ELECTRICAL
Input Voltage
475
-
600
VAC, 3
∅
Nominal
Frequency
50
/
60 Hz
Motor Full Load Amp Range
2-25 amps 3
∅
(loops required)
25-90 amps 3
∅
(direct)
80-800 amps 3
∅
(External CTs)
Power Consumption
10 W (Maximum)
Output Contact Rating SPDT (Form C)
Pilot Duty Rating: 480 VA @ 240 VAC
General Purpose: 10 A @ 240 VAC
Expected Life
Mechanical
1 x 10
6
Operations
Electrical
1 x 10
5
Operations at rated load
Accuracy at 25
o
C (77
o
F)
Voltage
±1%
Current
±3% plus CT accuracy
GF Current
±15%
Timing
5% ±1 second
Repeatability
Voltage
±0.5% of nominal voltage
Current
±1% of nominal current
TRIP TIMES (Those not shown have user selectable trip times)
Ground Fault
Trip Time
101-200% of Setpoint
8 Seconds ±1 Second
201-300% of Setpoint
4 Seconds ±1 Second
301-400% of Setpoint
3 Seconds ±1 Second
401% or Greater of Setpoint
2 Seconds ±1 Second
Current Unbalance
Trip Time
1% Over Setpoint
30 Seconds
2% Over Setpoint
15 Seconds
3% Over Setpoint
10 Seconds
4% Over Setpoint
7.5 Seconds
5% Over Setpoint
6 Seconds
6% Over Setpoint
5 Seconds
10% Over Setpoint
3 Seconds
15% Over Setpoint
2 Seconds
SAFETY MARKS
UL
UL508, UL1053
-15-
07/25/03
SPECIFICATIONS