background image

PROGRAMMING

1. Select the feature to program by 

    rotating the “MODE SELECT” switch

    to the desired position.  The “MULT” 

    setting must be programmed before

    any of the current settings to ensure

    proper display of actual current 

    setpoints.  Therefore, SymCom 

    recommends programming the “LV” 

    setting first, then move clockwise 

    through the postions to complete the

    process.  

2. Push and hold the RESET / PROGRAM button.

3. Rotate the DISPLAY / PROGRAM adjustment  to the desired setting of the  

    feature as shown in the LED display.

4. Release the RESET / PROGRAM button.  The unit is programmed when the  

     button is released.

5. Continue steps 1-4 until all features are programmed.

NOTE:

  Some “MODE SELECT” positions are dual function such as the 

 

“#RU / ADDR” position.  When the “MODE SELECT” switch is pointed  

 

at “#RU / ADDR,” you may view and program “#RU” and “ADDR.”  To 

 

view the two settings rotate the “DISPLAY / PROGRAM” adjustment  

             across its entire range.  You will see the “#RU” setting when the 

 

“DISPLAY / PROGRAM” adjustment is between approximately 7 O’Clock  

 

and 11 O’Clock.  You will see the “ADDR” setting

  

when the “DISPLAY/PROGRAM”adjustment is between approximately 

 

11 O’Clock and 5 O’Clock.  To program “#RU” or “ADDR,” follow the 

 

programming instructions above.  The “#RU” setting will only be 

 

programmed when the “DISPLAY / PROGRAM” adjustment is between 

             approximately 7 O’Clock and 11 O’Clock.  Likewise, the “ADDR” setting  

 

will only be programmed when the “DISPLAY/PROGRAM”adjustment is 

 

between approximately 11 O’Clock and 5 O’Clock.  “ADDR” settings will  

 

be an “A” followed by a number between 1 and 99.

07/25/03 

 

 

 

                 -4-

Operation

The relay operation of SymCom’s overload relay is a fail safe design.  This 

means when everything is within the limits programmed into the unit, the relay 

will energize; the normally open (NO) contact will close and the normally closed 

(NC) contact will open.  Once the unit has been wired and programmed, the unit 

is ready to operate.  Turn the mode select to the “RUN” position.  The display will 

show “RUN” alternating with some number (the numbers displayed will be the 

number corresponding to where the “DISPLAY/PROGRAM” knob is pointed). It 

will do this for the amount of time programmed into “RD1”.  After this time has 

expired, the relay will energize (normally open will close and normally closed 

contact will open).  If something else is in the display, see the troubleshooting 

section for more information. If the mode select is taken out of the “RUN” 

position, the units relay will de-energize.

L1

L2

L3

NO

C

NC

MODEL 777-FT

OVERLOAD RELAY

DISPLAY MESSAGE

RESET/

PROGRAM

+

V

O

L

T

A

G

E

C U

R

R

E

N

T

RD3

#RF

VUB

OC

#RU/ADDR

MULT

RD2

UTCD

HV

UC

RD1

CUB

GF

LV

TC

RUN

DISPLAY / PROGRAM

MODE SELECT

SYMCOM, INC.

800-843-8848

RAPID CITY, SD

IND. CONT. EQ

LISTED

786X

C

L1-

L2

L2-L3

L3-L

1

AV

G

AVG

A

B

C

Содержание 777-575-FT

Страница 1: ...t motor conductor i e the A phase conductor should go through the A round hole See Figure 1 for a typical wiring diagram 2 2 For amperages less than 26 amps loop the motor conductors according to Tabl...

Страница 2: ...IAGRAM FOR 26 90 FLA FULL LOAD AMPS NUMBER OF LOOPS NUMBER OF CONDUCTORS THROUGH A B and C MULT PROGRAM SETTING 2 0 2 5 9 10 10 2 6 3 0 8 9 9 3 1 3 5 7 8 8 3 6 4 0 6 7 7 4 1 5 0 5 6 6 5 1 6 0 4 5 5 6...

Страница 3: ...RMS 600 VAC MAX SYMCOM INC 800 243 8848 RAPID CITY SD IND CONT EQ LISTED 784X LR46510 L1 L2 L3 NO C NC MODEL 777 FT OVERLOAD RELAY 20 90A RESET PROGRAM RD3 RF VUB OC RU ADDR MULT RD2 KWS HV LKW RD1 C...

Страница 4: ...GRAM adjustment is between approximately 7 O Clock and 11 O Clock Likewise the ADDR setting will only be programmed when the DISPLAY PROGRAM adjustment is between approximately 11 O Clock and 5 O Cloc...

Страница 5: ...ection for the application All parameters are actual values except the VUB and CUB settings which are percentages The range these parameters can be programmed to is found in the specifications at the...

Страница 6: ...consulted for OC settings However OC is typically between 110 and 125 of Full Load Amperage FLA UC The UC undercurrent setting is typically set to 80 of full load amperage FLA The overload relay with...

Страница 7: ...rip mode TC J00 the RD1 position becomes the motor acceleration time To view and adjust MA TC must be J00 The motor acceleration time is related to the load on a motor For high inertia loads such as f...

Страница 8: ...The following settings are available 0 1 oc1 2 oc2 3 oc3 4 oc4 A and ocA A setting which includes oc will allow the overload relay to automatically reset after an overload fault eg a setting of oc2 w...

Страница 9: ...bled 1 minute after the motor starts and provides a 2 second trip time for motors exceeding 400 SFA regardless of trip class J00 Fast Linear Trip Mode This setting provides an adjustable linear trip t...

Страница 10: ...s that 1 start attempt usually clears the sand out of the impeller RF oc1 UCTD UCTD 10 GF Because it may take several days to get a new pump motor and schedule for maintenance personnel to remove and...

Страница 11: ...label The multi function display also announces system faults such as low voltage high voltage single phasing unbalance and reverse phasing errors Any time the MODE SELECT switch is in the RUN positio...

Страница 12: ...img down RD2 before restarting Display alternates uc with RUN The overload relay has tripped on undercurrent and is timing down RD3 before restarting If undercurrent is not a normal condition for this...

Страница 13: ...computer Control and monitoring is also possible from SymCom s RM 1000 and RM 2000 PLC and SCADA systems using the RS 485 standard and MODBUS protocol can also be used NOTE An RS 485MS 2W module is r...

Страница 14: ...ust the Display Program adjustment until cLr appears on the display Release the Reset Program Button To verify the last fault was cleared place the Mode Select switch in the Run position Then press an...

Страница 15: ...urrent 15 Timing 5 1 second Repeatability Voltage 0 5 of nominal voltage Current 1 of nominal current TRIP TIMES Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpo...

Страница 16: ...Compliance to a Level of 6 KV Line to Line Hi Potential Test Meets UL508 2 x Rated Voltage 1000 Volts for 1 Minute Vibration IEC 68 2 6 10 55 Hz 1 mm Peak to Peak 2 Hours 3 Axis Shock IEC 68 2 27 30...

Страница 17: ...h 0 315 Seconds RD2 Motor Cool Down Timer 2 500 Minutes x 0 5 if TC J00 OCTD Overcurrent Trip Delay Linear 2 250 x 0 158 0 315 Seconds RD3 Dry Well Recovery Timer 2 500 Minutes x 0 5 if TC J00 RU Numb...

Страница 18: ...DISPLAY MESSAGE RESET PROGRAM 800 843 8848 SYMCOM INC RAPID CITY SD DIMENSIONS 07 25 03 18...

Страница 19: ...sions 18 Fast Linear Trip Mode 5 Multi Function System Display 11 Operation 2 Programmable Operationg Points 17 Programming Examples 9 Programmable Parameters 5 Programming 4 Remote Reset 13 Specifica...

Страница 20: ...2880 North Plaza Drive Rapid City SD 57702 Phone 800 843 8848 or 605 348 5580 FAX 605 348 5685 Visit our website at www symcom com for our complete catalog and new product listings...

Отзывы: