background image

We reserve the right to alter specifications.

GB.FUNKRXHC.180907

www.swegon.com   5

When defrosting is completed, the outdoor air damper 
and the exhaust air damper open, the recirculation 
damper closes and stabilization operations are run. 
In order to reduce the risk of freezing, a termination 
sequence is started at the same time when the recircula-
tion damper is opened and closed a number of times.

Electrical air heater RX/HC (accessory)

When there is a defrosting requirement, the electric air 
heater is enabled immediately.  

Overheating protection is installed. Post-cooling is car-
ried out if the air handling unit stops during or just after 
defrosting.

Critical defrosting

If the evaporation temperature in the heating circuit drops 
below a critical limit, defrosting starts. 

If the control system discovers ongoing ordinary defrost-
ing, critical defrosting is adapted to the ordinary defrost-
ing sequence, e.g. recirculation starts.

3.10 Limitations

For operations outside the outdoor temperature limits 
and/or below air limits, the reversible heat pump function 
stops and the air handling unit acts as a GOLD RX.

Outdoor temperature limit, cooling

Operation of the reversible heat pump in cooling mode 
is only permitted at an outdoor temperature above 15°C 
(adjustable value).

Outdoor temperature limit, heating

Operation of the reversible heat pump in heating mode 
is only permitted at an outdoor temperature above -25°C 
(adjustable value).

Air flow limits

Operation of the reversible heat pump is only permitted 
when the extract airflow and supply airflow exceed a 
minimum airflow limit. Values can be set for the extract air 
and supply air.

3.9 Defrosting

Freezing occurs when operations are in heating mode and 
the temperature across the exhaust coil is below 0 °C.

Depending on the temperature, compressor speed, airflow 
as well as moisture content in the extract air and fresh air, 
freezing occurs with varying speed and behaviour. 

The pressure drop across the exhaust coil is measured 
to detect the defrosting requirement or stop ongoing 
defrosting. Defrosting starts when the pressure drop 
exceeds a specific limit. When the pressure drop falls 
below another lower limit defrosting stops.

At defrosting with recirculation, the recirculation damper 
have a finishing sequence for protection against freezing. 

Phases

Defrosting occurs by reversing the heat pump circuit. The 
exhaust coil then works as a condenser (as with the cool-
ing function) and heats. 

Start delay

 

When the pressure drop across the exhaust air coil exceeds 
the start limit, for a period longer than 60 seconds, 
defrosting starts.

Initiation

 

When defrosting is detected the Initiation phase starts. 
The recirculation damper then opens for recirculation, and 
if there is an electric air heater this starts. For recirculation 
the signal is sent with a delay of 60 seconds, if there is no 
recirculation the signal is sent without a delay.

Pre-defrosting

When the defrosting process starts, a signal is sent to the 
heating circuit which lowers the compressor speed and 
turns the flow directions through the four-way valve. 

Defrosting

 

The defrosting process continues through ramping up the 
compressor speed and running until the control system 
requests that defrosting stops or until the maximum 
defrosting time has been reached. 

Runoff

 

In the last part of the defrosting process, the compressor 
speed drops and the flow directions through the four-way 
valve are turned back. 

Adaptive start and stop 

Start and stop of the defrosting process is controlled by 
calculations in the control system, which take a number 
of different factors into consideration that are measured 
continuously. 

Adaptation is performed after each defrosting to optimise 
the process.   

Air recirculation section RX/HC (accessory)

When there is a defrosting requirement, the recircula-
tion damper opens, and the outdoor air damper and the 
exhaust air damper close. 

Recirculation operation is ensured before defrosting starts. 

Содержание RX/HC

Страница 1: ...ic air heater Option 3 Reversing the media circuit air recirculation section RX HC 1 1 Installation See the separate installation and maintenance instructions to install RX HC See the separate installation instructions to install the air recirculation section RX HC if used 2 Material specification Air handling unit with integrated reversible heat pump GOLD RX HC For defrosting according to option ...

Страница 2: ...rt sequence 3 3 Stop of RX HC air handling unit When stopping the GOLD air handling unit operation of the reversible heat pump is shut down immediately Post cooling of the refrigerant circuit and electric air heater for defrosting if fitted is carried out After cooling is in progress two minutes after the last operation of the compressor or electric air heater 3 4 Temperature regulation The heat p...

Страница 3: ... compressor is regulated to follow the tempera ture requirement At a temperature requirement below 62 5 the speed controlled compressor is run at 25 of max speed and the on off compressor is operational When the temperature requirement decreases below 50 the on off compressor shuts down and the speed controlled compressor is regulated to follow the tempera ture requirement At a temperature require...

Страница 4: ...ry heat exchanger is allowed to regulate to maintain the required supply air temperature If instead the temperature require ment exceeds MIN level operations return to normal mode If any of the following occurs the comfort function is can celled and operation of the reversible heat pump stops Stop of the GOLD air handing unit Time for comfort mode exceeds 30 minutes factory setting can be set 5 30...

Страница 5: ...esh air freezing occurs with varying speed and behaviour The pressure drop across the exhaust coil is measured to detect the defrosting requirement or stop ongoing defrosting Defrosting starts when the pressure drop exceeds a specific limit When the pressure drop falls below another lower limit defrosting stops At defrosting with recirculation the recirculation damper have a finishing sequence for...

Страница 6: ...ntrol card IQlogic Control card iPro cooling circuit control Pressure sensor for pressure drop measurement over the cooling circuit s exhaust air coil function selector switch in D position Temperature sensor for density cor rection of the airflow The sensor is placed between the coil and fan in the exhaust air supply air Temperature sensor for density cor rection of the airflow The sensor is plac...

Страница 7: ... P1 COM POWER IQlogic 1 2 3 4 5 6 7 8 9 10 11 12 S S C 13 NO 14 C 15 NO 16 17 18 19 20 G 21 G0 22 Com 1 Heat Cool Com 2 28 30 G G0 Y U G G0 31 32 P G0 G G0 1 2 1 2 1 2 8 9 G G0 Communication cable to the control unit of the air handling unit where it is connected to one of the outlets for COM 6 11 The function selector switch must be set to position 5 Outdoor air damper Exhaust air damper Air reci...

Страница 8: ...activated by selecting the required accessory from the menu HC defrosting accessory Set the required heating and cooling function standard or comfort Set the required values for outdoor temperature limits for heating and cooling Set the required values for airflow limits for supply air and extract air Calibration is carried out at the factory If recalibration is required this can be carried out by...

Отзывы: