71
j) Function G10 “SWING SETTING”
To prevent the connected consumer from switch on/off too often,
the hysteresis can be set in the function G10.
The consumer is only activated when a speci
fi
c deviation from
the target temperature is exceeded or undercut (depending on
operating mode H1 (“HEAT OR COOL”).
• Heating mode (“HEAT”)
Example:
Hysteresis = 0.5 °C, programmed temperature = +20.0 °C
Consumer is activated at <= +19.5 °C
Consumer is deactivated at >= +20.5 °C
• Cooling mode (“COOL”)
Example:
Hysteresis = 0.5 °C, programmed temperature = +20.0 °C
Consumer is activated at <= +20.5 °C
Consumer is deactivated at >= +19.5 °C
Proceed as follows:
1. After selecting this function G10 “SWING SETTING” and con-
fi
rming with “OK” (5), the temperature value for setting the
hysteresis
fl
ashes (basic setting is 0.5 °C).
2. Set the hysteresis value (0.2 °C....2.0 °C) with the buttons “–”
(3) and “+” (2).
3. Con
fi
rm the setting with “OK” (5).
The room thermostat is then in the previous menu for selec-
tion of functions again.
To leave the menu and return to the regular display, push the
button “MENU” (4), repeatedly if required.
Observe that a low hysteresis value leads to very fre-
quent activation/deactivation of the consumer!
Содержание TOUCH TX5
Страница 174: ...174 Het merk voor huistechniek voor het hele huis Kijk voor meer informatie op www sygonix com ...
Страница 175: ...175 ...