5.5 Alarm value
Choose the output value for the alarm (sensor error
or an internal alarm); at the same time the relay 3
drops down. Range of 0 ... 22 mA (Std 3 mA)
With C you set the value to 0.0. With the num-
bers you input the beginning value and with
the input is accepted and you quit
the menu level.
5.6 Filter time
Choose the filter time for the current output in the
range of 0,1 ... 999,9 s (Standard 1 s)
With C you set the value to 0.0. With the num-
bers you input the beginning value and with
the input is accepted and you quit the menu level.
5.7 Calibration: 4mA
Set the minimal current output. Fit to the external
measurement system (at differing display).
Adapt the current output to 4 mA with the keys < <
and >> quickly and with the keys < und > slowly.
With
the input is accepted and you quit the menu level, with C you quit the
menu point without any change.
5.8 Calibration: 20mA
Set the maximal current output. Fit to the external
measurement system (at differing display).
Adapt the current output to 4 mA with the keys < <
and >> quickly and with the keys < und > slowly.
With
the input is accepted and you quit the menu level, with C you quit the
menu point without any change.
6.
Digital inputs
It is only necessary for stopping and starting the
measurement via an external control line (for wir-
ing see 8.1).
With
and
you make a choice according to the display. With C you quit the
menu point without any change and with
the input is accepted and you arrive 1
menu point lower to make your settings.
6.1 Digital input 1
With
and
you make a choice according to
the accentuation. With C you quit the menu point
without any change and with
the input is ac-
cepted and you arrive 1 menu point lower to make
your settings.
Anal. output
7 8
9
Alarm value
4 5
6
3.0
mA
1 2 3
C
0
Anal. output
7 8
9
Filter time
4 5
6
3.0
s
1 2 3
C
0
Anal. output
Calibration 4.0mA
C
<< <
>
>>
Anal. output
Calibration 20.0mA
C
<< <
>
>>
6.Digital inputs
6.1.Digital input 1
6.2.Digital input 2
C
6.1. Dig. input1
6.1.1.Funct.
none
6.1.2.Direct. direct
6.1.3.Filter
1.0s