SycoTec 2002 1053 - IP 20 Скачать руководство пользователя страница 19

 
 

EN

 

19 

Subindex 42 

Subindex 42 refers to the Voltage 3 (P66) of the V/Hz table. 

The value is given from 1…650 in 0.1 V steps; 650 equals 65 V.

 

Index 
(hex) 

Name 

Object type 

Data type 

Access 

PDO 
mapping 

Default 

3000:42 

U3 

Variable 

Unsigned16 

rw 

no 

 

 

Subindex 46 

Subindex 46 refers to the Speed control (P70).  

Bit 3  Bit 2  Bit 1  Bit 0  Display inverter 

No motor active 

Pure speed control active (PMSM only) 

V/Hz control active (DASM only) 

I*R control active (DASM only) 

Load compensation active (DASM only) 

NOTE: See also Operating Manual Operating Software SycoDrive for HF Inverters e

@

syDrive 4624, 4625, 4626. 

 

Index 
(hex) 

Name 

Object type 

Data type 

Access 

PDO 
mapping 

Default 

3000:46 

Regler 

Variable 

Unsigned16 

ro 

no 

 

 

Subindex 47 

Subindex 47 refers to the I*R factor (P71) of the controller. 

The value is given from 1…100 in 0.1 V/A steps; 100 equals 10 V/A.

 

Index 
(hex) 

Name 

Object type 

Data type 

Access 

PDO 
mapping 

Default 

3000:47 

I*R-Faktor 

Variable 

Unsigned16 

rw 

no 

 

 
Subindex 48 

Subindex 48 refers to the Load comp. factor (P72) of the controller. 

The value is given from 0…400 in 0.1 %/A~ steps; 400 equals 40 %/A~.

 

Index 
(hex) 

Name 

Object type 

Data type 

Access 

PDO 
mapping 

Default 

3000:48 

Lastkompensation 

Variable 

Unsigned16 

rw 

no 

 

 

Subindex 49 

Subindex 49 refers to the Filter time (P73) of the I*R and Load compensation. The value is given in s. 

Index 
(hex) 

Name 

Object type 

Data type 

Access 

PDO 
mapping 

Default 

3000:49 

Komp-t_filt 

Variable 

Unsigned16 

rw 

no 

 

 

Subindex 4b 

Subindex 4b refers to the I²t threshold (P75). 

The value is given from 0…1000 in

 0.1 % steps; 

1000 equals 100 %. 

Index 
(hex) 

Name 

Object type 

Data type 

Access 

PDO 
mapping 

Default 

3000:4b 

I2tThd 

Variable 

Unsigned16 

rw 

no 

 

 

 

 

Содержание 2002 1053 - IP 20

Страница 1: ...Object description CANopen EN HF Inverters e syDrive 4624 4625 4626...

Страница 2: ...N This CANopen object description is only valid in connection with the operating manual of HF Inverter e syDrive 4624 4625 4626 material no 2 002 1912 The safety information must be observed before co...

Страница 3: ...meters 10 Object 0x1200 Server SDO Parameter 10 4 1 3 Receive PDO Parameter and Mapping Objects 11 Object 0x1400 Receive PDO Communication Parameter 11 Object 0x1600 Receive PDO Mapping Parameter 11 4...

Страница 4: ...uct as a result of new technical developments are possible This does not imply any right to retrofitting of existing units SycoTec assumes no responsibility for damage arising through use of incorrect...

Страница 5: ...r set x NMT Network management NTC Negative temperature coefficient PC Personal Computer PDO Process Data Object PLC Programmable logic controller PM BL motor Permanent magnet brushless motor PMSM Per...

Страница 6: ...4626 is galvanically isolated An external 24 V DC power supply is required The voltage range is 18 30 V A terminating resistance is not included This terminating resistance 120 Ohm must be connected...

Страница 7: ...device errors that occurred Value Meaning 1 Generic error The generic error is signaled at any error situation Index hex Name Object type Data type Access PDO mapping Default 1001 Error Register Varia...

Страница 8: ...number of the highest supported sub index Subindex 3 can be used to restore the factory defaults for manufacturer parameters Writing the value 0x64616f6c hexadecimal representation of load to this su...

Страница 9: ...s PDO mapping Default 1017 Producer Heartbeat Time Variable Unsigned16 rw no 1000 Object 0x1018 Identity Object This object contains identity information of the devise Subindex 0 gives information abo...

Страница 10: ...an internal device error occurred Value Meaning 0 Enter NMT pre operational state only if current NMT state is operational 1 No NMT state change 2 Enter NMT stopped state NOTE See CiA402 3 Index hex N...

Страница 11: ...event timer of the PDO which defines the time intervals for the cyclic transmission of the PDO Index hex Name Object type Data type Access PDO mapping Default 1400 Receive PDO Communication Parameter...

Страница 12: ...erved by CiA Subindex 5 contains the event timer of the PDO which defines the time intervals for the cyclic transmission of the PDO Index hex Name Object type Data type Access PDO mapping Default 1800...

Страница 13: ...Name Object type Data type Access PDO mapping Default 3000 01 f_soll Variable Unsigned16 ro no Subindex 8 Subindex 8 refers to the Speed display P8 A display of speed in Hz or in rpm can be selected V...

Страница 14: ...al TPDO only Subindex 12 Subindex 12 refers to the Active current P18 corrected by an offset of 25 000 mA It is a display value The value is given in mA Index hex Name Object type Data type Access PDO...

Страница 15: ...X X X X X 1 X X FAILURE X X X X X X X 1 X X X MOTOR ROT X X X X X X 1 X X X X MOTOR STOP X X X X X 1 X X X X X OVERLOAD X X X X 1 X X X X X X SPEED REACHED X X X 1 X X X X X X X CURRENT LIMIT X X 1 X...

Страница 16: ...a type Access PDO mapping Default 3000 24 t_Umrichter Variable Unsigned16 ro optional TPDO only Subindex 25 Subindex 25 refers to the Firmware P37 of the inverter It is a display value Index hex Name...

Страница 17: ...uals 100 s Index hex Name Object type Data type Access PDO mapping Default 3000 33 t_anlauf Variable Unsigned16 rw no Subindex 34 Subindex 34 refers to the Start up current P52 for micro step start up...

Страница 18: ...the V Hz table The value is given in Hz Index hex Name Object type Data type Access PDO mapping Default 3000 3d f1 Variable Unsigned16 rw no Subindex 3e Subindex 3e refers to the Voltage 1 P62 of the...

Страница 19: ...ex 47 Subindex 47 refers to the I R factor P71 of the controller The value is given from 1 100 in 0 1 V A steps 100 equals 10 V A Index hex Name Object type Data type Access PDO mapping Default 3000 4...

Страница 20: ...806ahex Deactivated 806bhex Warning 806chex Motor stop NOTE See also Operating Manual Operating Software SycoDrive for HF Inverters e syDrive 4624 4625 4626 Index hex Name Object type Data type Acces...

Страница 21: ...hex Name Object type Data type Access PDO mapping Default 3000 55 Motorschutz Variable Unsigned16 rw no Subindex 56 Subindex 56 refers to the Resistance value P86 of the temperature monitoring The val...

Страница 22: ...ault 3000 60 mot_polpaarzahl Variable Unsigned16 rw no Subindex 61 Subindex 61 refers to the Input current P97 It is a display value The value is given in 0 1 A steps Index hex Name Object type Data t...

Страница 23: ...2 Bit 1 Bit 0 Input X X X X X X X 1 DIN 1 X X X X X X 1 X DIN 2 X X X X X 1 X X DIN 3 X X X X 1 X X X DIN 4 X X X 1 X X X X DIN 5 X X 1 X X X X X DIN 6 X 1 X X X X X X Temperature monitoring motor 1 X...

Страница 24: ...anual Operating Software SycoDrive for HF Inverters e syDrive 4624 4625 4626 Index hex Name Object type Data type Access PDO mapping Default 3000 6f dig_in_2 Variable Unsigned16 rw no Subindex 70 Subi...

Страница 25: ...ion inverter 0000hex Off 803ehex Reset 803fhex Speed direction 8040hex Motor code bit 3 8041hex Fixed frequency bit 0 8043hex Parameter export NOTE See also Operating Manual Operating Software SycoDri...

Страница 26: ...ndex 79 refers to Relay 2 P121 Value Selection inverter 0000hex Off 804ahex Operation 804bhex Warning 804chex Failure 804dhex Overload 804ehex Nominal speed reached 804fhex Current limit 8050hex Motor...

Страница 27: ...Name Object type Data type Access PDO mapping Default 3000 88 f_fern_max Variable Unsigned16 rw no Subindex 89 Subindex 89 refers to the Maximum voltage P137 of the analog input The value is given fro...

Страница 28: ...oDrive for HF Inverters e syDrive 4624 4625 4626 Index hex Name Object type Data type Access PDO mapping Default 3000 92 drehrichtung Variable Unsigned16 rw no Subindex 95 Subindex 95 refers to the mo...

Страница 29: ...ufacturer specific r reserved oms operation mode specific h stop fr fault reset eo enable operation qs quick stop ev enable voltage so switch on The bits 0 to 9 shall be supported according to the mod...

Страница 30: ...uired speed of the system The value shall be given in Hertz Hz The direction of rotation is determined by the current setting of the parameter object Direction of rotation P146 0x3000 92 in connection...

Страница 31: ...amount Variable Unsigned32 rw optional 6046 02 vl_velocity_min_max _amount_vl_velocity _max_amount Variable Unsigned32 rw optional Object 0x6048 vl_velocity_acceleration This object must indicate the...

Страница 32: ...pe of motor attached to and driven by the drive device The following table specifies the value definition Value Name INV name 0007hex Squirrel cage Induction motor ASM 3 phase 000Bhex Trapezoidal PM B...

Страница 33: ...EN 33 5 0 State Machine The following figure shows the individual states Statusword and commands for changing the states Controlword...

Страница 34: ...ccordingly Control side evaluation of the transmit PDO A receive PDO matching the transmit PDO must be implemented in the controller The received data for the Statusword of the inverters and the curre...

Страница 35: ...have arisen as a result of natural wear and tear improper handling cleaning or maintenance non compliance with the maintenance operating or connecting instructions corrosion impurities in the air supp...

Страница 36: ...EN 002 6929 2019 11 B DE original...

Отзывы: