77
b) Function H2 “VALVE PROTECT”
When controlling an electrically powered heater valve, this func-
tion may help to prevent scale formation in the valve.
If the scale protection function was activated, the connected
consumer is activated daily at 10:00 AM for 1 to 10 minutes (ad-
justable), independently of the respective present programming.
Proceed as follows:
1. After selecting this function H2 “VALVE PROTECT” and con-
fi
rming with “OK” (5), either “OFF” or a number between 1 and
10
fl
ashes.
2. The scaling function can be set accordingly with the buttons
“–” (3) and “+” (2):
“OFF” = scale protection function off
“1”......”10” = Opening duration of the valve in minutes, scale
protection function on
3. Con
fi
rm the setting with “OK” (5).
The room thermostat is then in the previous menu for selec-
tion of functions again.
To leave the menu and return to the regular display, push the
button “MENU” (4), repeatedly if required.
The function should only be activated if the room ther-
mostat controls a suitable consumer.