Trouble shooting
Warning!
The electrical installation must be checked only by expert personnel.
Problem
Cause
Measure
System out of work
Power supply inter-
rupted
Check the power supply.
Cable break
Check the connecting cables for a possible
break of a cable
Defective fuse
Exchange fuse in the field housing
Defective device
Contact SWR
Measuring system
outputs wrong values
Incorrect calibration
Delete input signal correction, new cali-
bration
according to section 6
Calibration shifted by
Abrasion or caking on
front end of sensor
Delete input signal correction, new cali-
bration
according to section 6
Malfunction of sen-
sor
Sensor not properly
connected
Check cable
Sensor damaged
Replace sensor
No 24 VDC supply on
sensor
Assure right power supply
Voltage drop on the
supply
line too highly
Examine cable lengths on the basis of the
table
in chapter 4.5
Relay flickering
Hysteresis too small
Increase hysteresis, check effects caused
by external devices.