SymCom warrants its microcontroller based products against defects in material or workmanship 

for a period of five (5) years* from the date of manufacture.  All other products manufactured by 

SymCom shall be warranted against defects in material and workmanship for a period of two (2) 

years from the date of  manufacture.  For complete information on warranty, liability, terms, and 

conditions, please refer to the SymCom Terms and Conditions of Sale document.

* The 520 Series has a one (1) year warranty and the LSRU series has a two (2) year warranty.

CLEARING LAST FAULT

The last fault stored can be cleared on the unit.  This procedure is outline

d

 as 

follows:

 

1. Rotate the Mode Select Switch to GF .

 

2. Press and hold the Reset/Program Button. Adjust the Display/Program  

 

    adjustment until cLr appears on the display. Release the Reset/ 

 

    Program Button.

To verify the last fault was cleared, place the Mode Select switch in the Run 

position. Then press and hold the Reset/Program Button, cLr should be on the 

display.

TAMPER GUARD

The unit can be protected from unauthorized program changes by locking in the 

setpoints.

This procedure is outline

d

 as follows:

 

1. Rotate the Mode Select switch to GF .

 

2. Rotate Display/Program adjustment fully clockwise.

 

3. Press and hold the Reset Button. Adjust the Display/Program   

 

    adjustment until Loc appears in the display.

 

4. Release the Reset Button.

 

5. Turn Mode Select switch to run .

 

The program is now locked, but all settings can be viewed. The unit can be 

unlocked by following the procedure above except step three. This step should 

say: Press and hold the Reset Button. Adjust the Display/Program adjustment 

until unL appears in the display.

07/25/03 

 

 

 

                 -14-

Содержание 777-575-FT

Страница 1: ...t motor conductor i e the A phase conductor should go through the A round hole See Figure 1 for a typical wiring diagram 2 2 For amperages less than 26 amps loop the motor conductors according to Tabl...

Страница 2: ...IAGRAM FOR 26 90 FLA FULL LOAD AMPS NUMBER OF LOOPS NUMBER OF CONDUCTORS THROUGH A B and C MULT PROGRAM SETTING 2 0 2 5 9 10 10 2 6 3 0 8 9 9 3 1 3 5 7 8 8 3 6 4 0 6 7 7 4 1 5 0 5 6 6 5 1 6 0 4 5 5 6...

Страница 3: ...RMS 600 VAC MAX SYMCOM INC 800 243 8848 RAPID CITY SD IND CONT EQ LISTED 784X LR46510 L1 L2 L3 NO C NC MODEL 777 FT OVERLOAD RELAY 20 90A RESET PROGRAM RD3 RF VUB OC RU ADDR MULT RD2 KWS HV LKW RD1 C...

Страница 4: ...GRAM adjustment is between approximately 7 O Clock and 11 O Clock Likewise the ADDR setting will only be programmed when the DISPLAY PROGRAM adjustment is between approximately 11 O Clock and 5 O Cloc...

Страница 5: ...ection for the application All parameters are actual values except the VUB and CUB settings which are percentages The range these parameters can be programmed to is found in the specifications at the...

Страница 6: ...consulted for OC settings However OC is typically between 110 and 125 of Full Load Amperage FLA UC The UC undercurrent setting is typically set to 80 of full load amperage FLA The overload relay with...

Страница 7: ...rip mode TC J00 the RD1 position becomes the motor acceleration time To view and adjust MA TC must be J00 The motor acceleration time is related to the load on a motor For high inertia loads such as f...

Страница 8: ...The following settings are available 0 1 oc1 2 oc2 3 oc3 4 oc4 A and ocA A setting which includes oc will allow the overload relay to automatically reset after an overload fault eg a setting of oc2 w...

Страница 9: ...bled 1 minute after the motor starts and provides a 2 second trip time for motors exceeding 400 SFA regardless of trip class J00 Fast Linear Trip Mode This setting provides an adjustable linear trip t...

Страница 10: ...s that 1 start attempt usually clears the sand out of the impeller RF oc1 UCTD UCTD 10 GF Because it may take several days to get a new pump motor and schedule for maintenance personnel to remove and...

Страница 11: ...label The multi function display also announces system faults such as low voltage high voltage single phasing unbalance and reverse phasing errors Any time the MODE SELECT switch is in the RUN positio...

Страница 12: ...img down RD2 before restarting Display alternates uc with RUN The overload relay has tripped on undercurrent and is timing down RD3 before restarting If undercurrent is not a normal condition for this...

Страница 13: ...computer Control and monitoring is also possible from SymCom s RM 1000 and RM 2000 PLC and SCADA systems using the RS 485 standard and MODBUS protocol can also be used NOTE An RS 485MS 2W module is r...

Страница 14: ...ust the Display Program adjustment until cLr appears on the display Release the Reset Program Button To verify the last fault was cleared place the Mode Select switch in the Run position Then press an...

Страница 15: ...urrent 15 Timing 5 1 second Repeatability Voltage 0 5 of nominal voltage Current 1 of nominal current TRIP TIMES Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpo...

Страница 16: ...Compliance to a Level of 6 KV Line to Line Hi Potential Test Meets UL508 2 x Rated Voltage 1000 Volts for 1 Minute Vibration IEC 68 2 6 10 55 Hz 1 mm Peak to Peak 2 Hours 3 Axis Shock IEC 68 2 27 30...

Страница 17: ...h 0 315 Seconds RD2 Motor Cool Down Timer 2 500 Minutes x 0 5 if TC J00 OCTD Overcurrent Trip Delay Linear 2 250 x 0 158 0 315 Seconds RD3 Dry Well Recovery Timer 2 500 Minutes x 0 5 if TC J00 RU Numb...

Страница 18: ...DISPLAY MESSAGE RESET PROGRAM 800 843 8848 SYMCOM INC RAPID CITY SD DIMENSIONS 07 25 03 18...

Страница 19: ...sions 18 Fast Linear Trip Mode 5 Multi Function System Display 11 Operation 2 Programmable Operationg Points 17 Programming Examples 9 Programmable Parameters 5 Programming 4 Remote Reset 13 Specifica...

Страница 20: ...2880 North Plaza Drive Rapid City SD 57702 Phone 800 843 8848 or 605 348 5580 FAX 605 348 5685 Visit our website at www symcom com for our complete catalog and new product listings...

Отзывы: