 RU Numb...

Страница 18: ...DISPLAY MESSAGE RESET PROGRAM 800 843 8848 SYMCOM INC RAPID CITY SD DIMENSIONS 07 25 03 18...

Страница 19: ...sions 18 Fast Linear Trip Mode 5 Multi Function System Display 11 Operation 2 Programmable Operationg Points 17 Programming Examples 9 Programmable Parameters 5 Programming 4 Remote Reset 13 Specifica...

Страница 20: ...2880 North Plaza Drive Rapid City SD 57702 Phone 800 843 8848 or 605 348 5580 FAX 605 348 5685 Visit our website at www symcom com for our complete catalog and new product listings...

Отзывы: