We reserve the right to alter specifications.
GB.FUNKRXHC.180907
www.swegon.com 7
Damper
actua-
tor
5. Electrical connection of the air recirculation section RX/HC (accessory)
Requisite accessories
Outdoor air damper
TBSA-X-xxx-xxx-x-1
or
TCSA-xxx, spring return
Exhaust air damper
TBSA-X-xxx-xxx-x-1
or
TCSA-xxx spring return
Function
In normal mode the recirculation damper must be fully
closed (deenergized state).
When defrosting is selected, the air recirculation damper
should be completely open (actuating time: 90 seconds).
45
67
89
AB
CDEF
01
23
P1
COM POWER
IQlogic
+
1
2 3
4
5
6 7
8
9 10 11 12
-
+
-
+
-
+
+
-
-
S
-
S
C
13
NO
14
C
15
NO
16
+
17
-
18
+
19
-
20
G
21
G0
22
Com 1
Heat/Cool
Com 2
28
30
G
G0
Y
U
G
G0
31
32
P
G0
G
G0
1
2
1
2
1
2
8
9
G
G0
Communication cable to the control unit of
the air handling unit, where it is connected
to one of the outlets for COM 6-11.
The function
selector switch
must be set to
position 5.
Outdoor air
damper
Exhaust air
damper
Air recirculation
damper
GOLD Control unit
The electrical connections are to be wired by a qualified
electrician in accordance with local electrical safety regu-
lations.
The module is placed
in the electrical cabinet on the
GOLD air handling unit.
The damper motor has a 0.9 metre long connection cable,
4 x 0.75 mm
2
and is connected in the junction box, IP54.